Andover Continuum I/O System Reference, pages 30 to 35

Pages 30 to 35 of 222: Replacing or Adding I/O Modules; Module Configuration

The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Andover Controls AC-1, Andover Controls DO-4, Andover Controls UI-8 and Schneider UI-8

Page 30

Replacing or Adding I/O Modules There are two ways to replace an I/O module to minimize the potential for long-term harm to any equipment. The procedure that you follow depends upon the exact installation and the circumstances that exist at the time of replacement. Both procedures are described below. In either case, the controlled equipment must be overridden during the process. If no external method of override exists, the equipment will go off. Remove all power from the NetController and I/O modules: 1. Turn power supply off. 2. Disconnect the batteries. 3. Replace or add the I/O module. 4. Turn power supply on. 5. Reconnect batteries. 6. Reload NetController Remove power to the I/O bus only: 1. Ensure that batteries are connected and fully charged. 2. Turn power supply off. 3. On the CyberStation workstation or Command Terminal Interface, cd to the appropriate controller in the command line: type “set IOUPower = off”. The battery will now only power the CPU and modem (if applicable). 4. Replace or add the I/O module. 5. Restore power. 6. If the NetController version is prior to 1.03, type “set IOUPower = on” in the command line in CyberStation or Command Terminal Interface.

26

Schneider Electric

Page 31

Module Configuration This section of the document describes the procedure of configuring each module so that it will be recognized by the Andover Continuum hardware. The following procedure is common to all modules. Follow these instructions in the order given to assure proper operation of the module. It is assumed that you have knowledge or have access to someone who does have knowledge of the operation of the CyberStation workstation. It is also assumed that your CyberStation has configuration capabilities, is operating, logged-in and that the NetController connecting to the modules you are trying to configure has already been configured.

Commissioning a New I/O Module - CyberStation When you install a new I/O module onto the bus you must commission the unit before it will operate properly. Follow the steps below to properly commission an I/O module using the CyberStation workstation: Remove power from the I/O Bus where the module is to be installed Step 1

On the I/O Bus: Connect the IOU Module Connect the IOU Module to the I/O Bus.

Step 2

On the I/O Bus: Restore Power Restore power to the I/O Bus.

Step 3

From CyberStation: Create the IOU Module Log onto a CyberStation and create a new IOU module via the IOUModule editor.

Step 4

From CyberStation: Assign an IOU number to the Module During the creation process, you assign a unique number to the module being configured.

Step 5

If the module is not easily accessible: Enter the module ID into the Module ID text field. Enter the module ID found on the label inside the cover of the module into the field and click the Apply button, then skip to Step 8.

Step 6

If the module is easily accessible: Click the Learn Button on CyberStation After creating the module and assigning the number, click the Learn button. A dialog box displays requesting the operator to press the Commission button on the physical module.

Step 7

On local Modules: Press the Commission button on the Module Press the Commission button found on the front panel of the module. Clicking this button sends information from the module to CyberStation. When you push the Commission button, the dialog box should disappear indicating that it received the information from the module.

Andover Continuum I/O System Reference

27

Page 32

Step 8 On the CyberStation: Refresh the Form When you refresh the form you should notice that the ModuleID for commissioned modules, the ProgramID field and the IO model type (i.e. AO-4-8) are automatically entered. This information was received from the module. Also, the Comm Status should indicate an on-line status.

Commissioning a New I/O Module – Command Terminal When you install a new I/O module onto the bus you must commission the unit before it will operate properly. Follow the steps below to properly commission an I/O module using the Command Terminal: Remove power from the I/O Bus where the module is to be installed Step 1

On the I/O Bus: Connect the IOU Module Connect the IOU Module to the I/O Bus.

Step 2

On the I/O Bus: Restore Power Restore power to the I/O Bus.

Step 3

From the Command Terminal: Create the IOU Module Log onto a Command Terminal and create a new IOU Module (select Edit, then IOU Modules, then enter a name for the new IOU Module).

Step 4

On the Command Terminal: Assign an IOU number to the Module During the creation process, you assign a unique number to the module being configured.

Step 5

If the module is not easily accessible: Enter the module ID into the Module ID text field Enter the module ID found on the label inside the cover of the module into the field and TAB to the Save button and press ENTER, then skip to Step 8.

Step 6

If the module is easily accessible: TAB over to the Learn Button on the Command Terminal After creating the module and assigning the number, TAB over to the Learn button and press ENTER. A dialog box displays requesting the operator to press the Commission button on the physical module.

Step 7

On local Modules: Press the Commission button on the Module Press the Commission button found on the front panel of the module. Clicking this button sends information from the module to the Command Terminal. When you push the Commission button, the dialog box should disappear indicating that it received the information from the module.

Step 8

On the Command Terminal: Save the Form When you save the form you should notice that the ModuleID for commissioned modules, the ProgramID field and the IO model type (i.e. AO-48) are automatically entered. This information was received from the module. Also, the CommStatus should indicate an OnLine status.

