Reference manual for installing and wiring Andover Continuum I/O modules, including the UI-8, DO-4, AC-1 and other input and output modules.
Names · 4 models
The models it names
Filed with · 2 models
Also filed with these models on the old site
Summary
What is in it
Schneider Electric reference for the Andover Continuum I/O system, describing the installation, care and use of the Andover Continuum I/O modules. It covers DIN rail and panel mounting, dimensions, CPU to I/O connections, remote I/O over ACC-LON (RS-485) and LON FTT-10A, module configuration and wiring, then a section per module: UI-8-10 universal inputs, DI-6, DI-8, MI-6, DM-20, AO-4-8, DO-4-R, DO-6-TR, LO-2, DIO-20, AC-1, AC-1A, AC-1 Plus, VS-8-4 and VT-1.
Its parts
- Introduction
- Mechanical Installation
- CPU-I/O Connections
- Replacing or Adding I/O Modules
- Module Configuration
- Individual Module Wiring
- Input Modules
- Output Modules
- Mixed Modules
From the manual
Key facts from this manual
Each line names its page in the PDF.
Schneider Electric reference manual for installing, wiring and using the Andover Continuum I/O modules with the NetController and NetController II CPUs. It covers mechanical installation, the CPU-to-I/O bus, power budgets and cabling, then a chapter per module: UI-8-10 / UI-8-10-10V, DI-6-AC, DI-8, MI-6, DM-20, AO-4-8, DO-4-R / DO-4-R-O, DO-6-TR, LO-2, DIO-20, AC-1, AC-1A, AC-1 Plus, VS-8-4 and VT-1.
- Document
- Installation, care and use of all Andover Continuum I/O modules p. 5
- Modules per CPU
- 32 maximum, also limited by power supply capacity p. 16
- I/O bus connector
- 5 pins: 5 +24 VDC, 4 24 VDC Return, 3 Shield, 2 Comm B, 1 Comm A p. 14
- Bus interface
- Two-signal serial bus, factory set as RS 485 ACC-LON or LON FTT-10A p. 14
- Max bus length
- RS-485 2000 ft. (610 m); FTT-10A 8858 ft. (2700 m) double termination, 1640 ft. (500 m) free topology p. 17
- Connector part number
- 01-0010-840 (bus cable connector) p. 15
- RS-485 data cable
- 24-gauge shielded twisted pair, 100-120 ohm; Belden 9729 meets the spec p. 17
- Power supplies
- PS 120/240 AC 50 U (35 W), AC 85 U (70 W), AC 50 (50 W), AC 85 (85 W), PS -48 DC 50 (50 W) p. 16
- UI-8-10 inputs
- 8 universal inputs, 10-bit: voltage, thermistor, digital, counter or supervised; 0-5 V (UI-8-10-10V: 0-10 V) p. 39
- UI-8-10 power
- 10-28V supply; 0.7 Watt (29 mA) @ 24VDC max. p. 40
- UI-8-10 input impedance
- 5 megohm pull-up disabled, 10K ohm pull-up enabled; 4.4K ohm in 0-10V mode p. 40
- UI-8-10 thermistor
- 10K ohm Type III, -30 to 230°F (-34 to 110°C) p. 40
- DO-4-R outputs
- 4 Form C relays, 240 VAC @ 5 Amps, 30 VDC @ 5 Amps; 2.8 Watts at 24 VDC p. 100
- AC-1
- 1 Wiegand/proximity reader (64 bits), +5 or +12 V reader power, 3 supervised inputs, 2 Form C relays 24 VAC/VDC @ 5 Amp p. 134
What this manual walks you through
- Plugging modules together and cabling remote modules p. 15
- Working out how many modules a power supply can carry p. 16
- Adding the power drawn by card readers and keypads p. 17
- Choosing data and power cable for the I/O bus p. 17, 18
- Sizing power wire by distance and load p. 19
- UI-8-10 terminal connections p. 41
- Setting the UI-8-10-10V pull-up and voltage range switches p. 43, 44
- Wiring DO-4-R relay outputs p. 101
- Supervising DO-4 outputs for UL1076 with a UI-8 input p. 102
- Setting AC-1 reader power p. 136
Good to know
- The bus shield pin is not an earth ground; all shields must be connected together. p. 14
- Voltage drop to the furthest remote module is limited: 2V for 24 VDC modules, 12V for 10-28 VDC modules. p. 18
- On the UI-8-10-10V, the reference resistor ON together with the 10V range is an invalid setting. p. 44
- A 0-10V input reads as 0-5V, so the point needs a conversion of ElecValue * 2. p. 44
- Setting the AC-1 reader power switch to 12 V for a 5 V reader may damage the unit. p. 136
Questions this manual answers
How many I/O modules can one Continuum NetController run?
Up to 32, but the power supply capacity can lower that; auxiliary supplies can be added to reach 32. p. 16
How much power does a UI-8-10 use?
0.7 Watt (29 mA) at 24VDC maximum, with a 10-28V supply range. p. 40
How do I set a UI-8-10-10V input for 0-10 V?
Set that input's voltage range switch to 0-10 V, turn its reference resistor switch off, and use a conversion of ElecValue * 2. p. 44
How long can the Continuum I/O bus be?
2000 ft. (610 m) on RS-485; on FTT-10A 8858 ft. (2700 m) with double termination or 1640 ft. (500 m) in free topology. p. 17
What card readers work with the AC-1?
Wiegand and proximity readers of up to 64 bits per card, powered at +5 V or +12 V by a switch. p. 134
Contents
Chapters and sections
Each line opens the PDF at its page.
- Front Cover1
- Regulatory Notices3
- I/O Systems Overview5
- Introduction6
- Mechanical Installation8
- CPU-I/O Connections14
- Replacing or Adding I/O Modules30
- Module Configuration31
- Individual Module Wiring36
- Input Modules39
- Output Modules80
- Mixed Modules127
2 more lines, from page 197 on
The whole text · 27 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 31-3
- Pages 4 to 74-7
- Mechanical Installation8-13
- CPU-I/O Connections, pages 14 to 2114-21
- CPU-I/O Connections, pages 22 to 2922-29
- Pages 30 to 3530-35
- Individual Module Wiring36-38
- Input Modules, pages 39 to 4739-47
- Input Modules, pages 48 to 5648-56
- Input Modules, pages 57 to 6557-65
- Input Modules, pages 66 to 7466-74
- Input Modules, pages 75 to 7975-79
- Output Modules, pages 80 to 8980-89
- Output Modules, pages 90 to 9990-99
- Output Modules, pages 100 to 109100-109
- Output Modules, pages 110 to 119110-119
- Output Modules, pages 120 to 126120-126
- Mixed Modules, pages 127 to 136127-136
- Mixed Modules, pages 137 to 146137-146
- Mixed Modules, pages 147 to 156147-156
- Mixed Modules, pages 157 to 166157-166
- Mixed Modules, pages 167 to 176167-176
- Mixed Modules, pages 177 to 186177-186
- Mixed Modules, pages 187 to 196187-196
- Mixed Modules, pages 197 to 206197-206
- Mixed Modules, pages 207 to 216207-216
- Mixed Modules, pages 217 to 222217-222
The file