Andover Continuum I/O System Reference: Mechanical Installation
Pages 8 to 13 of 222, from Andover Continuum I/O System Reference
The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Andover Controls AC-1, Andover Controls DO-4, Andover Controls UI-8 and Schneider UI-8
Page 8
Mechanical Installation Each I/O module, except the Display variety, is enclosed in a plastic case that is designed to be mounted on a standard DIN rail or fastened to a panel. Note: In order to meet agency requirements in the United States, it is necessary that the modules along with the power supply and CPU be housed in another metal enclosure i.e., a NEMA box or the Andover Continuum enclosure. Only Schneider Electric enclosure models ENC-0DISP and ENC-3DISP are approved for UL 294 Access Control Systems. The two types of I/O module plastic cases are illustrated below: Status Indicators & switches
Status indicators and operator switches are located on the indicator panel. Other switches available for module configuration may be accessed by lifting the hinged door of the smaller module.
Connections to controlled/sensed equipment
4
Schneider Electric
Page 9
On the back of each module are molded DIN rail guide fingers. The design allows the module to easily hook onto and slide along a standard DIN rail. The fingers also allow the module to be mounted directly to a panel using them as a bracket. A stand-off is molded into the locking finger. To mount the module on a panel, extend the locking fingers and insert screws through the standoffs as shown below:
Locking Fingers
Panel Mounting
DIN Rail Mounting: With the mounting brackets (locking fingers) extended outward, hook the module onto the DIN rail as shown below:
Andover Continuum I/O System Reference
5
Page 10
Slide the module into position.
Press the upper bracket into its locked position.
Press the lower mounting bracket(s) inward until it locks the module in place.
Grounding the Modules All I/O modules except the VS-8 include a metal clip that is built into the locking mechanism on the back of the case. Mounting the module on an electrically conductive metal surface or DIN rail automatically provides an Earth ground. The VS-8 includes a ground stud that must be connected to Earth ground. It is important that this connection be made as close to the module as possible. Note: Anodized Aluminum DIN rails are not electrically conductive.
6
Schneider Electric
Page 11
Overall Dimensions The overall dimensions of the two types of I/O cases are as shown:
6.70'' (170.2 mm)
2.50 '' (63.5 mm)
3.50 '' (88.5 mm)
6.70'' (170.2 mm)
2.50 '' (63.5 mm)
9.0 '' (228.7 mm)
Andover Continuum I/O System Reference
7
Page 12
Enclosure-Mounted Modules The Schneider Electric enclosure provides a place to mount a power supply, CPU and up to 10 DIN rail mounted I/O modules. Several display modules can be affixed to the front panel. The Display modules are designed to fit into openings left by removing panels in the front door. The enclosure is a 6” deep NEMA box with integral display panels, DIN rails, cable troughs and a battery storage compartment.
DIN Rail
Cable Trough
Battery Storage
The enclosure features three DIN rails and cable management accessories. Use of the new enclosure is not required; however, it provides a convenient method of constructing small local systems.
8
Schneider Electric
Page 13
The front door of the enclosure contains removable sections into which special operator display and control modules may be mounted. Alternately, Plexiglas panels may be used to view the status lights of all internal modules when the door is closed.
5HPRYDEOH 'LVSOD\3DQHOV
Spacers for Additional Displays
I/O Module Layout Convention By convention, I/O modules should be separated according to function and whether they are connected to low or high voltages. Typically, Input wires should enter from only one of the wiring troughs, and should come from the left side of the rack. Output wires should enter from the other wiring trough, and should come from the right side of the rack. A good system would be to install all your input modules on one DIN rail, output modules on the next rail, and so on.
Andover Continuum I/O System Reference
9