Page 1 of Andover Continuum I/O System Reference

Manual · Schneider

Andover Continuum I/O System Reference

Manual222 pagesPDF 1.4 MB

Reference manual for installing and wiring Andover Continuum I/O modules, including the UI-8, DO-4, AC-1 and other input and output modules.

Download the PDF1.4 MB

Names · 4 models

The models it names

Filed with · 2 models

Also filed with these models on the old site

Summary

What is in it

Schneider Electric reference for the Andover Continuum I/O system, describing the installation, care and use of the Andover Continuum I/O modules. It covers DIN rail and panel mounting, dimensions, CPU to I/O connections, remote I/O over ACC-LON (RS-485) and LON FTT-10A, module configuration and wiring, then a section per module: UI-8-10 universal inputs, DI-6, DI-8, MI-6, DM-20, AO-4-8, DO-4-R, DO-6-TR, LO-2, DIO-20, AC-1, AC-1A, AC-1 Plus, VS-8-4 and VT-1.

Its parts

  1. Introduction
  2. Mechanical Installation
  3. CPU-I/O Connections
  4. Replacing or Adding I/O Modules
  5. Module Configuration
  6. Individual Module Wiring
  7. Input Modules
  8. Output Modules
  9. Mixed Modules

From the manual

Key facts from this manual

Each line names its page in the PDF.

Schneider Electric reference manual for installing, wiring and using the Andover Continuum I/O modules with the NetController and NetController II CPUs. It covers mechanical installation, the CPU-to-I/O bus, power budgets and cabling, then a chapter per module: UI-8-10 / UI-8-10-10V, DI-6-AC, DI-8, MI-6, DM-20, AO-4-8, DO-4-R / DO-4-R-O, DO-6-TR, LO-2, DIO-20, AC-1, AC-1A, AC-1 Plus, VS-8-4 and VT-1.

Read for this summary: pages 4 to 7, 14 to 19, 39 to 44, 99 to 102 and 133 to 136 of 222.

Document
Installation, care and use of all Andover Continuum I/O modules p. 5
Modules per CPU
32 maximum, also limited by power supply capacity p. 16
I/O bus connector
5 pins: 5 +24 VDC, 4 24 VDC Return, 3 Shield, 2 Comm B, 1 Comm A p. 14
Bus interface
Two-signal serial bus, factory set as RS 485 ACC-LON or LON FTT-10A p. 14
Max bus length
RS-485 2000 ft. (610 m); FTT-10A 8858 ft. (2700 m) double termination, 1640 ft. (500 m) free topology p. 17
Connector part number
01-0010-840 (bus cable connector) p. 15
RS-485 data cable
24-gauge shielded twisted pair, 100-120 ohm; Belden 9729 meets the spec p. 17
Power supplies
PS 120/240 AC 50 U (35 W), AC 85 U (70 W), AC 50 (50 W), AC 85 (85 W), PS -48 DC 50 (50 W) p. 16
UI-8-10 inputs
8 universal inputs, 10-bit: voltage, thermistor, digital, counter or supervised; 0-5 V (UI-8-10-10V: 0-10 V) p. 39
UI-8-10 power
10-28V supply; 0.7 Watt (29 mA) @ 24VDC max. p. 40
UI-8-10 input impedance
5 megohm pull-up disabled, 10K ohm pull-up enabled; 4.4K ohm in 0-10V mode p. 40
UI-8-10 thermistor
10K ohm Type III, -30 to 230°F (-34 to 110°C) p. 40
DO-4-R outputs
4 Form C relays, 240 VAC @ 5 Amps, 30 VDC @ 5 Amps; 2.8 Watts at 24 VDC p. 100
AC-1
1 Wiegand/proximity reader (64 bits), +5 or +12 V reader power, 3 supervised inputs, 2 Form C relays 24 VAC/VDC @ 5 Amp p. 134

What this manual walks you through

  • Plugging modules together and cabling remote modules p. 15
  • Working out how many modules a power supply can carry p. 16
  • Adding the power drawn by card readers and keypads p. 17
  • Choosing data and power cable for the I/O bus p. 17, 18
  • Sizing power wire by distance and load p. 19
  • UI-8-10 terminal connections p. 41
  • Setting the UI-8-10-10V pull-up and voltage range switches p. 43, 44
  • Wiring DO-4-R relay outputs p. 101
  • Supervising DO-4 outputs for UL1076 with a UI-8 input p. 102
  • Setting AC-1 reader power p. 136

Good to know

  • The bus shield pin is not an earth ground; all shields must be connected together. p. 14
  • Voltage drop to the furthest remote module is limited: 2V for 24 VDC modules, 12V for 10-28 VDC modules. p. 18
  • On the UI-8-10-10V, the reference resistor ON together with the 10V range is an invalid setting. p. 44
  • A 0-10V input reads as 0-5V, so the point needs a conversion of ElecValue * 2. p. 44
  • Setting the AC-1 reader power switch to 12 V for a 5 V reader may damage the unit. p. 136

Questions this manual answers

How many I/O modules can one Continuum NetController run?

