For the Andover Controls AC-1, Andover Controls DO-4, Andover Controls UI-8 and Schneider UI-8
Page 48
UI-8-10
Wiring Door Switches There are three supervisory inputs for door switches. The maximum length wire you may use is 500 ft of #18 gauge wire (152 m of 1.0 mm2 wire) or 200 ft of #22 gauge wire (60 m of 0.35 mm2 wire). Some switches have built-in resistors that facilitate Series Parallel connections as shown below: Switch with Built-In Resistor
AUX or DOOR or REX
10 KΩ
RET
Wiring Motion Detectors Motion detectors are devices that close a switch contact when motion is detected. Wiring is similar to a normal input contact switch input, however, the motion sensor requires an external power supply of 12 VDC or 24 VDC (UL listed under APHV). The maximum length wire you should use is 500 ft of #18 gauge wire (152 m of 1.0 mm2 wire) or 200 ft of #22 gauge wire (60 m of 0.35 mm2 wire). The following shows a typical motion detector circuit:
44
Schneider Electric
Page 49
UI-8-10 Measuring Temperature UI-8-10 inputs can be configured to sense temperature by configuring one of the module’s inputs appropriately. This is done by setting the Electrical Type to either ACC Temp (DEG F) or ACC Temp (DEG C). Connect a resistive thermistor sensor to that input terminal. The following is a schematic representation of the connection:
IN x Thermistor RET
One lead connects to a numbered input terminal, the other to a return terminal. To use the input for temperature sensing, the pull-up reference resistor must be connected into the circuit, therefore, the reference resistor switch for this input must be placed in the “on” position and the Range switch must be in the 5V position. When the input point is configured as a temperature input, the controller utilizes a look-up table to convert from a voltage reading to a temperature reading in degrees Fahrenheit or Celsius.
Caution Never apply voltage to a thermistor - doing so alters the thermistor’s accuracy and reliability. In fact, it’s a good idea to replace any thermistor that has had any sort of voltage applied to it.
Maximum Wire Runs for Thermistors To keep thermistor errors to a minimum, limit the length of wire runs to the maximum for the gauge wire you select. The following two pages include three tables that indicate the maximum length runs for wires of various gauges to keep errors within certain temperature limits when using thermistor elements.
Andover Continuum I/O System Reference
45
Page 50
UI-8-10 Wire Gauges and Corresponding Maximum Runs for Sensing Temperatures Up to 70 °F (21 °C) Gauge
1/2 °F (.28 °C) Error
1/4 °F (.14 °C) Error
1/10 °F (.06 °C) Error
#14 2.5 mm2
26,700 ft. 8150 m
13,300 ft. 4000 m
5,300 ft. 1600 m
#16 1.5 mm2
16,700 ft. 5120 m
8,300 ft. 2500 m
3,300 ft. 1000 m
#18 1.0 mm2
10,500 ft. 3200 m
5,200 ft. 1600 m
2,100 ft. 640 m
#20 0.5 mm2
6600 ft. 2000 m
3,300 ft. 1000 m
1,300 ft. 400 m
#22 0.35 mm2
4,100 ft. 1250 m
2,000 ft. 600 m
800 ft. 250 m
Wire Gauges and Corresponding Maximum Runs for Sensing Temperatures Up to 100 °F (38 °C) Gauge
1/2 °F (.28 °C) Error
1/4 °F (.14 °C) Error
1/10 °F (.06 °C) Error
#14 2.5 mm2
12,600 ft. 3800 m
6,300 ft. 1900 m
2,500 ft. 760 m
#16 1.5 mm2
7,900 ft. 2400 m
3,900 ft. 1200 m
1,500 ft. 450 m
#18 1.0 mm2
5,000 ft. 1500 m
2,500 ft. 760 m
1,000 ft. 300 m
#20 0.5 mm2
3,100 ft. 950 m
1,500 ft. 450 m
600 ft. 180 m
#22 0.35 mm2
1,900 ft. 580 m
900 ft. 275 m
300 ft. 90 m
Wire Gauges and Corresponding Maximum Runs for Sensing Temperatures Up to 150 °F (65 °C)
46
Gauge
1/2 °F (.28 °C) Error
1/4 °F (.14 °C) Error
1/10 °F (.06 °C) Error
#14 2.5 mm2
4,100 ft. 1250 m
2,000 ft. 600 m
800 ft. 240 m
#16 1.5 mm2
2,600 ft. 800 m
1,300 ft. 400 m
500 ft. 150 m
#18 1.0 mm2
1,600 ft. 500 m
800 ft. 240 m
300 ft. 90 m
#20 0.5 mm2
1,000 ft. 300 m
500 ft. 150 m
200 ft. 60 m
#22 0.35 mm2
600 ft. 180 m
300 ft. 90 m
100 ft. 30 m
Schneider Electric
Page 51
UI-8-10 Measuring DC Voltages The UI-8-10 inputs may be configured to sense DC voltage by connecting the input terminals to a DC voltage source within the range of the module’s input specifications. The following is a schematic representation of the connection:
IN x
+ V -
RET
The plus lead connects to the numbered input terminal, the other to a return terminal. When interfacing to a voltage output sensor, specific information on the transducer may be required. The pull-up resistor of the input circuit will affect the output of the transducer. 10V Input Notes Although the 10V input configuration allows you to measure a higher voltage, it is scaled so that you still measure a value of 0-5V. You have to convert the reading in your conversion equation. When the input is configured for 10V operation, the input resistance is 4.4kΩs. Therefore, the sensor would have to be able to source as much as 2.3mA. When configuring either type of voltage input, select: ElecType: Reference Resistor
Voltage OFF
Andover Continuum I/O System Reference
47
Page 52
UI-8-10 Voltage Dividers There are instances when it is necessary to interface to a voltage source that is higher than the input range of the module. In these cases a voltage divider is necessary.
