Andover Continuum I/O System Reference: Input Modules, pages 57 to 65

Pages 57 to 65 of 222, from Andover Continuum I/O System Reference

The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Andover Controls AC-1, Andover Controls DO-4, Andover Controls UI-8 and Schneider UI-8

Page 57

DI-6-AC

DI-6-AC, DI-6-AC-HV Digital AC Input Modules The DI-6-AC, Andover Continuum’s digital AC input module, has six digital (“wet”) AC inputs for cost-effective ON-OFF status indication of fan motor starters, solenoid valves, control relays, or external power supplies, and similar applications that require a quick and easy way to detect voltage. The DI-6-AC monitors the absence or presence of AC voltage levels directly, with no interposing relays needed. The DI-6-AC can monitor voltages from 20–132V. A DI-6-AC-HV model is also available for sensing higher voltages (90–250V). Both models can also accept DC voltages. All inputs are optically coupled with 2500V isolation on each input for noise-free operation.

FEATURES •

6 optically-coupled, digital AC input channels

•

Independently Mounted

•

Will accept AC or DC inputs

•

20–132V AC Input Range (DI-6-AC) 90–250V AC Input Range (DI-6-AC-HV)

Andover Continuum I/O System Reference

53

Page 58

DI-6-AC SPECIFICATIONS ELECTRICAL Power Supply Range: Input Voltage Range: 20-26V. Power Consumption: 0.7 Watt (29 mA) @ 24VDC (max.); normally provided by Andover Continuum power supply module. Overload Protection: INPUTS Number of Inputs:

0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection. 6 digital AC voltage inputs

Input Protection:

2500V isolation on each input. Each input has a 270V MOV.

Input Connections:

Two-piece, 13-position removable terminal block

Input Range: Input Current:

DI-6-AC

DI-6-AC-HV

20–132 Vrms 5 mA max.

90–250 Vrms 2 mA max. DI-6-AC

DI-6-AC-HV

AC Voltage “ON” Threshold: (Above this voltage is considered “ON”)

16 Vrms

75 Vrms

AC Voltage “OFF” Threshold: (Below this voltage is considered “OFF”)

8 Vrms

30 Vrms

Input Resistance (±5%):

30 KΩ

200 KΩ

Maximum Turn ON Time: Maximum Turn OFF Time:

20 mS 60 mS

20 mS 60 mS

DC Input Voltage Range: Pulse Width: DC Input Current: DC Voltage “ON” Threshold:

20–132V 90–250V 125mS min. (depends on scan time) 5mA (max.) 2mA (max.) 20V 90V (Above this voltage is considered “ON”)

DC Voltage “OFF” Threshold:

12V 45V (Below this voltage is considered “OFF”)

EUROPEAN STANDARDS European Multi-Purpose Control–Electronic Type 1B–Micro Disconnect

54

Schneider Electric

Page 59

DI-6-AC

I/O Connections The actual input connections are located on a thirteen-position removable screw terminal connector located at the bottom of the module. The inputs are labeled IN1, IN2, IN3, and so forth. Each pair of terminals corresponds to one input. With both AC and DC signals there is no polarity to observe during connection. The connector allows for an Earth ground connection, eight inputs and four signal returns. The diagram screen printed on the module indicates where each input number is located on the terminal block. These connections are also listed below.

Connection

Description

1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12.

Earth Ground IN 1 IN 1 IN 2 IN 2 IN 3 IN 3 IN 4 IN 4 IN 5 IN 5 IN 6 IN 6

Andover Continuum I/O System Reference

55

Page 60

DI-6-AC Input Circuitry The following is a simplified schematic of both the DI-6-AC and the DI-6-AC-HV Digital Input module:

AC OptoCoupler

15K

IN x

275V MOV

15K

RET

AC to DC Converter

II

AC to DC Converter

II

10V

DI-6-AC

275V MOV

RET

AC OptoCoupler

100K

IN x

100K

40V

DI-6-AC-HV

The main difference between the two is the DI-6-AC-HV circuit includes a front end that supports the higher voltages.

56

Schneider Electric

Page 61

DI-6-AC Sensing AC or DC Digital Inputs Digital input points are designed to provide an ON or OFF reading of a signal. Normally you would associate an AC or DC voltage input with a value measurement, however, the DI-6 modules include a voltage level trigger that senses the presence of a range of voltages and converts those readings to ON and OFF indications.

