Page 75
MI-6
I/O Connections The actual input connections are located on a thirteen-position removable screw terminal connector located at the bottom of the module. The inputs are labeled IN1, IN2, IN3, and so forth. Each input occupies a pair of terminals, resulting in a sequence of IN1+, IN1-, IN2+, IN2-, and so on. For any given input, observe the polarity for that input, + connects to the Supply terminal of the input. The minus terminal connects to the Signal input. The diagram below indicates where each input number is located in the terminal block.
Connection
Description
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12.
Earth Ground IN 1 + IN 1 IN 2 + IN 2 IN 3 + IN 3 IN 4 + IN 4 IN 5 + IN 5 IN 6 + IN 6 -
Andover Continuum I/O System Reference
71
Page 76
MI-6
Input Circuitry The following is a simplified schematic of the MI-6 Milliamp Input module:
24V
300mA Resettable Fuse
5V 100mA Resettable Fuse
R To Analog/Digital Converter
249Ω
C
All six input pairs include their own automatically resettable fuses. These devices are designed to open when sensing an over-current. They reset when the current supplied is within range. Note: In some extreme instances, the fuses may require that you remove power to the module temporarily to reset their state.
72
Schneider Electric
Page 77
MI-6
Sensing Current The current supplying sensor is connected as indicated in the following illustration:
Supply
24V Loop-Powered Sensor
INx
Signal
When configuring this type of input, select: ElecType:
ACC_InputCurrent
Andover Continuum I/O System Reference
73
Page 78
MI-6 Status/Control Panel Status Indicators The MI-6 module includes a complete indicator status panel on the front of the module.
This panel includes indicators reporting on the status of the following: POWER
This green indicator illuminates when DC power is applied through the I/O Bus.
COMM
This yellow indicator illuminates when data is transmitted from the module to the NetController. In normal operation, data is only transmitted when an input value changes. This indicator will also flash periodically as the NetController checks the I/O bus.
STATUS
This red indicator is normally off. If it is always on or flashing at a fast rate, there is a problem with the module. This indicator can be manually illuminated from CyberStation or Command Terminal and used as a troubleshooting aid when locating a particular module.
EXTERNAL POWER
74
This green indicator illuminates when 24V DC power is available to external sensors.
Schneider Electric
Page 79
MI-6 This panel also includes two operator switches that perform the following: COMMISSION
After physical installation and during configuration through the CyberStation workstation or Command Terminal, pressing this button registers the module’s address with the system. For more information, refer to the section on Module Configuration found earlier in this manual.
RESET
If the module becomes inoperable, pressing this button resets the module. It does not erase its memory.
Andover Continuum I/O System Reference
75