Up to 32, but the power supply capacity can lower that; auxiliary supplies can be added to reach 32. p. 16

How much power does a UI-8-10 use?

0.7 Watt (29 mA) at 24VDC maximum, with a 10-28V supply range. p. 40

How do I set a UI-8-10-10V input for 0-10 V?

Set that input's voltage range switch to 0-10 V, turn its reference resistor switch off, and use a conversion of ElecValue * 2. p. 44

How long can the Continuum I/O bus be?

2000 ft. (610 m) on RS-485; on FTT-10A 8858 ft. (2700 m) with double termination or 1640 ft. (500 m) in free topology. p. 17

What card readers work with the AC-1?

Wiegand and proximity readers of up to 64 bits per card, powered at +5 V or +12 V by a switch. p. 134

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Front Cover1
  2. Regulatory Notices3
  3. I/O Systems Overview5
  4. Introduction6
  5. Mechanical Installation8
    1. Overall Dimensions11
    2. Enclosure-Mounted Modules12
    3. I/O Module Layout Convention13
  6. CPU-I/O Connections14
    1. Connection of I/O Modules15
    2. Maximum Number of I/O Modules16
    3. Calculating Additional Power Supply Requirements17
    4. Maximum Length of I/O Bus17
    5. Cable Recommendations17
    6. Power Wiring Guideline Table19
    7. Connecting Remote I/O Modules with ACC-LON (RS-485)20
    8. Connecting Remote I/O Modules with LON FTT-10A24
  7. Replacing or Adding I/O Modules30
  8. Module Configuration31
  9. Individual Module Wiring36
    1. General Wiring Concerns for All Modules36
    2. Grounding the Modules36
    3. ESD Warning37
  10. Input Modules39
    1. UI-8-10, UI-8-10-10V39
    2. DI-6-AC, DI-6-AC-HV57
    3. DI-864
    4. MI-673
  11. Output Modules80
    1. DM-2080
    2. AO-4-8, AO-4-8-O90
    3. DO-4-R, DO-4-R-O99
    4. DO-6-TR107
    5. LO-2, LO-2-O115
  12. Mixed Modules127
    1. DIO-20127
    2. AC-1133
    3. AC-1A152
    4. AC-1 Plus171
2 more lines, from page 197 on
  1. VS-8-4, VS-8-4-T197
    1. VT-1203

From the PDF’s own bookmarks.

The whole text · 27 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 31-3
  2. Pages 4 to 74-7
  3. Mechanical Installation8-13
  4. CPU-I/O Connections, pages 14 to 2114-21
  5. CPU-I/O Connections, pages 22 to 2922-29
  6. Pages 30 to 3530-35
  7. Individual Module Wiring36-38
  8. Input Modules, pages 39 to 4739-47
  9. Input Modules, pages 48 to 5648-56
  10. Input Modules, pages 57 to 6557-65
  11. Input Modules, pages 66 to 7466-74
  12. Input Modules, pages 75 to 7975-79
  13. Output Modules, pages 80 to 8980-89
  14. Output Modules, pages 90 to 9990-99
  15. Output Modules, pages 100 to 109100-109
  16. Output Modules, pages 110 to 119110-119
  17. Output Modules, pages 120 to 126120-126
  18. Mixed Modules, pages 127 to 136127-136
  19. Mixed Modules, pages 137 to 146137-146
  20. Mixed Modules, pages 147 to 156147-156
  21. Mixed Modules, pages 157 to 166157-166
  22. Mixed Modules, pages 167 to 176167-176
  23. Mixed Modules, pages 177 to 186177-186
  24. Mixed Modules, pages 187 to 196187-196
  25. Mixed Modules, pages 197 to 206197-206
  26. Mixed Modules, pages 207 to 216207-216
  27. Mixed Modules, pages 217 to 222217-222

The file

Revision and size

RevisionRev. K, April 2010, part number 30-3001-499
PublisherSchneider Electric
Pages222
PDF1.4 MB
TextText from the PDF itself; page 1 is a scan, read by OCR, which may hold reading errors.

The first pages · 3 of 222

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 222
Page 2
Page 2of 222
Page 3
Page 3of 222