AC Signal

IN x

DC Signal

Polarity Independent

IN x

The determination of ON or OFF is based upon the following measurement thresholds: DI-6-AC

DI-6-AC-HV

AC Voltage “ON” Threshold: (Above this voltage is considered “ON”)

16 Vrms

75 Vrms

AC Voltage “OFF” Threshold: (Below this voltage is considered “OFF”)

8 Vrms

30 Vrms

DC Voltage “ON” Threshold: (Above this voltage is considered “ON”)

20V

90V

DC Voltage “OFF” Threshold: (Below this voltage is considered “OFF”)

12V

45V

Note: When configuring a Digital point, there is a ‘Polarity’ attribute. If this attribute is enabled, readings are reversed: ‘ON’ will occur when the input is at the normal OFF threshold. OFF occurs at the normal ON threshold. When configuring either type of input, select: ElecType:

Digital

Andover Continuum I/O System Reference

57

Page 62

DI-6-AC Status/Control Panel Status Indicators The DI-6-AC module includes a complete indicator status panel on the front of the module.

This panel includes indicators reporting on the status of the following: POWER

This green indicator illuminates when DC power is applied through the I/O Bus.

COMM

This yellow indicator illuminates when data is transmitted from the module to the NetController. In normal operation, data is only transmitted when an input value changes. This indicator will also flash periodically as the NetController checks the I/O bus.

STATUS

This red indicator is normally off. If it is always on or flashing at a fast rate there is a problem with the module. This indicator can be manually illuminated from the CyberStation workstation or Command Terminal and used as a troubleshooting aid when locating a particular module.

INPUT

58

These red indicators (one for each channel) illuminate when an ‘ON’ condition is sensed.

Schneider Electric

Page 63

DI-6-AC This panel also includes two operator switches that perform the following: COMMISSION

After physical installation and during configuration through CyberStation or Command Terminal, pressing this button registers the module’s address with the system. For more information, refer to the section on Module Configuration found earlier in this manual.

RESET

If the module becomes inoperable, pressing this button resets the module. It does not erase its memory.

Andover Continuum I/O System Reference

59

Page 64

DI-8 DI-8 Digital Input Module The DI-8, Andover Continuum’s digital input module, is used for cost-effective sensing of multiple dry digital inputs in applications such as equipment status monitoring or alarm point monitoring. The DI-8 has eight digital inputs⎯each can be software configured to accept a digital (contact closure or 0–5 volt input) or counter signal. Counter frequency is 10Hz on all eight inputs. In addition, high speed counting up to 10KHz max. is available (via a DIP switch) on Channels 1 and 2 for high-speed metering and industrial applications. 40V transient suppressors on all eight inputs protect against high voltage short duration transients events. The DI-8 is designed to accept dry contact inputs or 0-5 volts and can withstand up to 24 VAC/DC continuous voltage on four channels.

FEATURES

60

Schneider Electric

•

Allows interface to relay contact closures or 0–5v digital signals.

•

Allows high speed counting on channels 1 and 2.

•

Input protection allows accidental wiring of 24VAC to inputs.

•

10–28 V Power Supply Range

Page 65

DI-8 SPECIFICATIONS ELECTRICAL Power Supply Range: Input Voltage Range: 10-28V. 24V for UL864 and UL294 installations. Power Consumption: 0.8 Watt (33 mA) @ 24VDC (max.); normally provided by Andover Continuum power supply module. Overload Protection: INPUTS Number of Inputs:

0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection. 8 digital inputs

Input Types:

Digital or Counter, software selectable

Input Protection:

24V AC/DC applied to 4 channels max. (40V transient protection on each input)

Input Impedance:

10 KΩ pull-up resistor referenced to +5V

Input Connections:

Two-piece, 13-position removable terminal block

Digital: Input Type: Pulse Width: Current:

Contact closure or 0–5V input 50 ms minimum 0.5 mA

Counter: Input Type:

Contact closure or 0–5V input

Channels 1 and 2 in HI-speed mode: Frequency: Pulse Width: Current:

10 kHz (max.) 50 µs (min.) 0.5 mA

Channels 3 through 8; and Channel 1 and 2 in LO-speed mode: Frequency: Pulse Width: Current:

10Hz (max.) 50 ms (min.) 0.5mA

Andover Continuum I/O System Reference

61