Page 80
DM-20 DM-20 Digital Input/Output Module The DM-20, Andover Continuum’s Digital Input and Output module, provides high density, versatile I/O for many control applications. When coupled with the optional DIO20 Expansion Board, the DM-20 allows you to mix and match up to 20 digital inputs and outputs. Using standard off-the-shelf digital I/O blocks, the DIO-20 allows the system to meet a wide range of applications, including ON-OFF or pulse-width modulation (PWM) control of equipment and for switching inductive loads up to 240 VAC. The DM-20 provides 24 VDC power to the DIO-20 via a separate cable assembly. When used without the DIO-20 Expansion Board, the DM-20 can control any combination of inputs and outputs, up to a total of 20 per module.
FEATURES
76
Schneider Electric
•
20 General Purpose Digital Inputs/Outputs
•
Each point can be configured as an input or an output
•
Direct connection to DIO-20 Expansion Module
Page 81
DM-20 SPECIFICATIONS ELECTRICAL Power Supply Range: Power Consumption:
Input Voltage Range: 20-26V. 24V for UL864 and UL294 installations. 0.5 Watts (20 mA) @ 24VDC (max.); provided by Andover Continuum power supply module. Up to 9 Watts (375 mA) @ 24VDC when the DIO-20 is powered from the DM-20 .
External Power Connector:
Three-position removable connector
Overload Protection:
0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection for both DM-20 power and DIO-20 power.
LED Power Supply:
Customer-provided external 5V power supply when using the DM-20 to drive LEDs. For smoke control applications, Schneider Electric power supply: PS 120/240 AC-25 (UL 864 listed) must be used.
INPUTS/OUTPUTS
20 total points; user-selectable channel-by-channel as inputs or outputs
Inputs: Input Type:
Pulse Width: Outputs: Output Type:
w/DIO-20 w/o DIO-20
24 VDC logic voltage (DIO-20). Input rating depends on input module(s) selected.
0–5 VDC
125 ms (min.)
125 ms (min.)
w/DIO-20 5 VDC logic voltage. Range depends on output module selected.
w/o DIO-20 Open- collector Output transistor with series 330 Ω 1/8 W resistor; 5 VDC (max.), 15 mA
Output Resolution:
0.1 sec. For Pulse Width Modulation (PWM) control
Output Protection:
Transient voltage suppressor (TVS) and current limiting resistor on each channel.
I/O Connections:
25-position DB25 Female and one removable threeterminal block.
Andover Continuum I/O System Reference
77
Page 82
DM-20 I/O Connections The actual I/O connections are located on a 25-position DB25-type female connector located at the bottom of the module. A separate three-conductor removable screw connector provides 24 VDC power to external devices. The inputs are labeled I/O1, I/O2, I/O3, and so forth. Each input/output occupies a single position of the connector. Five signal ground pins are supplied as well. The diagram below indicates where each input number is located on the module. 3-Pin Connector Connection Description
1 2
Earth Ground + 24VDC @ .36 Amps 24 V Return
25-Pin D Connector Connection Description 1. I/O 1 2. I/O 2 3. I/O 3 4. I/O 4 5. I/O 5 6. I/O 6 7. I/O 7 8. I/O 8 9. I/O 9 10. I/O 10 11. I/O 11 12. I/O 12 13. I/O 13 14. I/O 14 15. I/O 15 16. I/O 16 17. I/O 17 18. I/O 18 19. I/O 19 20. I/O 20 21. Ground 22. Ground 23. Ground 24. Ground 25. Ground 78
Schneider Electric
Page 83
DM-20
Input/Output Circuitry The following is a simplified schematic of each DM-20 Input/Output channel: +5V
I/O x
330 II
I/O Channel (same for all 20 channels) All 20 I/O channels resemble the circuit shown above.
24V
500mA Resettable Fuse
The 24VDC power available to external devices includes an automatically resettable fuse. This fuse is designed to open when an external device tries to extract more current than is available. They reset when the current draw is back within range. Note: In some extreme instances, the fuses may require that you remove power to the module temporarily to reset their state.
Andover Continuum I/O System Reference
79
Page 84
DM-20 Using the DM-20 The DM-20 is primarily designed to directly interface with the DIO-20. However, it can also be used as a general purpose digital I/O module containing 20 points. Note: Make sure that external devices are attached to the DM-20 before powering the unit. DIO-20 Interface The DIO-20 Expansion Module provides a connection for up to 20* solid state input or output modules for the I/O channels of the DM-20. It includes individually fused sockets for modules from manufacturers such as Opto 22, Grayhill, Gordos, Crydom and Potter & Brumfield. You can mix input and output modules on the DIO-20 as needed. The connection between the DM-20 and the DIO-20 consists of a 25-pin ribbon cable to supply data between the modules and a two-conductor power cable. Data connection between the two is accomplished via a 25-pin male-male DB25 cable:
DM-20
DM-20 to DIO-20 Data Connection
DIO-20
*The actual number of modules supported depends on type and power used. Refer to the power requirements on page 86. .
