Page 36

Individual Module Wiring This section of the document describes the various I/O modules and presents interfacing information. Each module is presented in its own mini-section. The part number designator for the module being described is printed on the outer edge of each page.

General Wiring Concerns for All Modules Do not remotely ground any part of the input sensor wiring. Remote grounds connected to the return terminal could make the system operate incorrectly or damage the equipment. The signal return is not true earth ground. It is an electronic reference point necessary to interpret the sensor properly. It is recommended that you run input wiring in a conduit separate from AC power or output wiring and avoid long wiring runs. For reliable input operation, follow these input wiring guidelines: •

Never lay wires across the surface of a printed circuit board.

•

Wires should never be within 1 in. or 25 mm of any component on a printed circuit board.

•

Use shielded input wire.

•

Terminate the shield of the input wires at one end of the run only - preferably at the end where your I/O module is located.

•

Be careful when stripping wire not to drop small pieces of wire inside the cabinet.

•

Don’t run your input wiring in the same conduit with AC power.

•

Don’t run your input wiring in the same conduit with your output wiring.

•

Don’t run high and low voltage wiring in the same conduit.

------------------------------------ IMPORTANT -------------------------------------Grounding the Modules All I/O modules except the VS-8 include a metal clip that is built into the locking mechanism on the back of the case. Mounting the module on a metal surface or DIN rail automatically provides an Earth ground. The VS-8 includes a ground stud that must be connected to Earth ground. It is important that this connection be made as close to the module as possible. Caution Do not externally ground any input signal connected to the module. This may damage the unit. Signal return terminals are not connected to Earth Ground. When installing Andover Continuum I/O modules it is imperative that the installer supply a solid Earth ground connection to the pins provided.

32

Schneider Electric

Page 37

Electro Static Discharge (ESD) Warning To avoid damaging electronic components due to the discharge of static electricity, always ground yourself before touching any boards or other internal components of Schneider Electric devices. •

At the very least, touch metal first.

•

If possible, use a grounding strap or heel plate.

On each I/O module, the left-most pin is labeled with a ground symbol and should have a short earth ground connection made to it. The wire should be as short as possible, ideally 6 inches or less, and the wire gauge should be a minimum of 18 AWG.

Earth Ground

Failure to install these grounds can result in controller resets or physical damage to the CPU or I/O modules. Later shipments of I/O Modules include a grounding clip built into the DIN Rail clamp of the module. If the Din Rail itself is grounded you will no longer need to ground the I/O modules. You will still need to ground the CPU Modules.

Andover Continuum I/O System Reference

33

Page 38

Limitations of Non-Volatile Memory Flash memory devices used in our products are guaranteed for a minimum of 10,000 write operations. Flash memory is for storing completed configurations and a snapshot of data at a particular time. When used in this manner, the memory should last the lifetime of the product.

34

Schneider Electric