The text of a manual · part 11 of 27

Andover Continuum I/O System Reference: Input Modules, pages 66 to 74

Pages 66 to 74 of 222, from Andover Continuum I/O System Reference

The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Andover Controls AC-1, Andover Controls DO-4, Andover Controls UI-8 and Schneider UI-8

Page 66

DI-8

I/O Connections The actual input connections are located on a thirteen-position removable screw terminal connector located at the bottom of the module. The inputs are labeled IN1, IN2, IN3, and so forth. Each pair of inputs is followed by its return connection labeled RET. The connector allows for an Earth ground connection, eight inputs and four signal returns. The diagram screen printed on the module indicates where each input number is located on the terminal block. These connections are also listed below.

Connection

Description

1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12.

Earth Ground IN 1 IN 2 RETURN IN 3 IN 4 RETURN IN 5 IN 6 RETURN IN 7 IN 8 RETURN

62

Schneider Electric

Page 67

DI-8 High Speed Counter Selection Switches The DI-8 input module allows input channels 1 and 2 to be configured with the capability of counting input pulses or contact closures at a rate of up to 10 kHz. A selection switch is included for each of these two input channels. This switch allows you to select whether or not you want the high speed input connected. A small 2-position switch module is accessible from the front of the module when the door is opened.

1 2

O N

Slide marker moves left and right

These switch modules are commonly called “DIP Switches” and require a small object such as the tip of a pen or a small screwdriver to operate them. Each switch position acts as a “slide switch”. Pressing the raised slide marker to the left disables high speed counting. To enable high speed counting, move the slide marker over to the right side.

Andover Continuum I/O System Reference

63

Page 68

DI-8 Input Circuitry The following is a simplified schematic of the DI-8 Digital Input module:

5V

10K

IN x

5V

R II C

RET

Channels 1 and 2 can be configured to allow high speed counting. The switches on the front of the module substitute different value components for the low pass filter formed by the combination of R and C. These values support higher frequency inputs.

64

Schneider Electric

Page 69

DI-8

Sensing Digital Inputs or Contact Closures Digital input points are designed to provide an ON or OFF reading of a signal (wired between the input and return).

Digital logic Signal

IN x

IN x Contact Closure

RET

RET

A digital input is considered “ON” whenever the input senses a digital ‘low’ or a contact closure. Similarly, an OFF condition is sensed with a logic ‘high’ or an open contact. Note: When configuring a Digital point, there is a ‘Polarity’ attribute. If this attribute is enabled, readings are reversed.

When configuring this type of input, select: ElecType:

Digital

Andover Continuum I/O System Reference

65

Page 70

DI-8

Counting Pulsing Signals or Contact Closures Counter inputs are designed to allow the monitoring of digital pulse trains or contact closures across an input just like digital inputs, but they accumulate a total of those closures and act like a counter. When using an input as a counter, you must take into account the frequency of the input signal being counted. Inputs 3–8 do not allow for very high speed contact counting. These channels allow counting up to a maximum of 10 Hz or 10 contact closures or digital pulses per second. In high-speed mode, channels 1 and 2 can be configured (via front panel switch) to count to a maximum of 10 kHz or 10,000 contact closures or digital pulses per second. When configuring this type of input, select: ElecType:

66

Schneider Electric

Counter

Page 71

DI-8 Status/Control Panel Status Indicators The DI-8 module includes a complete indicator status panel on the front of the module.

This panel includes indicators reporting on the status of the following: POWER

This green indicator illuminates when DC power is applied through the I/O Bus.

COMM

This yellow indicator illuminates when data is transmitted from the module to the NetController. In normal operation, data is only transmitted when an input value changes. This indicator will also flash periodically as the NetController checks the I/O bus.

STATUS

This red indicator is normally off. If it is always on or flashing at a fast rate there is a problem with the module. This indicator can be manually illuminated from the CyberStation workstation or Command Terminal and used as a troubleshooting aid when locating a particular module.

INPUT

These red indicators (one for each channel) illuminate when an ‘ON’ condition is sensed.

Andover Continuum I/O System Reference

67

Page 72

DI-8 This panel also includes two operator switches that perform the following: COMMISSION

After physical installation and during configuration through the CyberStation workstation or Command Terminal, pressing this button registers the module’s address with the system. For more information, refer to the section on Module Configuration found earlier in this manual.

RESET

If the module becomes inoperable, pressing this button resets the module. It does not erase its memory.

68

Schneider Electric

Page 73

MI-6 MI-6 MilliAmp Input Module The MI-6, Andover Continuum’s milliamp input module, allows for a direct connection of a 2-wire, loop powered, 0–20mA or 4–20mA sensor to any of the module’s six inputs. The need for an external resistor and an external power supply are eliminated. The MI-6 module is a perfect match for temperature transmitters, humidity and pressure transducers, gas monitors, and other industry-standard sensors with either a 0–20mA or 4–20mA output. The six inputs on the MI-6 module have a 0–20mA range and 10 bit A/D conversion.

FEATURES •

6 Current Measuring Inputs

•

0–20mA Range

•

10 Bit A/D Converter

Andover Continuum I/O System Reference

69

Page 74

MI-6 SPECIFICATIONS ELECTRICAL Power Supply Range:

70

Input Voltage Range: 20-26V. 24V for UL864 installations.

Power Consumption:

3.8 Watts (158 mA) @ 24VDC (max.); normally provided by Andover Continuum power supply module (including up to 20mA sensor power for each input).

Overload Protection:

0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection.

INPUTS Number of Inputs:

6 Milliamp inputs

Input Range:

0–20 mA

Resolution:

20 µA

Accuracy:

±80 µA max.

Drift:

±50 ppm/DegC (max.)

Input Resistance:

249 Ω, 0.1%

Maximum Input Current:

±30 mA

Voltage Supply to Sensors:

19.0–26.0V (varies with +24VDC input voltage)

Input Protection:

Each input and the Sensor voltage output includes a transient voltage suppressor (TVS) and a resettable fuse.

Input Connections:

Two-piece, 13-position removable terminal block

Schneider Electric