Andover Continuum I/O System Reference: Output Modules, pages 100 to 109

Pages 100 to 109 of 222, from Andover Continuum I/O System Reference

The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Andover Controls AC-1, Andover Controls DO-4, Andover Controls UI-8 and Schneider UI-8

Page 100

DO-4-R SPECIFICATIONS ELECTRICAL Power Supply Range:

(DO-4-R, DO-4-R-O): Input Voltage Range: 10-28V. 24V for UL864 and UL294 installations.

Power Consumption:

2.8 Watts (116 mA) @ 24 VDC (max.); normally provided by Andover Continuum power supply module.

Overload Protection:

0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection.

OUTPUTS DO-4-R:

4 Form C relay outputs

DO-4-R-O:

4 Form C relay outputs with overrides

Output Rating:

240 VAC @ 5 Amps; 30 VDC @ 5 Amps

Output Resolution:

0.1 sec. For Pulse Width Modulation (PWM) control

Output Protection:

270 V varistors across contacts. 5000 VRMS isolation @ 60 Hz between relay contacts and relay coil.

DO-4-R-O Output Overrides:

3-position manual override switch on each output, with software feedback. LED override status indicator

DO-4-R-O Override Feedback:

Override detection and feedback provided for each output.

Output Connections:

Two-piece, 13-position removable terminal block

EUROPEAN STANDARDS European Multi-Purpose Control–Electronic Type 1B–Micro Disconnect

96

Schneider Electric

Page 101

DO-4-R

I/O Connections The actual output connections are located on a thirteen-position removable screw terminal connector located at the bottom of the module. The outputs are labeled OUT 1 NC, OUT 1 NO, OUT 1 COM, and so forth. Each output presents a single pole double throw set of contacts. OUT 1 NC is the normally closed side of the contact. OUT 1 NO is the normally open contact. OUT 1 COM is the common connection that represents the armature of the relay switch. The diagram below indicates where each output number is located in the terminal block.

Connection

Description

1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12.

Earth Ground OUT 1 NC OUT 1 NO OUT 1 COM OUT 2 NC OUT 2 NO OUT 2 COM OUT 3 NC OUT 3 NO OUT 3 COM OUT 4 NC OUT 4 NO OUT 4 COM

Andover Continuum I/O System Reference

97

Page 102

DO-4-R

Output Circuitry The following is a simplified schematic of each Output channel: OUT x NC

OUT x NO

OUT x COM

All 4 channels resemble the circuit shown above. These output contacts operate as a standard relay. When the output is set to an “ON” state, the normally open contacts (OUTx NO) close and the normally closed contacts (OUTx NC) open. To use the Form C output in your system, configure an output point with an Electrical Type of Digital.

Supervising the Outputs for UL1076 To supervise the operation of the DO-4 outputs, install a remote relay in parallel with the device being switched. The contacts of this relay are connected back to a UI-8 supervised input. A 10K EOL resistor is connected across the relay contacts. A Plain English program containing the following line would be executed: If (DO4_Output = On AND UI8_Input = Off) OR (UI8_Input = TROUBLE) THEN DO4_Alarm = ON ELSE DO4_Alarm = OFF

If an open, short or grounded condition exists either on the cable out to the switched device or the cable running back to the UI-8, an audio and visual alarm would be triggered at the central receiving station when the output was turned on. For 24 VDC Loads use relay: Potter & Brumfield (TYCO) KUP5D15 * For 24 VAC loads use relay: Potter & Brumfield (TYCO) KUP5A15 * *These relays are UL recognized components

98

Schneider Electric

Page 103

DO-4-R Override Controls The DO-4-R-O model includes an output override switch for each output. ON OFF AUTO

The output of the module can be directed from program control to manual control. The output can be disabled completely as well. The following describes the actions associated with each position of the override controls: ON

The output relay is energized to an “ON” state manually by setting the switch to ON. Programs have no effect on the output when the switch is in this position.

OFF

The output relay is de-energized to an ‘OFF’ state manually by setting the switch to OFF. Programs have no effect on the output when the switch is in this position.

AUTO

The action of the output relay is determined as a direct result of program control.

Loss of Power / Communication: Output Restore Time When power is lost to the module or it loses contact with the NetController for more than 255 seconds, all outputs turn off. When power is finally restored, the module can immediately restore the last state of the outputs or be delayed so that the NetController can update the state before energizing them. This option is called Output Restore Time and its value can be set through a Numeric. The Output Restore Time numeric is configured as follows: Function

Channel

Object Type

Direction

Values

Output Restore Time

5

Numeric

IOOutput

Number of seconds to wait before restoring output state: 0–255

If the Output Restore Time numeric is not defined, the output will restore immediately upon return of I/O power.

