Page 90

AO-4-8

AO-4-8, AO-4-8-O Analog Output Modules The AO-4-8, Andover Continuum’s analog output module, has four analog outputs with eight-bit resolution, which can be configured as either voltage (0-10 VDC) or current (020 mA) outputs. The AO-4-8 is the perfect choice for valves, dampers, variable speed drives, and similar equipment that demand high control accuracy. An AO-4-8-O model with full override capabilities is also available. Each output contains a three-position manual override switch and override potentiometer. In addition, the AO4-8-O provides software override feedback to the Plain English programming language for each output.

FEATURES •

4 Analog Outputs

•

8 bit Resolution

•

0–10V Voltage Outputs

•

0–20mA Current Outputs

AO-4-8-O Only:

86

Schneider Electric

•

Override Toggle Switches and Potentiometers

•

Override Detection

Page 91

AO-4-8 SPECIFICATIONS ELECTRICAL Power Supply Range:

Input Voltage Range: 20-26V. 24V for UL864 installations.

Power Consumption:

3.8 Watts (158 mA) @ 24VDC (max.); normally provided by Andover Continuum power supply module.

Overload Protection:

0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection.

OUTPUTS AO-4-8:

4 analog outputs; 8 bit resolution

AO-4-8-O:

4 analog outputs with overrides; 8 bit resolution

Output Protection:

1/8 pico fuse per channel (40V TVS on each output⎯AO-48-O model only)

Output Connections:

Two-piece, 13-position removable terminal block

Output Types: Voltage: Range:

Voltage or current 0–10 V

Resolution:

0.05 V

Accuracy:

±0.10V (1%FSR)

Output Current:

+5 mA (sourcing) -1 mA (sinking)

Load Resistance:

2 KΩ min.(sourcing)

Current: Range:

0–20 mA

Resolution:

0.1 mA

Accuracy:

±0.2 mA

Load Resistance:

650Ω (max.)

Output Overrides: (AO-4-8-O only)

3-position manual override switch and override potentiometer on each output, with software feedback. LED override status indicator.

Output Connections:

Two-piece, 13-position removable terminal block

Andover Continuum I/O System Reference

87

Page 92

AO-4-8

I/O Connections The actual output connections are located on a thirteen-position removable screw terminal connector located at the bottom of the module. The outputs are labeled OUT1 I, OUT1 V, OUT1 GND, and so forth. Each output presents two ways of connecting, resulting in a current output between OUT1 I and OUT1 GND, and a voltage output between OUT1 V and OUT1 GND. The connector allows for an Earth ground connection, eight inputs and four signal returns. The diagram screen printed on the module indicates where each input number is located on the terminal block. These connections are also listed below.

Connection

Description

1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12.

Earth Ground OUT1 I OUT1 V OUT1 GND OUT2 I OUT2 V OUT2 GND OUT3 I OUT3 V OUT3 GND OUT4 I OUT4 V OUT4 GND

88

Schneider Electric

Page 93

AO-4-8

Output Circuitry The following is a simplified schematic of each AO-4-8 Output channel: 24V

OUTx V

125mA Pico Fuse

Digital to Analog Converter

24V

OUTx I

125mA Pico Fuse

Voltage to Current Converter

GND

All 4 channels resemble the circuit shown above.

Andover Continuum I/O System Reference

89

Page 94

AO-4-8 Override Controls The AO-4-8-O model includes an output override switch and manual variable control for each output.

MANUAL OFF AUTO

ADJUST

The following describes the actions associated with each position of the override controls:

90

MANUAL

The analog signal generated by the module is controlled manually by adjusting the ADJUST potentiometer below to the manual override switch. Programs have no effect on the output when the switch is in this position.

OFF

The output is set to zero volts, zero mA. Programs and the setting on the ADJUST potentiometer have no effect on the output Device when the switch is in this position.

AUTO

The analog signal is generated as a direct result of program control. The setting on the ADJUST potentiometer has no effect on the output Device when the switch is in this position.

ADJUST

This is a variable control that allows you to manually adjust the output of the analog signal when the override switch is in the MANUAL position. Insert the tip of a small screwdriver to use this control. Turning to the right (clockwise) increases the output. Turning left (counterclockwise) decreases the output.

Schneider Electric

Page 95

AO-4-8 Voltage Output The voltage output is a ground-referenced signal with a range of 0–10 VDC. The maximum output current is 5 mA (2,000 s minimum resistance). Ensure that the device being connected is either floating or at the same ground potential as the controller. Connect the device across the following terminals:

OUTx I

OUTx V Device Load Resistance

≥ 2KΩ GND

NOTE: The load resistance (of the external device) must be greater than or equal to 2KΩ.

When configuring this type of output, select: ElecType:

Voltage

Andover Continuum I/O System Reference

91

Page 96

AO-4-8

Current Output The current output is a current-sourcing, ground referenced circuit. This output can source 0 - 20 mA with a maximum load impedance of 650 s. Connect the device across the following terminals:

OUTx I

Device Load Resistance ≤ 650Ω

OUTx V

GND

NOTE: The load resistance (of the external device) must be less than or equal to 650 Ω.

When configuring this type of output, select: ElecType:

92

Schneider Electric

Current

Page 97

AO-4-8

Status/Control Panel Status Indicators The AO-4-8 module includes a complete indicator status panel on the front of the module.

This panel includes indicators reporting on the status of the following: POWER

This green indicator illuminates when DC power is applied through the I/O Bus.

COMM

This yellow indicator illuminates when data is transmitted from the module to the NetController. In normal operation, data is only transmitted when an input value changes. This indicator will also flash periodically as the NetController checks the I/O bus.

STATUS

This red indicator is normally off. If it is always on or flashing at a fast rate, there is a problem with the module. This indicator can be manually illuminated from the CyberStation workstation or Command Terminal and used as a troubleshooting aid when locating a particular module.

OVERRIDE

This red indicator illuminates whenever any of the override switches is in a position other than AUTO.

Andover Continuum I/O System Reference

93

Page 98

AO-4-8 This panel also includes two operator switches that perform the following: COMMISSION

After physical installation and during configuration through the CyberStation workstation or Command Terminal, pressing this button registers the module’s address with the system. For more information, refer to the section on Module Configuration found earlier in this manual.

RESET

If the module becomes inoperable, pressing this button resets the module. It does not erase its memory.

94

Schneider Electric

Page 99

DO-4-R DO-4-R, DO-4-R-O Digital Output Module The DO-4-R, Andover Continuum’s digital output module, has four Form C relay outputs, rated at 5 Amps @240 VAC. These versatile outputs make the DO-4-R an excellent choice for switching motor starters and other inductive loads up to 240 VAC, with either two position (on/off) or Pulse-Width Modulation (PWM) control. The PWM feature permits the modulation of valves and dampers to 0.1 second resolution. Two adjacent Form C relay outputs can be combined in software to provide a Tri-state output, for bi-directional control of valves and dampers and other end devices. Metal oxide varistors and 5000V isolation on each output ensure reliable noise-free operation. A DO-4-R-O model with full override capabilities is also available. Each output has a local hand-off-auto switch, which enables service personnel to override the output. The switch also provides override feedback of output values for use in troubleshooting or test conditions. A local indicator light for each output displays relay status. Another LED provides override status.

FEATURES •

4 Form C Relay Outputs

•

240 VAC @ 5A Contact Rating

•

Independently Mounted

•

Output Status LEDs

•

10–28 V Power Supply Range

DO-4-R-O Only: •

Override Toggle Switches

•

Override Detection

Andover Continuum I/O System Reference

95