80
Schneider Electric
Page 85
DM-20 The Power connection between the DIO-20 and the DM-20 is via a two-conductor cable assembly as shown:
DM-20 D CONNECTOR G G G G G I/O I/O I/O I/O I/O I/O I/O N N N N N 14 15 16 17 18 19 20 D D D D D
24VDC @ .36 Amps TO DI0-20
+ 1
2
I/O I/O I/O I/O I/O I/O I/O I/O I/O I/O I/O I/O I/O 1 2 3 4 5 6 7 8 9 10 11 12 13
DM-20 to DIO-20 DC Power Connection
+24 V Return +24 VDC
DIO-20
Using the DM-20/DIO-20 Combination The DIO-20 provides the DM-20 with a real-world interface to its I/O channels. Solid-state input modules (on the DIO-20) provide interface circuitry to a variety of signals. These modules convert their signals to digital levels for input to the DM-20. Similarly, solid-state output modules (on the DIO-20) allow the digital levels of the DM-20 to interface to a variety of signals. In both cases, the I/O points are set up to have an Electrical Type of Digital no matter what type of solid-state module is installed.
Andover Continuum I/O System Reference
81
Page 86
DM-20 General Purpose DM-20 Digital Interface The DM-20 can be used to provide 20* general purpose digital inputs and outputs. It is not necessary to interface the module with an external expansion product to use its capabilities. Each channel can be used to output a digital signal or read a digital signal or contact closure. The DM-20 can be configured as a general purpose digital input. With the addition of an external reference pull-up resistor, it can be used for sensing contact closures or digital logic signals as shown below: 5V
10K
Digital logic Signal
I/O x
I/O x Contact Closure
GROUND
GROUND
As a digital output, the DM-20 has an open collector output with a 330 Ω series resistor. Connect digital devices and LED indicators as shown below: 5V
+5V
10K
Digital logic Input
LED Indicator I/O x
I/O x
GROUND
GROUND
When configuring any of these inputs/outputs, select: ElecType:
Digital
* The actual number of modules supported depends on type and power used. Refer to the power requirements on the following page.
82
Schneider Electric
Page 87
DM-20 Loss of Power / Communication Output Restore Time When power is lost to the module, all outputs turn off. This also occurs when the module has lost communication with the NetController for more than 255 seconds. When power is finally restored, the module can immediately restore the last state of the outputs or be delayed so that the NetController can update the state before energizing them. This option is called Output Restore Time and its value can be set through a Numeric. The Output Restore Time numeric is configured as follows: Function Output Restore Time
Channel 21
Object Type Numeric
Direction
Values
IOOutput
Number of seconds to wait before restoring output state: 0–255
If the Output Restore Time numeric is not defined, the output will restore immediately upon return of I/O power. NOTE: Pulsed values are "saved" and will occur in their entirety after delay. DM-20/DIO-20 Module Power Requirements The DM-20 includes the ability to directly power a DIO-20 module. DIO-20 modules support a combination of up to 20 input and output modules. The following details the power requirements of each combination. This information is presented to determine the power supply requirements for the board. • • •
Input modules consume a maximum current in their ON state of 23mA. The DM20 can only supply enough power for 14 input modules. Output modules consume a maximum current in their ON state of 16mA. The DIO-20 itself without any modules installed draws 20mA.
The DM-20 provides a total of 360mA for the DIO-20. Using the numbers supplied above you can calculate how many modules are allowed. Examples: Up to 14 input modules: (14 x 23mA) + 20mA = 342mA A total of 14 input modules exhausts (with only 18mA remaining) the current capability of the DM-20. Up to 20 output modules:(20 x 16mA) + 20mA = 340mA A total of 20 output modules consumes only 340mA from the DM-20.
Andover Continuum I/O System Reference
83
Page 88
DM-20
Status/Control Panel Status Indicators The DM-20 module includes a complete indicator status panel on the front of the module.
This panel includes indicators reporting on the status of the following: POWER
This green indicator illuminates when DC power is applied through the I/O Bus.
COMM
This yellow indicator illuminates when data is transmitted from the module to the NetController. In normal operation, data is only transmitted when an input value changes. This indicator will also flash periodically as the NetController checks the I/O bus.
STATUS
This red indicator is normally off. If it is always on or flashing at a fast rate, there is a problem with the module. This indicator can be manually illuminated from CyberStation or Command Terminal and used as a troubleshooting aid when locating a particular module.
84
Schneider Electric
Page 89
DM-20 This panel also includes two operator switches that perform the following: COMMISSION
After physical installation and during configuration through the CyberStation workstation or Command Terminal, pressing this button registers the module’s address with the system. For more information, refer to the section on Module Configuration found earlier in this manual.
RESET
If the module becomes inoperable, pressing this button resets the module. It does not erase its memory.
Andover Continuum I/O System Reference
85