Page 57
DI-6-AC
DI-6-AC, DI-6-AC-HV Digital AC Input Modules The DI-6-AC, Andover Continuum’s digital AC input module, has six digital (“wet”) AC inputs for cost-effective ON-OFF status indication of fan motor starters, solenoid valves, control relays, or external power supplies, and similar applications that require a quick and easy way to detect voltage. The DI-6-AC monitors the absence or presence of AC voltage levels directly, with no interposing relays needed. The DI-6-AC can monitor voltages from 20–132V. A DI-6-AC-HV model is also available for sensing higher voltages (90–250V). Both models can also accept DC voltages. All inputs are optically coupled with 2500V isolation on each input for noise-free operation.
FEATURES •
6 optically-coupled, digital AC input channels
•
Independently Mounted
•
Will accept AC or DC inputs
•
20–132V AC Input Range (DI-6-AC) 90–250V AC Input Range (DI-6-AC-HV)
Andover Continuum I/O System Reference
53
Page 58
DI-6-AC SPECIFICATIONS ELECTRICAL Power Supply Range: Input Voltage Range: 20-26V. Power Consumption: 0.7 Watt (29 mA) @ 24VDC (max.); normally provided by Andover Continuum power supply module. Overload Protection: INPUTS Number of Inputs:
0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection. 6 digital AC voltage inputs
Input Protection:
2500V isolation on each input. Each input has a 270V MOV.
Input Connections:
Two-piece, 13-position removable terminal block
Input Range: Input Current:
DI-6-AC
DI-6-AC-HV
20–132 Vrms 5 mA max.
90–250 Vrms 2 mA max. DI-6-AC
DI-6-AC-HV
AC Voltage “ON” Threshold: (Above this voltage is considered “ON”)
16 Vrms
75 Vrms
AC Voltage “OFF” Threshold: (Below this voltage is considered “OFF”)
8 Vrms
30 Vrms
Input Resistance (±5%):
30 KΩ
200 KΩ
Maximum Turn ON Time: Maximum Turn OFF Time:
20 mS 60 mS
20 mS 60 mS
DC Input Voltage Range: Pulse Width: DC Input Current: DC Voltage “ON” Threshold:
20–132V 90–250V 125mS min. (depends on scan time) 5mA (max.) 2mA (max.) 20V 90V (Above this voltage is considered “ON”)
DC Voltage “OFF” Threshold:
12V 45V (Below this voltage is considered “OFF”)
EUROPEAN STANDARDS European Multi-Purpose Control–Electronic Type 1B–Micro Disconnect
54
Schneider Electric
Page 59
DI-6-AC
I/O Connections The actual input connections are located on a thirteen-position removable screw terminal connector located at the bottom of the module. The inputs are labeled IN1, IN2, IN3, and so forth. Each pair of terminals corresponds to one input. With both AC and DC signals there is no polarity to observe during connection. The connector allows for an Earth ground connection, eight inputs and four signal returns. The diagram screen printed on the module indicates where each input number is located on the terminal block. These connections are also listed below.
Connection
Description
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12.
Earth Ground IN 1 IN 1 IN 2 IN 2 IN 3 IN 3 IN 4 IN 4 IN 5 IN 5 IN 6 IN 6
Andover Continuum I/O System Reference
55
Page 60
DI-6-AC Input Circuitry The following is a simplified schematic of both the DI-6-AC and the DI-6-AC-HV Digital Input module:
AC OptoCoupler
15K
IN x
275V MOV
15K
RET
AC to DC Converter
II
AC to DC Converter
II
10V
DI-6-AC
275V MOV
RET
AC OptoCoupler
100K
IN x
100K
40V
DI-6-AC-HV
The main difference between the two is the DI-6-AC-HV circuit includes a front end that supports the higher voltages.
56
Schneider Electric
Page 61
DI-6-AC Sensing AC or DC Digital Inputs Digital input points are designed to provide an ON or OFF reading of a signal. Normally you would associate an AC or DC voltage input with a value measurement, however, the DI-6 modules include a voltage level trigger that senses the presence of a range of voltages and converts those readings to ON and OFF indications.
