The text of a manual · part 4 of 27
Andover Continuum I/O System Reference: CPU-I/O Connections, pages 14 to 21
Pages 14 to 21 of 222, from Andover Continuum I/O System Reference
The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Andover Controls AC-1, Andover Controls DO-4, Andover Controls UI-8 and Schneider UI-8
Page 14
CPU-I/O Connections The Andover Continuum NetController/NetController II CPU module includes a connector on the upper right side of its case for further distribution of the 24 VDC input power and special I/O communications signals to all I/O modules. Andover Continuum I/O modules use these signals for power and communications. The power-I/O connector is a five pin male assembly that is designed to easily insert directly into the left side connector of any I/O module. The signals within this connector are as follows:
PIN 5
Function +24 VDC
4
24 VDC Return
3
Shield
2
Comm B
1
Comm A
5 4 3 2 1
The main system power supply generates a +24 VDC source for the CPU. This power source is received through the input power connector on the left side of the CPU module and sent through to pins 4 and 5 of this connector. All Andover Continuum I/O modules can operate at 24V. Some have extended ranges to allow operation at lower voltages. Refer to the individual specifications for each module. Communications between the CPU and I/O modules is through a two-signal serial interface that is factory configured as either RS 485 ACC-LON or LON FTT-10A. Pins 1 and 2 (Comm B and Comm A) provide the electrical connection for this interface. Pin 3 (Shield) is the communications signal shield connection. This is not an Earth ground connection. Proper shielding requires that the installer connect all shields together. The CPU (if grounded properly) provides the single Earth ground point for all modules. Each I/O also has its own Earth ground connection.
10
Schneider Electric
Page 15
Connection of I/O Modules When installing I/O modules it is imperative that the installer supply a solid Earth ground connection to the pins provided. The CPU can directly connect to I/O without the use of cables through a system of built-in plugs and jacks. All I/O modules include two complementary module inter-connectors. Creating a system is as simple as physically plugging the modules together.
Power Supply
CPU
Power Supply
I/O
CPU
I/O
I/O
I/O
In vertical extended systems, I/O modules may be located above or below other modules. In this case, cable assemblies bridge the I/O modules together.
I/O
Power Supply
CPU
The cables necessary to connect the CPU and external I/O modules are attached using a plug-in screw terminal connector. Connection between the modules is one-to-one straightforward wiring as shown below: 5 4 3 2 1
5 4 3 2 1
Connectors are available from Schneider Electric under part number 01-0010-840.
Andover Continuum I/O System Reference
11
Page 16
Maximum Number of I/O Modules The Andover Continuum system allows a maximum of 32 I/O modules per CPU. There is also a limit based upon the capacity of the power supply feeding the modules. Note: It is possible to insert auxiliary power supplies into the I/O bus to increase the number of modules supported, up to a maximum of 32. The Andover Continuum Power Supply Reference, 30-3001-702, includes information on auxiliary supply installation. • PS 120/240 AC 50 U, UPS power supply: • PS 120/240 AC 85 U, UPS power supply: • PS 120/240 AC 50, non-UPS power supply: • PS 120/240 AC 85, non-UPS power supply: • PS –48 DC 50, Battery operated power supply:
35 Watts of power available 70 Watts of power available 50 Watts of power available 85 Watts of power available 50 Watts of power available
UPS power supplies (models with the designation ‘U’) include battery charging circuitry that consumes 15 Watts of the total power available. This is why the UPS supplies are listed with less available Wattage. To determine the maximum number of I/O modules each power supply can support, subtract the power requirements for each module from the maximum available per supply. If the supply also powers a NetController, be sure to subtract the 10 Watts it consumes. The power requirements for the NetController and each I/O module* is listed below: Module NetController UI-8-10 & UI-8-10-10V; Universal Input Modules DI-6 AC & DI-6 AC HV; AC Digital Input Modules DI-8; Digital Input Module MI-6; MilliAmp Input Module DM-20; Digital Input/Output Module AO-4-8 & AO-4-8-O; Analog Output Modules DO-4(A)-R & DO-4(A)-R-O; Relay Output Modules DO-6-TR; Triac Output Module LO-2 & LO-2-O; Lighting Output Modules AC-1; Door, Access Control, Module AC-1A; Door, Access Control, Module AC-1 Plus; Door, Access Control, Module VS-8 & VS-8-T; Video Switch Module VT-1; Voice Telecom Module
Power @24.0 VDC (Watts) (mA) 10 0.7 0.7 0.8 3.8 0.5 ** 3.8 2.8 1.1 0.4 2.6 ** 2.0 ** 2.2 ** 2.0 1.5
417 29 29 33 158 20 ** 158 116 45 16 108 83 92 83 63
* Power requirements for Display Modules can be found in the Andover Continuum Enclosure and Display Module Reference, 30-3001-711. ** Listed power value does not include any devices attached and powered by the module (card readers or DIO-20). Refer to the formulas on the next page for calculation.
