Page 39

UI-8-10 UI-8-10, UI-8-10-10V Universal Input Modules The UI-8-10, Andover Continuum’s universal input module, provides 8 universal inputs, software configurable as voltage, thermistor, digital, or counter point types. Each point can also be configured as a supervised input for security monitoring, providing indication of on/off and trouble conditions. This module is a perfect choice for any mix of temperature, pressure, flow, status points, and similar inputs in a control system, with a 0-5 volt input range and 10 bit A/D conversion. The UI-8-10-10V model is available for 0–10V applications. It provides the identical point type selection; but is equipped with individual voltage divider DIP switches on each input, allowing each to be configured for a 0–10 volt range.

FEATURES •

8 Universal Inputs

•

10 bit Resolution

•

0–5V or 0–10V Input Range

•

Supports Voltage, Thermistor, Digital, Counter and Supervised Electrical Types

•

Pull-up Resistor Disable Switches

•

10–28 V Power Supply Range

2

N

2

N

O

O

1

1 3

3

4

4

5

5

6

6

7

7

8

8

Andover Continuum I/O System Reference

35

Page 40

UI-8-10

SPECIFICATIONS ELECTRICAL Power Supply Range: Input Voltage Range: 10-28V. 24V for UL864 and UL294 installations. Power Consumption: 0.7 Watt (29 mA) @ 24VDC (max.); normally provided by Andover Continuum power supply module. Overload Protection: INPUTS Number of Inputs:

8 Universal inputs; 10 bit resolution

Input Types:

Voltage, Thermistor, Digital, Counter, and Supervised

Input Protection:

24V AC/DC allowed to any single input (40V transient voltage suppressor on each input – UI-8-10-10V)

Input Impedance:

5 MΩ w/pull-up disabled; 10 KΩ w/pull-up enabled – UI-8-10 (4.4 KΩ in 0-10V mode UI-8-10-10V)

Input Connections:

Two-piece, 13-position removable terminal block

Voltage: Range: Resolution: Accuracy: Filtering: Calibration:

Thermistor: Type: Range: Resolution: Accuracy:

36

0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection.

UI-8-10 (0–5V) UI-8-10-10V (0–10V mode) 0–5 volts 0–10 volts 5 mV 10 mV ±15 mV (±0.3% FSR) ±40 mV (±0.4% FSR) Corner Frequency at 15 Hz, –20 db/decade Permanent (factory)

10 KΩ, Type III Thermistor -30 to 230°F (-34 to 110°C) 40 to 100°F range (4 to 38°C) 40 to 100°F range (4 to 38°C)

0.20°F typical (0.11°C typical) ± 1.0°F (includes 0.36° error for thermistor) (±0.55°C)

Digital & Counter: Input Type: Frequency: Pulse Width:

Contact Closure 4 Hz max. 125 ms min. (depends on scan time)

Supervised: Input Type:

Single or Double Resistor Supervision, Parallel or Series Circuit

Schneider Electric

Page 41

UI-8-10

I/O Connections The actual input connections are located on a thirteen-position removable screw terminal connector located at the bottom of the module. The inputs are labeled IN1, IN2, IN3, and so forth. Each pair of inputs is followed by its return connection labeled RET, resulting in a sequence of IN1, IN2, RET, IN3, IN4, RET, and so on. The connector allows for an Earth ground connection, eight inputs and four signal returns. The diagram screen printed on the module indicates where each input number is located on the terminal block. These connections are also listed below. Connection

Description

1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12.

Earth Ground IN 1 IN 2 RETURN IN 3 IN 4 RETURN IN 5 IN 6 RETURN IN 7 IN 8 RETURN

O

2

N

2

N

1

O

1

3

3

4

4

5

5

6

6

7

7

8

8

Andover Continuum I/O System Reference

37

Page 42

UI-8-10

Input Circuitry UI-8-10 Inputs are essentially voltmeters. Universal inputs can be configured through software to become one of five different input circuits: ƒ ƒ ƒ ƒ ƒ

Temperature Voltage Digital Counter Supervised

During configuration, the value of the Electrical Type attribute you select tells the controller how to interpret the reading from each input. The following is a simplified schematic of both the UI-8-10 and the UI-8-10-10V Universal inputs:

UI-8-10

UI-8-10-10V

The main difference between the two is the UI-8-10-10V circuit includes a switch selectable front-end voltage divider that effectively divides the 10V input signal by two. The proper switch settings for various modes of operation are listed on the front for the module. Note: Setting the reference resistor enable switch to ‘ON’ and setting the range to ‘10V’ is invalid.

