Page 347

Pico GFX-70 Settings

DEBOUNCE

✓

▲

P BUTTONS RUN MODE CARD MODE

Deactivation of Card Mode 1. Select CARD MODE

✓ ▼

7-19

✓.

2. Press OK. The RUN mode function is deactivated. The Pico GFX-70 default setting is for display of the CARD MODE menu, i.e. Pico GFX-70 starts in RUN mode without the memory module when the power is switched on.

Terminal Mode The Pico GFX-70 also supports the TERMINAL MODE. Terminal mode enables the display and the keypad of the GFX to be used as a terminal for operating another device. In this operating mode you are thus able to remotely control all devices supporting Terminal mode operation. The interface to the other device can be implemented using the serial interface or the Pico-Link.

IMPORTANT

TERMINAL MODE operation is only possible if the GFX is in STOP mode.

Permanent TERMINAL MODE Setting In the SYSTEM menu you set the GFX to start in TERMINAL MODE when the power supply is switched on. Switch to the System menu.

IMPORTANT

If Pico GFX-70 is protected by a password, the System menu will not be available until Pico GFX-70 is “unlocked” (see Unlocking Pico GFX-70 on page 7-5).

Publication 1760-UM002B-EN-P - March 2005

Page 348

7-20

Pico GFX-70 Settings

Activating an Automatic Startup in TERMINAL MODE Requirement: The GFX is in RUN or STOP mode without visualization (the System menu must be reachable). P BUTTONS

▲

RUN MODE CARD MODE TERMINAL MODE ✓ ▼

1. Select TERMINAL MODE in the System menu and press OK. 2. The next time that the GFX is started, it will establish the connection to the selected device. 3. Press ESC to return to the Status display.

IMPORTANT

P BUTTONS

▲

RUN MODE

The correct station number must be selected in order for the GFX to start TERMINAL MODE with the correct station. (see Commissioning on page 3-1)

Deactivating an Automatic Startup in TERMINAL MODE 1. Select TERMINAL MODE

✓.

CARD MODE TERMINAL MODE

▼

2. Press OK. The automatic starting in TERMINAL MODE has been deactivated. The default setting of the GFX is for the display of the TERMINAL MODE menu, i.e. GFX starts in RUN or STOP mode when the power is switched on.

Setting LCD Contrast and Backlight

The backlight of the LCD display can be set to one of five stages to adapt it to local conditions. The display contrast can be set to one of five stages. The contrast and backlight settings are implemented as device settings. 1. Switch to the System menu.

IMPORTANT

Publication 1760-UM002B-EN-P - March 2005

If GFX is protected by a password, the System menu will not be available until Pico GFX-70 is “unlocked” (see Unlocking Pico GFX-70 on 7-5).

Page 349

Pico GFX-70 Settings

2. Select the SYSTEM menu.

▲

SECURITY

7-21

3. Press the OK button.

SYSTEM... MENU LANGUAGE CONFIGURATOR... ▼

4. Use the down arrow button to select the DISPLAY menu and press OK.

▲

RUN MODE CARD MODE TERMINAL MODE DISPLAY...

▼

CONTRAST:

0

The menus for setting the contrast and backlight are displayed. LIGHTING:

CONTRAST: LIGHTING:

5. Press the OK button and move to the contrast entry field

75%

Use the up and down arrow buttons to set the contrast to a value between -2 and +2.

+1 75%

6. Select your setting. 7. Complete your setting by pressing OK. CONTRAST: LIGHTING:

+1

The contrast setting will be retained until it is modified.

75%

8. Use the up and down arrow buttons to move to the LIGHTING menu. CONTRAST: LIGHTING:

+1

9. Press the OK button.

75%

10. Use the up and down arrow buttons to change the value in 25% steps. CONTRAST: LIGHTING

+1

11. Set the required backlighting.

75%

. IMPORTANT

CONTRAST:

+1

LIGHTING

100%

IMPORTANT

The backlight will immediately change to the set value. 0, 25, 50, 75 and 100% are possible values.

Pico GFX-70 comes with the following factory setting: The contrast is set to 0. The backlight is set to 75%.

Publication 1760-UM002B-EN-P - March 2005

Page 350

7-22

Pico GFX-70 Settings

Retention

It is a requirement of system and machine controllers for operating states or actual values to have retentive settings. What this means is that the values will be retained safely even after the supply voltage to a machine or system has been switched off and are also retained until the next time the actual value is overwritten. The following operands and function blocks can be set to operate retentively: • Markers • Counter function blocks, • Data function blocks and • Timing relays. Operating hours counter The device provides four retentive operating hours counters. They are always retentive and can only be selectively deleted with a reset command. Retentive data volume 200 bytes is the maximum memory range for retentive data (operating hours counters are not included). Markers A user-definable and consistent marker range can be declared as retentive. Counters All C.., CH.. and CI.. function blocks can be operated with retentive actual values. Data function blocks A user-definable consistent data function block range can be operated with retentive actual values. Timing relays A user-definable and consistent range for timing relays can be run with retentive actual values.

Publication 1760-UM002B-EN-P - March 2005

Page 351

Pico GFX-70 Settings

7-23

Requirements To make data retentive, the relevant markers and function blocks must have been declared as retentive.

ATTENTION

The retentive data is saved every time the power supply is switched off, and read every time the device is switched on. The data integrity of the memory is guaranteed for 1010 read/write cycles.