12
Schneider Electric
Page 17
Calculating Additional Power Supply Requirements The DM-20 and all the AC Series access control modules have the built-in capability to power an external device. The module power requirements listed in the table on the previous page does not include power consumption information for these devices. In the case of external card readers and keypads, it is not possible for us to determine the power requirements of all the combinations of manufacturer’s products you might connect. However, we can provide a simple formula to determine any additional power the module may draw when powering those devices. Module
Formula
Example
AC-1:
15 X (Reader/Keypad Current Amps)
15 X 0.05 (50 mA reader) = .75W
Module X Supply Voltage
24 X 0.05 (50 mA reader) = 1.20W
AC-1A: AC-1Plus:
DM-20
Reader/Keypad Current (Amps)
Refer to the DIO-20 section of this document for additional power requirements
Maximum Length of I/O Bus The Andover Continuum I/O Bus is a network. Networks are limited by cable lengths because electrical signals lose power and distort as they travel along wire. The longer the wire, the lower the signal strength. The following are the maximum cable length specifications: RS-485 FTT-10A
2000 ft. (610 m) 8858 ft. (2700 m) double termination 1640 ft. (500 m) free topology
Cable Recommendations Data Cable (Pins 1, 2 and 3) You must use shielded cable for the data lines (pins 1, 2 and 3) to provide reliable communications and to ensure compliance with the Class A FCC limits (USA). ACC-LON (RS-485) The data cable should be 24-gauge (0.25 mm), single-twisted-pair, tinned, shielded copper wire with an impedance of 100-120 Ωs and a nominal velocity of propagation of 78%. Capacitance of the cable should be below 12.5 pF/ft (41 pF/m) between conductors and below 22 pF/ft (72 pF/m) between the conductor connected to ground and the next conductor. The following cable meets all of the data cable specifications: Belden 9729, double twisted pair, shielded
Andover Continuum I/O System Reference
13
Page 18
LON FTT-10A The installer can choose a variety of cables, depending on cost, availability, and performance. Performance can vary with cable type. The transmission specification depends on such factors as resistance, mutual capacitance, and the velocity of propagation. Currently, Schneider Electric has documented system performance on the cable types shown below. They are listed in order of performance. Cable Type
Wire dia./AWG
Belden 85102, single twisted pair, stranded 19/29, unshielded Belden 8471, single twisted pair, stranded 19/29, unshielded, 600C Level IV, twisted pair, typically solid & unshielded TIA568A Category 5, twisted pair
16 16 22 24
If a shielded cable is used, the shield should be connected to earth ground via a 470 kΩ, 1/4 W <=10%, metal film resistor to prevent static charge build-up.
Power Cable (Pins 4 and 5) You should use shielded cable for the power lines as well (pins 4 and 5) to ensure noise immunity and therefore more reliable operation. The shield would be connected to pin 3 like that of the data cable. The gauge of the power cable is determined by the power it carries. As indicated previously, the longer the wire the more voltage drop. Do not allow the power supply voltage measured at the furthest remote module to drop more than the allowable amount: 24 VDC modules: 10-28 VDC modules:
2V (1V for the power run and 1V for the return run) 12V (6V for the power run and 6V for the return run)
Voltage drop can be calculated by using Ohms Law: Voltage=Current x Resistance A table providing some guidelines for choosing wire gauge is included on the next page.
14
Schneider Electric
Page 19
Power Wiring Guideline Table The following is a conservative estimate of typical power consumptions and their related wire gauge and number of feet: 24 VDC Modules 10 AWG
14 16 18 20 22 24
Resistance per 1000 ft (305 m) 2.5 4 6 10 15 24
Total I/O Power Draw (Watts) 20 30 40
50
Distance in Feet (meters) 585 (178) 366 (111) 244 (74) 146 (44) 98 (30) 61 (19)
255 (78) 159 (48) 106 (32) 64 (20) 43 (13) 27 (8)
145 (44) 91 (28) 60 (18) 36 (11) 24 (7) 15 (5)
90 (27) 56 (17) 38 (12) 23 (7) 15 (6) 9 (3)
57 (17) 36 (11) 24 (7) 14 (4) 10 (3) 6 (2)
10 - 28 VDC Modules 10 AWG
14 16 18 20 22 24
Resistance per 1000 ft (305 m) 2.5 4 6 10 15 24
Total I/O Power Draw (Watts) 20 30 40
50
Distance in Feet (meters) 3885 (1184) 2428 (740) 1619 (493) 971 (296) 648 (198) 405 (123)
1905 (581) 1191 (363) 794 (242) 476 (145) 318 (97) 198 (60)
1245 (379) 778 (237) 519 (158) 311 (95) 208 (63) 130 (40)
915 (279) 572 (174) 381 (116) 229 (70) 153 (47) 95 (29)
717 (219) 448 (137) 299 (91) 179 (55) 120 (37) 75 (23)
These tables are intended as a guide. There is no way to account for every Andover Continuum I/O permutation. External noise suppression may be required if the power wiring is run in a noisy environment.
Andover Continuum I/O System Reference
15
Page 20
Connecting Remote I/O Modules with ACC-LON (RS-485) The Andover Continuum system allows I/O modules to be placed in a remote location from the CPU (NetController). Long cable lengths in ACC-LON (RS 485)-based networks can cause signal communications problems on the I/O bus. When locating an I/O module remotely on an RS 485-based bus, it is necessary to add an external 120 Ω terminator resistor to the bus to compensate for the distance. The terminator must be connected at both ends of the bus for proper operation. The following diagrams are typical installations that indicate the correct placement of the terminator:
Simple CPU and 1 ACC-LON Remote I/O Module: The I/O Bus that needs to be terminated is the one formed by the cable attaching the remote module to the CPU. In this case, a terminator resistor is connected across the communications lines (pins 1 & 2) directly at the NetController and again at the remote I/O module.
CPU
5
5
4
4
3
3
2
2
1
1
120 Ω Resistor
16
Schneider Electric
Remote I/O Module
120 Ω Resistor
Page 21
CPU with Local and 1 ACC-LON Remote I/O Module: The I/O Bus that needs to be terminated is the one formed by the cable that starts at the NetController and ends at the remote module. The bus that extends from the NetController through the local I/O stack does not need termination. In this case, the terminator resistor is connected directly across the communications lines (pins 1 & 2) at the NetController and again at the remote I/O module.
CPU
Local I/O
Local I/O
5 4 3 2 1
120 Ω Resistor
5 4 3 2 1
Remote I/O Module
120 Ω Resistor
Andover Continuum I/O System Reference
17