External DC input Voltage Divider Two resistor values set up a ratio of voltage drop. These resistors must be sized appropriately (value and wattage) for the source being monitored. The higher the resistance values, the less loading effect there will be on the source.
The circuit shown above is a simple two-resistor voltage divider connected to one of the UI-8-10 module’s inputs. The input circuitry of the module can measure a maximum of either 5 Volts or 10 Volts (UI-8-10-10V only). Therefore, the voltage measured across the reference resistor must not exceed this maximum. In this case, be sure to switch the pull-up resistor out of the circuit.
48
Schneider Electric
Page 53
UI-8-10 Assuming you know the maximum voltage reading you are trying to measure (Vsource), perform the following steps to determine the resistance values necessary to condition the input for the module. If you have the UI-8-10-10V model, set the Range switch to 5V. 1. First, determine the current that will flow through the divider. Pick a value that your source can supply. Let’s say 20 mA. This value will be represented by the variable Itotal in the following equations. 2. Determine the total resistance value required of the entire divider (R1 + R2) to create 20mA given the source voltage by solving the following: Rtotal = Vsource Itotal Example: if you are measuring a source that can supply 0- 30 V: Rtotal = 30 V 20 mA Rtotal = 30 V .02 A Rtotal = 1500 Ω The current is constant through the two resistors. Knowing this and the fact that our input can’t exceed 5V can determine the value of the resistor labeled R2. 3. Determine the value of R2 by solving the following: R2 = Vinput Itotal R2 = 5 V .02 A R2 = 250 Ω Through subtraction, you can determine the remaining resistor value: Rtotal = R1 + R2 R1 = 1500 Ω - 250 Ω R1 = 1250 Ω
Andover Continuum I/O System Reference
49
Page 54
UI-8-10 Sensing Contact Closures (Digital) Digital input points are designed to allow the monitoring of contact closures across an input (contact wired between the input and return).
IN x Contact Closure RET
Note: When configuring a Digital point, there is a “Polarity” attribute. If this attribute is enabled, readings are reversed: “On” will occur when the contact is open, and “Off” occurs when the contact is closed.
When configuring this type of input, select: ElecType: Reference Resistor
50
Schneider Electric
Digital ON
Page 55
UI-8-10
Counting Pulsing Signals or Contact Closures Counter inputs are designed to allow the monitoring of digital pulse trains or contact closures across an input just like digital inputs, but they accumulate a total of those closures and act like a counter. When using an input as a counter, you must take into account the frequency of the input signal being counted. Universal inputs do not allow for very high speed contact counting. This module allows counting up to a maximum of 4 Hz or 4 contact closures per second. Minimum Pulse Width The high period of the signal must be at least 125 milliseconds. The low period of the signal must be at least 125 milliseconds. When configuring this type of input, select: ElecType: Reference Resistor
Counter ON
Andover Continuum I/O System Reference
51
Page 56
UI-8-10 Status/Control Panel Status Indicators The UI-8-10 module includes a complete indicator status panel on the front of the module.
This panel includes indicators reporting on the status of the following: POWER
This green indicator illuminates when DC power is applied through the I/O Bus.
COMM
This yellow indicator illuminates when data is transmitted from the module to the NetController. In normal operation, data is only transmitted when an input value changes. This indicator will also flash periodically as the NetController checks the I/O bus.
STATUS
This red indicator is normally off. If it is always on or flashing at a fast rate there is a problem with the module. This indicator can be manually illuminated from the CyberStation workstation or Command Terminal Interface and used as a troubleshooting aid when locating a particular module.
This panel also includes two operator switches that perform the following: COMMISSION
After physical installation and during configuration through the CyberStation workstation or Command Terminal Interface, pressing this button registers the module’s address with the system. For more information, refer to the section on Module Configuration found earlier in this manual.
RESET
If the module becomes inoperable, pressing this button resets the module. It does not erase its memory.
52