Page 22

CPU with Local and Several Remote ACC-LON I/O Modules: The I/O Bus that needs to be terminated is the one formed by the cable that starts at the NetController and ends at the first remote module. The bus that extends from the NetController through the local I/O stack and the one that starts at the first remote module and extends through subsequent modules do not need termination. In this case, the terminator resistor is connected directly across the communications lines (pins 1 & 2) at the NetController and again at the first remote I/O module.

CPU

Local I/O

5 4 3 2 1

120 Ω Resistor

5 4 3 2 1

Remote I/O Module

18

Schneider Electric

Remote I/O Module

120 Ω Resistor

Page 23

CPU with Two Remote ACC-LON Modules Separated by Distance: The I/O Bus that needs to be terminated is the one formed by both cables on either end of the first remote I/O module. In this case, the bus begins at the NetController, flows by the first remote module and ends at the second. The terminator resistor is connected directly across the communications lines (pins 1 & 2) at the NetController and again at the last remote I/O module. If the last module is actually a stack of directly connected I/O modules, the terminator is placed at the first module of the stack as indicated in the scenario described on the previous page.

CPU

5 4 3 2 1

120 Ω Resistor

5 5 4 4 3 3 2 2 1 1

Remote I/O Module

Remote I/O Module

120 Ω Resistor

Andover Continuum I/O System Reference

19

Page 24

Connecting Remote I/O Modules with LON FTT-10A The ACC LON bus topology wiring (RS-485) consists of a network of I/O modules that are interconnected using a shielded twisted wire pair. In accordance with RS-485 guidelines, all of the devices must be wired in a bus topology to limit electrical reflections and ensure reliable communications. There is a high cost associated with installing and maintaining the cable plant that links together the many elements of an RS-485 based control system. Bus topology wiring is more time consuming and expensive to install because the installer is unable to branch or star the wiring where convenient: all devices must be connected directly to the main bus. The best solution for reducing installation and maintenance costs and simplifying system modifications is a flexible topology communication system. Echelon's free topology transceiver (FTT) technology offers just such a solution, and provides an elegant and inexpensive method of interconnecting the different elements of a distributed control system. The Echelon LON FTT-10A free topology architecture allows you to wire Andover Continuum I/O modules with virtually no topology restrictions. Unlike ACC-LON, the FTT-10A system uses a free topology wiring scheme that supports star, loop, and/or bus wiring. This design has many advantages. First, the installer is free to select the method of wiring that best suits the installation, reducing the need for advanced planning and allowing last minute changes at the installation site. Second, retrofit installations with existing wiring plants can be accommodated with minimal, if any, rewiring. This capability ensures that FTT-10A technology can be adapted to both old and new projects. Finally, free topology permits Andover Continuum systems to be expanded in the future by simply tapping into the existing wiring where it is most convenient to do so. This reduces the time and expense of system expansion, and from the customer's perspective, keeps down the life cycle cost of the free topology network.

IMPORTANT FTT-10A NETWORK INSTALLATION NOTICE The termination and wiring information provided in this guide is a small subset of the complete technical information presented by Echelon Corporation in their FTT-10A installation documentation. It is highly recommended that you obtain their document and read the sections pertaining to network installation. As a courtesy, the Echelon FTT-10A documentation has been included on the TAC TSD website. The document filename is Echelon FTT-10A.pdf

20

Schneider Electric

Page 25

FTT-10A Cable Termination (see important notice on the previous page) When locating an I/O module remotely on a LON FTT-10A-based system, it is necessary to add an external terminator to the wiring to compensate for the distance. The terminator can be connected at both ends or at one central point. * The Schneider Electric implementation of the Lon FTT-10A network can connect to a LinkPower network; however, it does not use the Link Power.

Free Topology Segment In a free topology segment, only one termination is required and may be placed anywhere on the free topology segment. Using 24 AWG cable the maximum loop impedance is 75 Ωs. Termination Non-Link Power network Resistor = 52.30±1%, 1/8W

R1

Termination Link Power network Resistor = 52.30±1%, 1/8W Capacitors = 100 μF 50V min.

52.3 Ω ± 1%

Doubly Terminated Bus Topology Segment In a doubly terminated bus topology, two terminations are required, one at each end of the bus. Using 24 AWG cable the maximum loop impedance is 150 Ωs. Termination Non-Link Power network Resistor = 105 Ω±1%, 1/8W

R1

Termination Link Power network Resistor = 105 Ω±1%, 1/8W Capacitors = 100 μF 50V min.

105 Ω ± 1%

Andover Continuum I/O System Reference

21

Page 26

The following characteristics apply when using doubly terminated or free topology wiring schemes: 1. 2. 3.

Network lengths vary for doubly terminated vs. free topology. Network lengths vary based on cable type. FTT-I/O has two specifications for a free topology network: total wire length and node-to-node wire length (which also applies to termination).

A doubly terminated bus may have stubs of up to 3 meters from a bus to each node. Doubly Terminated Bus Topology Specifications

Belden 85102 Belden 8471 Level IV, 22AWG JY (St) Y 2x2x0.8 TIA Category 5

Maximum bus length (meters) 2700 2700 1400 900 900

The free topology transmission specification includes two components that must be met for proper system operation. The distance from each transceiver to all other transceivers and to the termination (including the LPI-10 termination, if used) must not exceed the maximum node-to-node distance. If multiple paths exist, e.g., a loop topology, then the longest path should be used for calculations. The maximum total wire length is the total amount of wire connected per segment. Free Topology Specifications

Belden 85102 Belden 8471 Level IV, 22AWG JY (St) Y 2x2x0.8 TIA Category 5

Maximum nodeto-node distance (meters) 500 400 400 320 250

Maximum total wire length (meters) 500 500 500 500 450

The following pages contain diagrams of typical installations that indicate the correct placement of the terminator:

22

Schneider Electric

Page 27

Example of Maximum Total and Node-to-Node Lengths

Power Supply

CPU

I/O

I/O

Maximum Wire Length

Node-to-Node Length

I/O

I/O

I/O

Andover Continuum I/O System Reference

23

Page 28

CPU with Local and a CPU with Several Remote FTT-10A I/O Modules*:

Power Supply

CPU

I/O

I/O

I/O

I/O

3

I/O

2 1

Power Supply

CPU

I/O

I/O

I/O

I/O

I/O

3 2 1

* See Important Installation Notice on page 20

24

Schneider Electric

52.3 Ω

52.3 Ω

Page 29

CPU with Several Remote FTT-10A I/O Modules and Doubly Terminated Bus*:

Power Supply

3

CPU

2

105 Ω

1 I/O

I/O

I/O

I/O

3

I/O

2

105 Ω

1

* See Important Installation Notice on page 20

Andover Continuum I/O System Reference

25