The text of a spec sheet · part 1 of 1
NetController CPU Module, pages 1 to 6
Pages 1 to 6 of 6
The original document is the PDF (89 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Andover Controls CPU-4M and Andover Controls CPU-8M
Page 1
ª
NetController CPU Module The Continuum NetController is the high-powered Central Processing Unit (CPU) module and network manager for the Andover Controls Continuum intelligent building system. With its 8 MB DRAM, 4 MB FLASH, math co-processor, and four programmable communications ports, • Native Ethernet TCP/IP Network Controller including an interface to Infinity’s Infinet distributed controllers, the Continuum NetController provides a total solution for facility-wide network communications and
• Powerful, Modular CPU Board for Monitoring and Control information management. A lower-cost version of the NetController is also available with 4 MB DRAM, 2 MB FLASH, and no math co-processor.
of Both Continuum I/O Modules and Infinity Infinet Distributed Controllers
HIGH-SPEED COMMUNICATIONS
The NetController acts as the system coordinator, providing integrated global control and monitoring, history logging, and local and remote alarming for both the Continuum I/O modules and the RS-485 Infinet controllers that control
• High-Speed Networking - your individual building services - heating, ventilating, air conditioning, lighting, access control, smoke control, and
4 Million Nodes on Ethernet more. The NetController communicates with up to 32 Continuum I/O modules via Andover Controls LON communications over a choice of RS-485 or free topology bus media. The NetController supports expansion of up to two Infinet
• Four Programmable Comm. Ports for Flexible Interconnect and networks. Each Infinet network can contain 127 Infinet controllers and up to 31 ACX series access controllers or DCX 250 display controllers.
Third-Party Communications
An optional Ethernet port also allows the NetController to communicate with other NetControllers and Continuum Workstations over a high-speed 10 MB/s Ethernet Local Area Network (LAN) using TCP/IP protocol. Continuum • Programmable Battery Backup Provides Choice of Shutdown Options
• FLASH for Easy On-Line Software Updates workstations are capable of communicating with up to 4 millions nodes on Ethernet. Two different network interfaces are available - you can choose either Ethernet 10BASE-T (twisted pair) cable media or Ethernet 10BASE-FL (fiber optic cable). A Token Ring LAN interface option is also available. See factory for details. NetController’s FLASH allows you to download software revisions over Ethernet using a Continuum workstation. The FLASH memory feature eliminates the need to perform EPROM change-outs in the field. SERIAL COMMUNICATIONS
• Plain English ® Language Simplifies Programming
NetController’s four programmable communications ports can be configured as a combination of RS-232 or RS-485 interfaces to modems, printers, third-party devices, and up to two Infinity Infinet field controller networks. Andover Controls has developed an extensive library of third-party software interfaces, including controls for
• DIN Rail Mounting and SlideTogether Connectors for Easy chiller panels, fire alarm systems, emergency generator systems, bar code readers, elevator controls, videomatrix switchers, and more.
Installation
PLAIN ENGLISH ® PROGRAMMING • Backward Compatible with
Infinity Hardware
The Continuum NetController can be configured to meet the exact requirements of your application using the powerful Andover Controls Plain English programming language. Programs are entered into the NetController using the Continuum Workstation. The program is then stored in, and executed by, the NetController. Just as with Infinity, one single language is used system-wide.
Page 2
SOFTWARE CAPABILITIES
The dynamic memory of the Continuum NetController can be allocated for any combination of programs, scheduling, alarming, reporting and data logging. Our object-oriented Plain English language with intuitive keywords provides easy operation and programming. In addition, Plain English ‘s pre-defined and customized functions and powerful math capabilities reduce programming time.
OPTIONAL AUTO-BAUD MODEM
The optional Andover Controls Continuum modem allows NetController to communicate and exchange data over standard voice grade telephone lines with speeds up to 14,4K baud. The modem has built-in data compression and error-correction protocols, auto-dial/auto-answer capabilities, and is UPS-supported.
UPS OPERATION
The Continuum NetController incorporates software programmable battery backup that reduces or eliminates the impact of power failure. In powerfail mode, the NetController CPU can turn off I/O power to extend battery life and support modem and network operation for up to four hours. In addition, the NetController can go into a low-power mode in which only the DRAM and real-time clock are powered for up to 72 hours.
MODULAR DESIGN FOR SLIDE-TOGETHER CONNECTION
The NetController features a sleek, lightweight casing designed for natural convection cooling. Built-in connectors on either side of the NetController module allow power transmission from the power supply module and communication signals to the Continuum I/O modules to feed through easy slide-together connections. Built-in quick-release fasteners at the back of the module are provided for DIN rail mounting - no tools required. These fasteners also snap into a locked position for panel mounting. The NetController module is designed for mounting in an optional NEMA 1-style Continuum enclosure. (See the Continuum Enclosure and Display Module System data sheet.)
DIMENSION
DRAWING
Page 3
SPECIFICATIONS
ELECTRICAL
Power Consumption:
10 watts at 24VDC max.; provided by Continuum power supply module.
Overload Protection:
3A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection.
Real Time Clock:
Battery-backed by UPS
MECHANICAL
Operating Environment:
32 to 120°F, (0 to 49°C), 10 to 95%RH (non-condensing)
Size:
9.0”W (228.7mm) 7.2”H (182.88mm) (with mounting clips extended) 6.2”H (157.48mm) (with mounting clips closed) 2.5”D (96.5 x 170.2 x 63.5mm)
Weight:
1.6 lbs (0.73kg)
Enclosure Type:
UL open class, flammability rating of UL94-5V, IP 10
Mounting:
Mount on DIN rail or wall-mount using attached fasteners. Continuum NEMA 1-style enclosure available.
