Page 381
Specifications
A-9
Table A.9 Processor Unit, Real-Time Clock/Timing Relay/Memory Repetition accuracy of timing relays Accuracy of timing relay (from value)
± 0.02%
Resolution
Range “s”: 5 ms Range “M:S”: 1s Range “H:M”: 1 min
Circuit connections
256
Contacts in series
4
Coil per circuit connection
1
Program memory for program/circuit diagram
8 KB
Program memory for display objects (visualization)
24 KB
RAM working memory
8 KB
Storage of programs (retentive)
FRAM
Retentive memory (retentive data, retentive) FRAM Size: 200 byte Operating hours counter: 16 byte Write-read cycles FRAM (minimum)
1010
Publication 1760-UM002B-EN-P - March 2005
Page 382
A-10
Specifications
Table A.10 GFX I/O Modules Input Specifications Specification
1760-IB12XOW4IF, 1760-IB12XOW4IOF 1760-IB12XOB4IF, 1760-IB12XOB4IOF
1760-IA12XOW4I
Number of digital inputs
12(1)
12
Inputs usable as analog inputs (I7, I8, I11, I12)
4(1)
0
Inputs usable as high-speed inputs (I1, I2, I3, I4) 4
0
Rated voltage
24V dc
120/240V ac
Off-state voltage
I1 to I6 and I9 to I10: < 5V dc I7, I8, I11, I12: < 8V dc
0 to 40V ac
On-state voltage
I1 to I6 and I9 to I10: > 15V dc I7, I8, I11, I12: > 8V dc
79 to 264V ac
On-state current
I1 to I6, I9 to I10 at 24V dc: 3.3 mA I7, I8, I11, I12 at 24V dc: 2.2 mA
115V ac: 0.2 mA 230V ac: 0.5 mA
Signal delay
Debounce On: 20 ms Debounce Off, typical: I1 to I4s: 0.025 ms I5, I6, I9, I10: 0.25 ms I7, I8, I11, I12: 0.15 ms
0 to 1: 10 ms
Electrical Isolation
To supply voltage: No Between each other: No To the outputs: Yes To PC interface, memory module, the Pico-Link network, expansion I/O: Yes
To supply voltage: No Between each other: No To the outputs: Yes To PC interface, memory module, the Pico-Link network, expansion I/O: Yes
Cable Length (unshielded)
100 m (328 ft)
60 m (197 ft)
Number of analog inputs (I7, I8, I11, I12)
4
0
Input type
DC voltage
–
Signal range
0 to 10V dc
–
Resolution analog
0.01V
–
Resolution digital
10-bit (0 to 1023 counts)
–
Input impedance
11.2K Ω
–
Accuracy
Two GFX devices, from actual value: ±3% Within a unit, from actual value, (I7, I8, I11, I12): ±2%
–
Input current
< 1 mA
–
Conversion time, analog to digital
Debounce On: 20 ms Debounce OFF: each cycle time
–
Electrical Isolation
To supply voltage: No To the digital inputs: No To the outputs: Yes To the Pico-Link network: Yes
–s
Cable Length (unshielded)
30 m (98 ft)
–
Publication 1760-UM002B-EN-P - March 2005
1 to 0: 100 ms
Page 383
Specifications
A-11
Table A.10 GFX I/O Modules Input Specifications Specification
1760-IB12XOW4IF, 1760-IB12XOW4IOF 1760-IB12XOB4IF, 1760-IB12XOB4IOF
1760-IA12XOW4I
Number of high-speed inputs (I1, I2, I3, I4)
4
0
High-speed up and down counters
Frequency: < 3 kHz Pulse shape: square wave
–
Frequency counters
Frequency: < 3 kHz Pulse shape: square wave
–
Incremental counter encoder
Frequency: < 3 kHz Pulse shape: square wave Counter inputs I1 and I2, I3 and I4: 2 Signal offset: 90°
–
(1) Four of the digital dc inputs can alternately be used as 0 to 10V dc analog inputs. These inputs can be used as either digital or analog, not both. For example, you could use 4 analog inputs plus 8 digital inputs.