AC Signal
IN x
DC Signal
Polarity Independent
IN x
The determination of ON or OFF is based upon the following measurement thresholds: DI-6-AC
DI-6-AC-HV
AC Voltage “ON” Threshold: (Above this voltage is considered “ON”)
16 Vrms
75 Vrms
AC Voltage “OFF” Threshold: (Below this voltage is considered “OFF”)
8 Vrms
30 Vrms
DC Voltage “ON” Threshold: (Above this voltage is considered “ON”)
20V
90V
DC Voltage “OFF” Threshold: (Below this voltage is considered “OFF”)
12V
45V
Note: When configuring a Digital point, there is a ‘Polarity’ attribute. If this attribute is enabled, readings are reversed: ‘ON’ will occur when the input is at the normal OFF threshold. OFF occurs at the normal ON threshold. When configuring either type of input, select: ElecType:
Digital
Andover Continuum I/O System Reference
57
Page 62
DI-6-AC Status/Control Panel Status Indicators The DI-6-AC module includes a complete indicator status panel on the front of the module.
This panel includes indicators reporting on the status of the following: POWER
This green indicator illuminates when DC power is applied through the I/O Bus.
COMM
This yellow indicator illuminates when data is transmitted from the module to the NetController. In normal operation, data is only transmitted when an input value changes. This indicator will also flash periodically as the NetController checks the I/O bus.
STATUS
This red indicator is normally off. If it is always on or flashing at a fast rate there is a problem with the module. This indicator can be manually illuminated from the CyberStation workstation or Command Terminal and used as a troubleshooting aid when locating a particular module.
INPUT
58
These red indicators (one for each channel) illuminate when an ‘ON’ condition is sensed.
Schneider Electric
Page 63
DI-6-AC This panel also includes two operator switches that perform the following: COMMISSION
After physical installation and during configuration through CyberStation or Command Terminal, pressing this button registers the module’s address with the system. For more information, refer to the section on Module Configuration found earlier in this manual.
RESET
If the module becomes inoperable, pressing this button resets the module. It does not erase its memory.
Andover Continuum I/O System Reference
59
Page 64
DI-8 DI-8 Digital Input Module The DI-8, Andover Continuum’s digital input module, is used for cost-effective sensing of multiple dry digital inputs in applications such as equipment status monitoring or alarm point monitoring. The DI-8 has eight digital inputs⎯each can be software configured to accept a digital (contact closure or 0–5 volt input) or counter signal. Counter frequency is 10Hz on all eight inputs. In addition, high speed counting up to 10KHz max. is available (via a DIP switch) on Channels 1 and 2 for high-speed metering and industrial applications. 40V transient suppressors on all eight inputs protect against high voltage short duration transients events. The DI-8 is designed to accept dry contact inputs or 0-5 volts and can withstand up to 24 VAC/DC continuous voltage on four channels.
FEATURES
60
Schneider Electric
•
Allows interface to relay contact closures or 0–5v digital signals.
•
Allows high speed counting on channels 1 and 2.
•
Input protection allows accidental wiring of 24VAC to inputs.
•
10–28 V Power Supply Range
Page 65
DI-8 SPECIFICATIONS ELECTRICAL Power Supply Range: Input Voltage Range: 10-28V. 24V for UL864 and UL294 installations. Power Consumption: 0.8 Watt (33 mA) @ 24VDC (max.); normally provided by Andover Continuum power supply module. Overload Protection: INPUTS Number of Inputs:
0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection. 8 digital inputs
Input Types:
Digital or Counter, software selectable
Input Protection:
24V AC/DC applied to 4 channels max. (40V transient protection on each input)
Input Impedance:
10 KΩ pull-up resistor referenced to +5V
Input Connections:
Two-piece, 13-position removable terminal block
Digital: Input Type: Pulse Width: Current:
Contact closure or 0–5V input 50 ms minimum 0.5 mA
Counter: Input Type:
Contact closure or 0–5V input
Channels 1 and 2 in HI-speed mode: Frequency: Pulse Width: Current:
10 kHz (max.) 50 µs (min.) 0.5 mA
Channels 3 through 8; and Channel 1 and 2 in LO-speed mode: Frequency: Pulse Width: Current:
10Hz (max.) 50 ms (min.) 0.5mA
Andover Continuum I/O System Reference