Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of NetController CPU Module

Spec sheet · Andover Controls

NetController CPU Module

Spec sheet6 pagesPDF 89 KB

Data sheet for the Andover Controls Continuum NetController CPU module (8 MB and 4 MB DRAM versions) for building automation.

Download the PDF89 KB

Filed with · 2 models

Also filed with these models on the old site

Summary

What is in it

Andover Controls data sheet for the Continuum NetController, the CPU module and network manager of the Continuum intelligent building system. It is offered with 8 MB DRAM and 4 MB FLASH plus a math co-processor, or as a lower-cost version with 4 MB DRAM and 2 MB FLASH. The sheet describes Ethernet and serial communications, Infinet support, Plain English programming, the optional modem, UPS operation and DIN rail mounting, then gives electrical, mechanical, battery, communications and connection specifications, LEDs, agency listings and options.

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

Data sheet for the Andover Controls Continuum NetController CPU module, the processor and network manager of the Continuum building control system. It describes two memory versions (8 MB DRAM with 4 MB FLASH and a math co-processor, or 4 MB DRAM with 2 MB FLASH) but does not print the CPU-4M or CPU-8M designations. It gives power, ports, network limits, LEDs and battery backup times.

Device
Continuum NetController CPU module and network manager for Continuum I/O modules and Infinet controllers p. 1
Memory
DRAM 8 MB or 4 MB; FLASH 4 MB or 2 MB p. 5
Processor
68ECO20 at 24 MHz; 68882 floating point math co-processor on the 8 MB model only p. 5
Power
10 watts at 24VDC max., from the Continuum power supply module; 3A resettable fuse p. 3
Serial ports
Four programmable ports: Port 1 RS-485/232, Port 2 RS-485, Port 3 RS-232/Modem, Port 4 RS-485 p. 3
Ethernet
Optional 10 MB/s Ethernet, TCP/IP: 10BASE-T on RJ-45 or 10BASE-FL on ST-style connector p. 1, 4
I/O bus
ACC-LON on RS-485 (39k baud, 2,000 ft.) or FTT-10A (78k baud); up to 32 I/O modules p. 3, 4
Infinet
Up to two Infinet networks on Ports 1 and 2; 127 Infinet controllers each; 4,000 ft. (1,220m) bus p. 1, 3
Serial speed
300 to 19.2K baud for Infinet; 14.4K baud for modem p. 3
Battery backup
From two 12V 7.0AHr batteries on the power supply: 60 minutes full UPS, 4 hours CPU only, or 72 hours DRAM and clock p. 3
Operating environment
32 to 120°F (0 to 49°C), 10 to 95%RH non-condensing p. 3
Weight
1.6 lbs (0.73kg) p. 3
Mounting
DIN rail or wall mount with attached fasteners; slide-together side connectors p. 2, 3
Other connectors
Printer RJ-45; modem RJ-11; Infinet and TankNet on removable terminal block p. 4

What this sheet walks you through

  • Planning Ethernet, Infinet and I/O bus cable lengths p. 3, 4
  • Reading the status, comm port and Ethernet LEDs p. 4
  • Using the Clear Memory and modem override push buttons p. 5
  • Updating software over Ethernet into FLASH p. 1
  • Power failure behavior and battery backup modes p. 2

Good to know

  • A 120 Ω termination is needed at both ends of an RS-485 ACC-LON network when modules are mounted remotely. p. 4
  • TankNet needs an external +26 volts. p. 4
  • Comm Port 3 is shared between RS-232 and the modem. p. 4
  • The 14.4K baud modem option is for the U.S. and Canada only. p. 5

Questions this sheet answers

What memory does the Andover Continuum NetController have?

8 MB DRAM with 4 MB FLASH, or the lower-cost version with 4 MB DRAM and 2 MB FLASH and no math co-processor. p. 1

How many I/O modules can a NetController run?

Up to 32 Continuum I/O modules on the I/O bus. p. 1

What power does the NetController CPU need?

10 watts at 24VDC maximum, supplied by the Continuum power supply module through a 5-position connector. p. 3, 4

How long does the NetController run on battery?

60 minutes for full UPS, 4 hours for the CPU module only, or 72 hours for DRAM and the real-time clock. p. 3

The whole text · 1 part

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 61-6

The file

Revision and size

RevisionDS-C-NETCONTROL-F
PublisherAndover Controls Corporation
Pages6
PDF89 KB
TextText from the PDF itself.

The first pages · 4 of 6

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 6
Page 2
Page 2of 6
Page 3
Page 3of 6
Page 4
Page 4of 6