38

Schneider Electric

Page 43

UI-8-10

Each input includes a low-pass filter after the pull-up formed by a series resistor and a parallel capacitor. The resistor is utilized for over-voltage protection in limiting current to two protection diodes (not shown). It is possible to have more than one input share a single return wire. Keep in mind that the current through each input is approximately 0.3mA, so voltage drops occur with long runs of small gauge wire. Pull-up Reference Resistor Selection Switches In some measuring instances it is desirable that there be no pull-up resistor. Instead of physically removing or cutting the resistor off the printed circuit board, the input module includes a pull-up resistor selection switch for each input position. This switch allows you to select whether or not you want a pull-up resistor in the circuit. A small 8-position switch module is accessible from the front of the module when the door is opened.

These switch modules are commonly called “DIP Switches” and require a small object such as the tip of a pen or a small screwdriver to operate them. Each switch position acts as a “slide switch”. Pressing the raised slide marker to the side marked “on” closes or enables the switch. To open or disable the switch position, press the slide marker over to the “off” side.

Input Voltage Range Selection Switches (UI-8-10-10V Only) Andover Continuum I/O System Reference

39

Page 44

UI-8-10 The UI-8-10-10V module allows you to choose from two input voltage ranges. Selection is accomplished by using a switch arrangement that is similar to the operation of the pullup resistor switches. This small 8-position switch module is located to the right of the pullup selector switch and is accessible from the front of the module when the door is opened. The Voltage Range switches allow you to select a range (0-5 V) or (0-10 V) for each input. The 0-5V range allows connections to signals that do not exceed 5.00V. The 0-10V range allows connection to signals up to 10.00V. In this mode the circuit actually uses the same input measuring circuit as the 0-5V range, however, it divides the voltage present by two thereby limiting the internal circuitry to 0-5V. When you read a 010V input the actual reading will be 0-5V. You must adjust your readings for the higher range via formula. This is accomplished by applying a conversion factor to the reading. When creating a 10V InfinityInput, set the Conversion to ElecValue * 2. When using the 10V mode be sure to set the Reference resistor switch to Off.

Note: Setting the Reference Resistor enable switch to ‘ON’ and setting the Range to ‘10V’ is invalid. Switching to 10V inputs dramatically lowers the impedance of the input to 4.4 KΩ.

40

Schneider Electric

Page 45

UI-8-10 Supervisory Inputs UI-8 inputs may be connected as supervisory inputs. The following drawings depict the three types of supervisory inputs that exist - three normally closed and three normally open types. Normally Closed Supervised Inputs NC Series With this type of input wiring, a resistor is placed in series with the input being monitored. When the input contact presents a short circuit (normal closed position) the input is assumed in a normal closed state, the circuit presents a reading of 10 K Ωs at the input.

Circuit Action

Input Senses

Condition

Switch Closed Switch Opened Wire Cut Input Shorted

External Resistance Infinite Resistance Infinite Resistance Zero Ωs

Input contact Closed Input contact Open Input contact Open ‘Violation’ Violation or error

When the input contact is opened, the circuit opens and an infinite resistance is measured. If the wires to the input contact are cut it also appears as an “input contact open” condition. In this case there would be an input contact open without a valid card swipe or valid keypad entry resulting in an “input contact violation”. Shorting the input causes a zero Ω resistance, which also results in an input contact violation. When configuring for this type of contact select: ElecType: Resistor Type:

Supervised NCSeries

Andover Continuum I/O System Reference

41

Page 46

UI-8-10

Normally Closed Supervised Inputs NC Series Parallel With this type of input wiring, two external resistors are added to the input, one in series and the other in parallel. When the input contact switch is closed (normal position) the input contact is assumed to be closed. The circuit presents a reading composed of both resistances in parallel that works out to be half the value of one of them (5 KΩ).

Circuit Action

Input Senses

Condition

Switch Closed Switch Opened Wire Cut Input Shorted

External Resistance ÷ 2 External Resistance Infinite Resistance Zero Ωs

Input contact Closed Input contact Open Violation or error Violation or error

When the input contact is opened the switch opens and the value of the parallel resistor is measured. If the wires to the input contact are cut it appears as an infinite resistance. Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance (open) should result in an error condition. When configuring for this type of contact select: ElecType: Resistor Type:

42

Supervised NCSerPar

Schneider Electric

Page 47

UI-8-10 Normally Open Supervised Inputs NO Series Parallel With this type of input wiring, two external resistors are added to the input, one in series and the other in parallel. When the input contact switch is open (normal position) the input contact is assumed to be closed. The circuit reads the value of the parallel resistor.

Circuit Action

Input Senses

Condition

Switch Closed Switch Opened Wire Cut Input Shorted

External Resistance ÷ 2 External Resistance Infinite Resistance Zero Ωs

Input contact Open Input contact Closed Violation or error Violation or error

When the input contact is opened the switch closes and a reading results that is composed of both resistances in parallel that works out to be half the value of one of them (5 KΩ). If the wires to the input contact are cut it appears as an infinite resistance. Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance (open) should result in an error condition. When configuring for this type of contact select: ElecType: Supervised Resistor Type: NOSeriPar

Andover Continuum I/O System Reference

43