Page 110
DO-6-TR
Output Circuitry The following is a simplified schematic of each DO-6-TR Output channel:
OUT x
OUT x
All 6 channels resemble the circuit shown above. These output contacts operate as a solid state relay. When the output is set to an “ON” state, the contacts close allowing current to flow between the output terminals. To use the Form A output in your system, configure an output point with an Electrical Type of Digital. Loss of Power / Communication: Output Restore Time When power is lost to the module or it loses contact with the NetController for more than 255 seconds, all outputs turn off. When power is finally restored, the module can immediately restore the last state of the outputs or be delayed so the NetController can update the state before energizing them. This option is called Output Restore Time and its value can be set through a Numeric. The Output Restore Time numeric is configured as follows: Function
Channel
Object Type
Direction
Values
Output Restore Time
7
Numeric
IOOutput
Number of seconds to wait before restoring output state: 0–255
If the Output Restore Time numeric is not defined, the output will restore immediately upon return of I/O power. 106
Schneider Electric
Page 111
DO-6-TR
Switching Loads with Triacs Although the Triac-based outputs of this module appear as relay contacts in the schematics provided, they are actually solid-state switches that have limitations on the loads they can switch.
AC vs. DC The first limitation is that they cannot be used with DC loads. A Triac switches AC only.
Minimum Load Current The second limitation involves the minimum load current. In order for the Triac to switch, it must detect at least 30 mA of current from the load. If your load is less than 30 mA, you can induce the required load by connecting a resistor across the load (not directly at the Triac!). Check the current draw specification on your field device, and if it does not meet this minimum, add a resistor in parallel with the device being driven sized to achieve the minimum loading. Use the following formulas to determine resistance and wattage:
Resistance (Ωs) =Voltage Current
Power (Watts) = (Voltage) 2 Resistance
Andover Continuum I/O System Reference
107
Page 112
DO-6-TR
Tri-State Output Although the module contains six separate form A relays, adjacent pairs of these can be combined at any one time to form a standard Tri-state output: OUT1 and OUT2 OUT3 and OUT4 OUT5 and OUT6 Configure the output point of the first point (OUT1, OUT3 or OUT5) with an Electrical Type of Tri-state. Caution: Do not attempt to use OUT2 and OUT3 or OUT4 and OUT5 as a tri-state pair. An error message may result. Configure tri-state outputs as OUT1-OUT2, OUT3-OUT4 or OUT5-OUT6. Connect two outputs together to form a tristate output as follows (pair OUT1 and OUT2 is shown):
+ ON
OUT 1
OUT 1
Common OUT 2
ON
108
Schneider Electric
OUT 2
Page 113
DO-6-TR
Status/Control Panel Status Indicators The DO-6-TR module includes a complete indicator status panel on the front of the module.
This panel includes indicators reporting on the status of the following: POWER
This green indicator illuminates when DC power is applied through the I/O Bus.
COMM
This yellow indicator illuminates when data is transmitted from the module to the NetController. In normal operation, data is only transmitted when an input value changes. This indicator will also flash periodically as the NetController checks the I/O bus.
STATUS
This red indicator is normally off. If it is always on or flashing at a fast rate, there is a problem with the module. This indicator can be manually illuminated from the CyberStation workstation or Command Terminal and used as a troubleshooting aid when locating a particular module.
OUTPUT
These red indicators (one for each channel) illuminate when a triac output is ON.
Andover Continuum I/O System Reference
109
Page 114
DO-6-TR This panel also includes two operator switches that perform the following: COMMISSION
After physical installation and during configuration through the CyberStation workstation or Command Terminal, pressing this button registers the module’s address with the system. For more information, refer to the section on Module Configuration found earlier in this manual.
RESET
Should the module become inoperable, pressing this button resets the module. It does not erase its memory.
110
Schneider Electric
Page 115
LO-2 LO-2, LO-2-O Lighting Control Module The LO-2, Andover Continuum’s lighting control module, can control 2 high voltage lighting circuits, using externally mounted GE RR7 or RR9 lighting relays, rated for 277 VAC and 20 Amps (347 VAC option for Canada). The RR9 relay provides status feedback of the relay position, using a built-in pilot contact. The RR7 relay provides control of the circuit with no feedback. An on-board status LED for each output is provided when RR9 relays are used, as well as pilot light voltage for wall switches that have status indication. External 28 VAC is required to power the GE relays. This same transformer can power the LO-2 when the module is located remotely. An LO-2-O model, with on-board momentary override toggle switches, is also available.