Andover Continuum I/O System Reference

99

Page 104

DO-4-R Tri-State Output Although the module contains four separate form C relays, adjacent pairs of these can be combined at any one time to form a standard Tri-state output: OUT1 and OUT2 OUT3 and OUT4 Configure the output point of the first point (OUT1 or OUT3) with an Electrical Type of Tri-state.

Caution: Do not attempt to use OUT2 and OUT3 as a tri-state pair. An error message may result. Configure tri-state outputs as OUT1-OUT2 or OUT3-OUT4.

Connect the two outputs together as follows (example shows OUT1 and OUT2):

OUT 1 NC

+ ON

Common

OFF

ON

OUT 1 NO

OUT 1 COM

OUT 2 NC

OUT 2 NO

OUT 2 COM

100

Schneider Electric

Page 105

DO-4-R

Status/Control Panel Status Indicators All DO-4 models include a complete indicator status panel on the front of the module.

This panel includes indicators reporting on the status of the following: POWER

This green indicator illuminates when DC power is applied through the I/O Bus.

COMM

This yellow indicator illuminates when data is transmitted from the module to the NetController. In normal operation, data is only transmitted when an input value changes. This indicator will also flash periodically as the NetController checks the I/O bus.

OVERRIDE

This red indicator illuminates whenever any of the override switches is in a position other than AUTO. (operates on -O models only)

STATUS

This red indicator is normally off. If it is always on or flashing at a fast rate, there is a problem with the module. This indicator can be manually illuminated from CyberStation or Command Terminal and used as a troubleshooting aid when locating a particular module.

OUTPUT

These red indicators (one for each channel) illuminate when an output relay is energized.

Andover Continuum I/O System Reference

101

Page 106

DO-4-R This panel also includes two operator switches that perform the following: COMMISSION

After physical installation and during configuration through CyberStation or Command Terminal, pressing this button registers the module’s address with the system. For more information, refer to the section on Module Configuration found earlier in this manual.

RESET

If the module becomes inoperable, pressing this button resets the module. It does not erase its memory.

102

Schneider Electric

Page 107

DO-6-TR DO-6-TR Triac Output Module The DO-6-TR, Andover Continuum’s triac output module, has six Form A triac-based outputs, rated at 0.5 Amps @ 24 VAC, for cost-effective on/off or pulse-width modulation (PWM) control of lighting, heat, and fan units. The PWM feature permits the modulation of valves and dampers to 0.1 second resolution. Adjacent outputs can also be configured in pairs to provide up to three Form K, Tri-state outputs for bi-directional control of dampers and valves. Metal Oxide Varistors (MOVs), Snubbers and Optocouplers on the DO-6-TR provide 2500 V isolation on each output, ensure noise-free operation, and, in most cases, eliminate the need to install MOVs in the field.

FEATURES •

Six (6) Triac-based outputs

•

24 Vrms @ 0.5 A Contact Rating

•

Output Status LEDs

Andover Continuum I/O System Reference

103

Page 108

DO-6-TR SPECIFICATIONS ELECTRICAL Power Supply Range:

Input Voltage Range: 20-26V. 24V for UL864 installations.

Power Consumption:

1.1 Watts (45 mA) @ 24 VDC (max.); normally provided by Andover Continuum power supply module.

Overload Protection:

0.5 A resettable fuse with Transient Voltage Suppressor (TVS) and reverse polarity protection.

OUTPUTS Output Type:

6 Form A optically isolated triac outputs (can be configured up to 3 Form K Tri-State outputs)

Output Rating:

0.5A @ 24 VAC, (Cannot switch DC loads)

Output Accuracy:

0.1 sec. for Pulse Width Modulation (PWM) control

Output Protection:

2500 V optical isolation

MOV and Snubber on each output Output Connections:

104

Schneider Electric

Two-piece, 13-position removable terminal block

Page 109

DO-6-TR

I/O Connections The actual output connections are located on a thirteen-position removable screw terminal connector located at the bottom of the module. The outputs are grouped in pairs of two connector terminals per channel. Each output presents a normally open single pole set of contacts. The diagram below indicates where each output number is located in the terminal block.

Connection

Description

1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12.

Earth Ground OUT 1 OUT 1 OUT 2 OUT 2 OUT 3 OUT 3 OUT 4 OUT 4 OUT 5 OUT 5 OUT 6 OUT 6

Andover Continuum I/O System Reference

105