Setting Retentive Behavior Requirement: Pico GFX-70 must be in STOP mode. 1. Switch to the System menu.

IMPORTANT

If Pico GFX-70 is protected by a password, the System menu will not be available until Pico GFX-70 is “unlocked” (see Unlocking Pico GFX-70 on 7-5).

The default setting of Pico GFX-70 is for no retentive actual value data to be selected. When Pico GFX-70 is in STOP mode or has been switched to a de-energized state, all actual values are cleared. ✓

RUN MODE

▲

3. Switch to the System menu.

CARD MODE ✓

LIGHTING

▼

RETENTION…

MB 00 -> MB 00 ▲ C

00 -> C

00

CH 00 -> CH 00 ▼ B:200

2. Switch to STOP mode.

4. Proceed to the SYSTEM menu and continue to the RETENTION… menu. 5. Press the OK button. The first screen display is the selection of the marker range. 6. Select a range using the up/down arrow keys. 7. Press OK to access the Entry modes.

– Select a position from/to using the left/right arrow keys. – Set a value using the left/right arrow keys. 8. Save the input from .. to .. with OK. Publication 1760-UM002B-EN-P - March 2005

Page 352

7-24

Pico GFX-70 Settings

9. Press ESC to exit the input for the retentive ranges. CI 00 -> CI 00 ▲ DB 00 -> DB 00 T

00 -> T

00 ▼

Up to six different ranges can be selected.

B:200

IMPORTANT

MB 01 -> MB 04 C

12 -> C

16

The display on the lower right B:200 indicates the number of free bytes.

Example: MB 01 to MB 04, C 12 to C 16, DB 01 to DB 16, T 26 to T 32 should be retentive.

CH 00 -> CH 00 CI 00 -> CI 00 DB 01 -> DB 16 T

26 -> T

124 bytes have been assigned to the retentive data range. 76 bytes are still available.

32

B:076

Deleting Ranges Set the ranges to be erased to the values from 00 to 00. e.g.: MB 00 -> MB 00. The markers are no longer retentive.

Deleting Retentive Actual Values of Markers and Function Blocks The retentive actual values are cleared if the following is fulfilled (applies only in STOP mode): • When the circuit diagram is transferred from PicoSoft Pro (PC) or from the memory module to Pico GFX-70, the retentive actual values are reset to 0. This also applies when there is no program on the memory module. In this case the old circuit diagram is retained in Pico GFX-70. • When changing the respective retentive range. • When the circuit diagram is deleted via the DELETE PROGRAM menu.

Transferring Retentive Behavior The setting for retentive behavior is a circuit diagram setting. In other words, the setting of the retentive menu may also under certain circumstances be transferred to the memory module or by uploading or downloading from the PC.

Publication 1760-UM002B-EN-P - March 2005

Page 353

Pico GFX-70 Settings

7-25

Changing the Operating Mode or the Circuit Diagram When the operating mode is changed or the Pico GFX-70 circuit diagram is modified, the retentive data is normally saved together with their actual values. The actual values of relays no longer being used are also retained.

Changing the Operating Mode If you change from RUN to STOP and then back to RUN, the actual values of the retentive data will be retained.

Modifying the Circuit Diagram If a modification is made to the Pico GFX-70 circuit diagram, the actual values will be retained.

Changing the Startup Behavior in the SYSTEM Menu The retentive actual values are retained in Pico GFX-70 regardless of the setting.

Modification of the Retentive Range If the set retentive ranges are reduced, only the actual values saved in the range will remain. If the retentive range is extended, the older data is retained. The new data is written with the current actual values in RUN mode.

Displaying Device Information

Device information is provided for service tasks and for determining the capability of the device concerned. This function is only available with devices featuring a display. Exception: Terminal mode with Pico GFX-70. The device enables the display of the following device information: • AC or DC power supply • T (transistor output) or R (relay output) • C (clock provided) • A (analog output provided) • LCD (display provided) • Pico-Link (Pico-Link provided) • OS: 1.10.204 (operating system version)

Publication 1760-UM002B-EN-P - March 2005

Page 354

7-26

Pico GFX-70 Settings

• CRC: 25825 (checksum of the operating system). 1. Switch to the System menu. IMPORTANT

SECURITY

▲

If Pico GFX-70 is protected by a password, the System menu will not be available until Pico GFX-70 is “unlocked” (see Unlocking Pico GFX-70 on page 7-5).

2. Select the SYSTEM menu. 3. Press the OK button.

SYSTEM... MENU LANGUAGE CONFIGURATOR... ▼ CARD MODE

▲

4. Use the down arrow button to select the INFORMATION menu and press OK.

DISPLAY... RETENTION... INFORMATION...

▼

This will display all device information. Example: 1760-DUB, 1760-LDFC, 1760-IB12XOB4IOF

DC TCA LCD NET OS : 1.11.111 CRC: 63163

Example: 1760-DUB, 1760-LDF, 1760-IB12XOW4IF DC RC

LCD

Display in STOP mode.

OS : 1.11.111 CRC: 63163

Display in RUN mode. DC RC

LCD

The CRC checksum is not displayed.

OS : 1.11.111 CRC: - - -

5. Press ESC to leave the display. CARD MODE

▲

DISPLAY... RETENTION... INFORMATION...

▼

Publication 1760-UM002B-EN-P - March 2005