Table A.11 GFX I/O Modules Relay Output Specifications Specification
1760-IA12XOW4I, 1760-IB12XOW4IF 1760-IB12XOW4IOF, 1760-OW2
Number of relay outputs
4 (2 for the 1760-OW2)
Type of outputs
Relays
In groups of
1
Connection of outputs in parallel to increase the output
Not permissible
Protection for an output relay
Miniature circuit-breaker B16: 16A or fuse (slow-blow): 8A
Potential isolation to mains power supply, input, PC interface, memory module, Pico-Link network, expansion I/O
Safe isolation: 300V ac Basic insulation: 600V ac
Mechanical life span
10 x 106 switch operations
Contacts relays Conventional thermal current, (UL)
8A, (10A)
Recommended for load at 12V ac/dc
> 500 mA
Protected against short-circuit cos ϕ = 1, 16A characteristic B (B16) at
600A
Protected against short-circuit cos ϕ = 0.5 to 0.7, 16A characteristic B (B16) at
900A
Rated impulse withstand voltage Uimp contact coil
6 kV
Rated insulation voltage Ui Rated operational voltage Ue
250V ac
Safe isolation to EN 50178 between coil and contact
300V ac
Safe isolation to EN 50178 between two contacts
300V ac
Making capacity, IEC 60947 AC-15 250V ac, 3A (600 Ops/h)
300,000 switch operations
DC-13 L/R ≤150 ms 24V dc, 1A (500 Ops/h)
200,000 switch operations
Breaking capacity, IEC 60947
Publication 1760-UM002B-EN-P - March 2005
Page 384
A-12
Specifications
Table A.11 GFX I/O Modules Relay Output Specifications Specification
1760-IA12XOW4I, 1760-IB12XOW4IF 1760-IB12XOW4IOF, 1760-OW2
AC-15 250V ac, 3A (600 Ops/h)
300,000 switch operations
DC-13 L/R ≤150 ms 24V dc, 1A (500 Ops/h)
200,000 switch operations
Filament lamp load 1000 W at 230/240V ac
25,000 switch operations
500 W at 115/120V ac
25,000 switch operations
Fluorescent tube with ballast, 10 x 58 W at 230/240V ac
25,000 switch operations
Conventional fluorescent tube, compensated, 1 x 58 W at 230/240V ac
25,000 switch operations
Conventional fluorescent tube, uncompensated, 10 x 58 W at 230/240V ac
25,000 switch operations
Operating frequency, relays Mechanical switch operations
10 million (107) switch operations
Mechanical switching frequency
10 Hz
Resistive lamp load
2 Hz
Inductive load
0.5 Hz
Table A.12 UL/CSA Relay Ratings Uninterrupted current at 240V ac/24V dc
10A/8A
AC
Control Circuit Rating Codes (utilization category)
B300 Light Pilot Duty
Max. rated operational voltage
300V ac
Max. thermal uninterrupted current cos ϕ = 1 at B300
5A
Maximum make/break capacity cos ϕ k 1 (Make/break) at B300
3600 VA/360 VA
Control Circuit Rating Codes (utilization category)
R300 Light Pilot Duty
Max. rated operational voltage
300V dc
Max. thermal uninterrupted current at R300
1A
Maximum make/break capacity at R300
28 VA/28 VA
DC
Publication 1760-UM002B-EN-P - March 2005
Page 385
Specifications
A-13
Table A.13 GFX I/O Modules Transistor Output Specifications Specification
1760-IB12XOB4IF, 1760-IB12XOB4IOF
Number of transistor outputs
4
Contacts
Semiconductors
Rated voltage Ue
24V dc
Voltage Range
20.4V dc to 28.8V dc
Residual Ripple
≤ 5%
Supply current
On 0 state: 18 mA (typical), 32 mA (max) On 1 state: 24 mA (typical), 44 mA (max)
Reverse polarity protection
Yes
ATTENTION
If voltage is applied to the outputs when the polarity of the power supply is reversed, this will result in a short circuit.
Potential isolation to the inputs, supply voltage, PC interface, memory module, Pico-Link network, expansion I/O
Yes
Rated current Ie at state 1, maximum
0.5A
Lamp load
5W (Q1 to Q4 without RV)
Residual current at state “0” per channel
< 0.1 mA
Max. output voltage
On 0 state with external load, 10 MΩ: 2.5V On 1 state, Ie = 0.5 A U = Ue - 1V
Short-circuit protection: Thermal (Q1 to Q4)
Yes (evaluation with diagnostics inputs I16, I15)
Short-circuit tripping current for Ra ≤ 10 MΩ
0.7A ≤ Ie ≤2A
(depending on number of active channels and their load) Maximum total short-circuit current
8A
Peak short-circuit current
16A
Thermal cutout
Yes
Maximum switching frequency with constant resistive load RL = 100 kΩ (depends on program and load)
40,000 switch operations/hour
Parallel connection of outputs with resistive load; inductive load with external suppression circuit (See Connecting Transistor Outputs on page 2-30); combination within a group
Yes Group 1: Q1 to Q4 Maximum number of outputs: 4
Total maximum current
2A
ATTENTION
Status display of the outputs
Outputs must be actuated simultaneously and for the same time duration.