BATTERY
Battery Backup:
Two 12V 7.0AHr sealed rechargeable batteries on the Continuum power supply provides 60 minutes @ 35 watts power consumption full UPS (CPU plus I/O power); 4 hours CPU module only (including modem and network interface) with no I/O; or 72 hours DRAM and real-time clock. Expandable by use of greater amp-hour batteries.
COMMUNICATIONS
Comm. Error Checking:
International Standard CRC 16
Ethernet LAN Interface:
10BASE-T: 327 ft (100m) standard between 2 nodes using 10BASE-T unshielded twisted pair cable. Standard Ethernet repeaters allow for longer distances. 10BASE-FL: 6562 ft (2000m) standard for 2 nodes using 10BASE-FL fiber optic cable. Standard Ethernet repeaters allow for longer distances.
Serial Comm. Interface:
Four programmable RS-232/485 ports, software configurable as printer, modem, third-party system, or TankNet. Infinet can be configured on Ports 1 and 2. Port 1: RS-485/232 Port 2: RS-485 Port 3: RS-232/Modem Port 4: RS-485
Serial Comm. Speed:
300 to 19.2K baud selectable for Infinet and 14.4K baud for modem
Infinet Bus Length:
4,000 ft. (1,220m) standard for Infinet using approved shielded, twisted pair, low capacitance cable. InfiLink module allows extension to longer distances.
I/O Bus:
ACC-LON communications. Choice of bus media, RS-485 or FTT-10A
Page 4
RS-485:
Communications Speed: 39k baud Bus Length: 2,000 ft. (610m). Bus Media: Shielded, twisted pair cable. 120 Ω termination required at both ends of the ACC-LON network (when modules are mounted remotely).
FTT-10A:
Communications Speed: 78k baud Bus Length: Up to 8858 ft. (2700m) – bus topology Up to 1640 ft (500m) – free topology Repeater required for longer distances. Bus Media: Refer to Echelon FTT-10A free topology documentation
CONNECTIONS
Power:
5-position plug-in connector on left side of module for direct connection to Continuum power supply module.
Ethernet:
RJ-45 connector for Ethernet 10BASE-T or ST-style connector for 10BASE-FL.
Infinet, TankNet:
Removable terminal block (Requires external +26 volts for TankNet.)
Printer:
RJ-45
Modem:
RJ-11 connector
I/O Bus:
5-position plug-in connector on right side of module for direct connection of up to 32 I/O modules.
USER LEDS/SWITCHES STATUS INDICATOR LEDS
POWER CPU SCAN ERROR
NetController Power is ON NetController Active NetController Scanner ON NetController Error
COMM1 TD COMM1 RD
Comm. Port 1 Transmit On-Line Comm. Port 1 Receive Data
COMM2 TD COMM2 RD
Comm. Port 2 Transmit On-Line Comm. Port 2 Receive Data
COMM3 TD COMM3 RD
Comm. Port 3 Transmit Data Comm. Port 3 Receive Data
COMM4 TD COMM4 RD
Comm. Port 4 Transmit On-Line Comm. Port 4 Receive Data
MODEM DCD MODEM DTR MODEM Selected
Data Carrier Detect Data Terminal Ready Indicates the MODEM is selected (Comm Port 3 is shared - RS-232 and MODEM)
I/O Bus On-Line
Indicates the LON I/O Bus is On-Line
ETHERNET:
TD RD COL LINK POL
ETHERNET Transmit Data ETHERNET Receive Data ETHERNET Collision ETHERNET Link ETHERNET Polarity
Page 5
PUSH BUTTON SWITCHES:
Clear Memory
RESET/Clear Memory
MODEM RS-232 Override
Selects between the MODEM and RS-232C (Comm 3)
GENERAL
Microprocessor:
68ECO20 running at 24 MHz with 68882 Floating Point Math Co-Processor (8 MB model only)
Memory:
DRAM: 8 MB or 4 MB FLASH : 4 MB or 2 MB
AGENCY LISTINGS
UL/CUL 916, UL 864, UL 294, UL 1076, FCC Class A, CE
OPTIONS
Ethernet (TCP/IP) Module, 10BASE-T (Twisted Pair) Ethernet (TCP/IP) Module , 10BASE-FL (Fiber Optic) Third-party Interface Support (up to 3 commports) 14.4K baud Modem (UPS Supported) (U.S. and Canada only)
Page 6
Andover Controls Corporation World Headquarters 300 Brickstone Square • Andover, Massachusetts 01810 USA Tel: +1 978 470 0555 • Fax: +1 978 470 0946 http://www.andovercontrols.com Andover Controls Ltd. Smisby Road • Ashby-de-la-Zouch • Leicestershire LE65 2UG, England Tel: +44 1530 417733 • Fax: +44 1530 415436 Andover Control GmbH Am Seerhein 8 • D-78467 Konstanz, Germany Tel: +49 7531 99370 • Fax: +49 7531 993710 Andover Control S.A. Immeuble Dolomites 2 • 58 Rue Roger Salengro • 94126 Fontenay Sous • Bois Cedex, France Tel: +33 153 99 16 16 • Fax: +33 153 99 16 15 Andover Controls Asia Unit 1201-02, Phase I, Cheuk Nang Centre • 9 Hillwood Road, Tsim Sha Tsui • Kowloon, Hong Kong Tel: +852 2739 5497 • Fax: +852 2739 7350 Andover Controls Mexico Insurgentes Sur 1722-501 • Col. Florida • Mexico D.F. 01030, Mexico Tel: +525 661 56 72 • Fax: +525 661 54 15 Copyright 2000, Andover Controls Corporation. Data subject to change without notice. All brand names, trademarks and registered trademarks are the property of their respective holders. Consult Andover Product Installation Guides for exact installation instructions and specifications. #DS-C-NETCONTROL-F