28

Schneider Electric

Page 33

Commissioning a Replacement I/O Module - CyberStation When you replace an I/O module**, proceed as follows: Remove power from the I/O Bus where the module is to be installed Note: This procedure is for all modules except when replacing an AC-1 with an AC-1. For that procedure, follow the instructions in the next section. Step 1

Replace the module, re-apply power Remove the old module, connect the new module in its place & re-apply power.

Step 2

From CyberStation: Open the IOUModule Editor Log onto a CyberStation and open the IOUModule editor of the IOU that is being replaced.

Step 3

From CyberStation: Type in the new Module ID text field Enter the module ID found on the label inside the cover of the new IOU module into the field and click the Apply button.

Step 4

From CyberStation: Verify the new IOU Module is online Click Refresh. You should notice that in the ModuleID field for the commissioned module, the ProgramID field and the IO model type (i.e. AO-48) are automatically entered. This information was received from the module. Also, the Comm Status should indicate an on-line status.

Commissioning a Replacement I/O Module – Command Terminal When you replace an I/O module**, proceed as follows: Remove power from the I/O Bus where the module is to be installed Note: This procedure is for all modules except when replacing an AC-1 with an AC-1 Plus. For that procedure, follow the instructions in the next section. Step 1

Replace the module, re-apply power Remove the old module, connect the new module in its place & re-apply power.

Step 2

From the Command Terminal: Edit the IOU Module Log onto a Command Terminal and edit the IOU Module (select Edit, then IOU Modules, then press F2 to bring up the list of IOU Modules).

Step 3

From the Command Terminal: Enter the new module ID into the Module ID text field Enter the module ID found on the label inside the cover of the module into the Module ID field and TAB over to the Save button then press ENTER.

Andover Continuum I/O System Reference

29

Page 34

Step 4 From the Command Terminal: Verify the new IOU Module is online Edit the IOU Module that was replaced (select Edit, then IOU Modules, then press F2 to bring up a list of the IOU Modules, select from the list and press ENTER). You should notice that the ModuleID field for the commissioned module, the ProgramID field and the IO model type (i.e. AO-4-8) are automatically entered. This information was received from the module. Also, the Comm Status should indicate an Online status.

Replacing an AC-1 with an AC-1 Plus Module - CyberStation When you substitute an AC-1 Plus for an AC-1 module, proceed as follows: Step 1

Place Cyberstation in OffLine Edit Mode

Step 2

Record the AC-1 IOU Number Open the AC-1 module editor and note the module's ID (IOU field in the editor)

Step 3

Close the AC-1 editor

Step 4

Delete the AC-1 module (still offline) Remove power from the I/O Bus where the module is to be installed

Step 5

Replace the AC-1 with an AC-1 Plus Physically remove the AC-1 and Replace with an AC-1 Plus and re-apply power to the I/O Bus.

Step 6

Create a new IOU Module Create a new IOU module through CyberStation Explorer (still offline) using the same IOU Number as the AC-1 (NOTE: New IOU name DOES NOT have to match old AC-1 name)

Step 7

Enter the new ModuleID Enter the ModuleID of the new AC-1 Plus (ex: 00-03-63-27-61-00) into the module ID field.

Step 8

Save the new AC-1 Plus module (click OK) and close the editor

Repeat steps 2 through 8 for all AC-1 to AC-1Plus replacements Step 9

Place CyberStation back online

Step 10

Reload the controller

Step 11

Open, then close each AC-1 Plus Module editor After reload is complete, open and close each AC-1 Plus module editor (this step is necessary to relay some information from the controller to the database)

Note: The AC-1 Plus has operational differences from AC-1 and AC-1A modules (i.e. Degrade mode). Please refer to the AC-1, AC-1A and AC-1 Plus sections of this manual for further information.

30

Schneider Electric

Page 35

Replacing an AC-1 with an AC-1 Plus Module – Command Terminal When you substitute an AC-1 Plus for an AC-1 module, proceed as follows: Step 1

Record the AC-1 IOU Number Open the AC-1 module editor and note the module's ID (IOU field in the editor)

Step 2

Close the AC-1 module editor

Step 3

Open the door editor Open the door editor for the door that is associated with the AC-1 to be replaced and set the entry IOU (or exit IOU if appropriate) to 0 (zero).

Step 4

Save and close the door editor

Step 5

Delete the AC-1 module Remove power from the I/O Bus where the module is to be installed

Step 6

Replace the AC-1 with an AC-1 Plus Physically remove the AC-1 and Replace with an AC-1 Plus and re-apply power to the I/O Bus.

Step 7

Create a new IOU Module Create a new IOU module using the same IOU Number as the AC-1 (NOTE: New IOU name DOES NOT have to match old AC-1 name)

Step 8

Learn the AC-1 Plus Module Perform a Learn operation, or populate the Module ID field with the Module ID of the new AC-1 Plus Module.

Step 9

Save the new AC-1 Plus module and close the editor

Step 10

Re-open the door object Re-open the door object changed in Step 3 and restore the entry IOU (or exit IOU if applicable) number, then save and close the door editor.

Andover Continuum I/O System Reference

31