LCD Status display (if provided)
Publication 1760-UM002B-EN-P - March 2005
Page 386
A-14
Specifications
Inductive load without external suppressor circuit General explanations: T0.95 = time in milliseconds until 95% of the stationary current is reached
T0.95 ≈ 3 x T0.65 = 3 x L R
Table A.14 Utilization Category in Groups for Q1 to Q4, Q5 to Q8 T0.95 = 1 ms
Utilization factor per group g =
0.25
R = 48 Ω
Relative duty factor
100%
Max. switching frequency
1500 switch operations per hour
L = 16 mH f = 0.5 Hz Max. duty factor DF = 50% DC13 T0.95 = 72 ms R = 48 Ω
Utilization factor g =
0.25
Relative duty factor
100%
Max. switching frequency
1500 switch operations per hour f = 0.5 Hz
L = 1.15 H Max. duty factor DF = 50%
Table A.15 Utilization Category for Other Inductive Loads T0.95 = 15 ms
Utilization factor g =
0.25
R = 48 Ω
Relative duty factor
100%
Max. switching frequency
1500 switch operations per hour
L = 0.24 H f = 0.5 Hz Max. duty factor DF = 50% Inductive loading with external suppressor circuit for each load (See Connecting Transistor Outputs on page 2-30)
Utilization factor g =
1
Relative duty factor
100%
Max. switching frequency
Number of switch operations per hour depends on the suppressor circuit
Max. duty factor
Publication 1760-UM002B-EN-P - March 2005
Page 387
Specifications
A-15
Table A.16 Analog Output Specifications Specification
1760-IB12XOW4IOF, 1760-IB12XOB4IOF
Number of analog outputs
1
Electrical isolation
To power supply: No To the digital inputs: No To the digital outputs: Yes To the Pico-Link network: Yes
Output type:
DC voltage
Signal range
0 to 10V dc
Output current max.
10 mA
Load resistor
1k Ω
Short-circuit and overload proof
Yes
Resolution analog
0.01V dc
Resolution digital
10-bit 0 to 1023 counts
Transient recovery time
100 µs
Accuracy (-25°C to +55°C), related to the range
2%
Accuracy (25°C), related to the range
1%
Conversion time
Each processor cycle
Publication 1760-UM002B-EN-P - March 2005
Page 388
A-16
Specifications
Table A.17 Pico-Link Specifications Specification
1760-LDFC and 1760-LDFCA
Number of stations
8
Bus length/transmission speed(1)
6m/1000k Baud 25m/500k Baud 40m/250k Baud 125m/125k Baud 300m/50k Baud 700m/20k Baud 1000m/10k Baud
Electrical isolation
To power supply, inputs, outputs, expansion I/O, PC interface, memory module: Yes
Bus termination (see accessories)
Yes (First and last station)
Plug connector (see accessories)
8 poles RJ45
Cable cross-sections, with cable lengths and cable resistance/m Cross-section up to 1000, < 16 mΩ/m
1.5 mm2 (16 AWG)
Cross-section up to 600, < 26 mΩ/m
0.75 mm2 to 0.8 mm2 (18 AWG)
Cross-section up to 400, < 40 mΩ/m
0.5 mm2 to 0.6 mm2 (20, 19 AWG)
Cross-section up to 250, < 60 mΩ/m
0.34 mm2 to 0.5 mm2 (22, 21, 20) AWG
Cross-section up to 175, < 70 mΩ/m
0.25 mm2 to 0.34 mm2 (23, 22 AWG)
Cross-section up to 40, < 140 mΩ/m
0.13 mm2 (26 AWG)
(1)
Publication 1760-UM002B-EN-P - March 2005
Bus lengths above 40 m can only be achieved with cables with reinforced cross-section and connection adapter.