FEATURES •
2 Lighting Outputs
•
Uses standard RR-7 or RR-9 relays
•
External 28 VAC required to power GE relays
•
On-board logic powered by Andover Continuum Power Supply or External 28V transformer. Therefore, when the LO-2 is remotely located, it can be powered by 28 VAC alone.
•
Output Status LEDs
LO-2-O Only: •
Override Toggle Switches
Andover Continuum I/O System Reference
111
Page 116
LO-2
SPECIFICATIONS ELECTRICAL Power Supply Range:
Input Voltage Range: 20-26V.
Power Consumption:
0.4 Watts (16 mA) @ 24 VDC (max.); provided by Andover Continuum power supply module. Consumes no DC power when external AC power is present.
External AC Power:
28 VAC powers both the module and lighting relays; can also power the LO-2 module when mounted remotely.
External Transformer Size:
40 VA transformer provides power for up to 5 LO-2 modules (10 GE relays and associated devices).
Overload Protection:
DC: 0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection. AC: 0.5 A resettable fuse with MOV.
INPUTS/OUTPUTS Inputs: Input Protection:
2 Class II Low Voltage override inputs, providing direct control of lighting relays Transient voltage suppressors (TVS) with reverse polarity protection
Outputs: Output Type:
2 pulsed lighting control outputs compatible with externally mounted GE RR7 or RR9 relays
Output Rating: (Relay)
Lamp Load – 20 Amp Tungsten Filament @125 VAC Resistive Load – 20 Amp Ballast @ 277 VAC (20 amp @347 VAC, Canada) Motor Load – 0.5 Hp @ 110–125 VAC 0.5 HP @ 220–277 VAC (0.5 Hp @ 347 VAC, Canada) Pilot Contact Rating (RR9 only): 1 Amp, 24 VAC, isolated
Output Feedback:
RR9 relays have LED status indication and software feedback for relay status
Output Protection:
Transient voltage suppressors (TVS) on outputs. GE relays provide isolation.
Overrides:
Momentary override toggle switches (LO-2-O model only)
Power/Output Connections:
Two-piece, 12-position removable terminal block
Lighting Relay Connections: 5-position male connector accepts standard GE female plug-in connector.
112
Schneider Electric
Page 117
LO-2 I/O Connections The actual I/O connections are located on a combination of a twelve-position removable screw terminal connector located at the center of the module and two five-pin Molex relay connectors at the bottom. The diagram below indicates where each output number is located in the terminal block.
Connection
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11.
Description Earth Ground GND for 24–30V Ext. Power 24–30V External VAC OUT 1 RED OUT 1 BLK OUT 1 YEL OUT 1 WHT OUT 2 RED OUT 2 BLK OUT 2 YEL OUT 2 WHT 24 VAC RECT
Andover Continuum I/O System Reference
113
Page 118
LO-2 Electrical Description The outputs of the LO-2 module are digital in nature (ON or OFF) yet are designed specifically to control lighting. The two outputs are electrically connected (via cable) to an external bracket where two GE-style lighting relays (RR-7 or RR-9) have been mounted. Both outputs can be controlled via program or be activated manually through override switches (LO-2-O only) on the front panel. An external momentary switch (a push button, motion detector or other occupancy sensor) can be wired to control each of the relays as well. The GE relays mechanically latch in the ON position when energized. The relay remains ON until set to OFF from the program or any external override controls. RR-9 relays also provide operational status information (ON or OFF) that can be read via Plain English commands. The OUTPUT indicators on the front panel illuminate if the RR-9 relay output is ON. Override Controls The LO-2-O model includes a built-in output override switch for each output. ON
OFF
The operation of the relays can be operated from program control or manual control using the front panel mounted override switches or externally wired controls. The following describes the actions associated with each position of the override controls:
114
ON
The output relay is energized to an “ON” state manually by setting the switch to ON. The spring-loaded momentary action of the switch moves the switch back to the center position after pressing.
OFF
The output relay is de-energized to an “OFF”’ state manually by setting the switch to OFF. The spring-loaded momentary action of the switch moves the switch back to the center position after pressing.
Schneider Electric
Page 119
LO-2 External Override Capabilities Two Class II low voltage manual override inputs, one for each relay output, are provided for override capabilities. These inputs directly control the lighting relays, independent of any schedule or program. Wall switches, occupancy sensors, or a combination of both may be wired to these inputs.
Lighting Control The LO-2 can be coupled with Andover Continuum’s programmable input modules to provide flexible lighting control strategies such as: • • • • • • • • •
Outdoor Lighting Control with a Photocell Daylight Control After-Hours Lighting Usage with Card Swipe Readers Adjustable Override Time with Flick Warning Cleaning Crew Override Data Logging and Reporting Run time Analysis, including Accumulated On-Time and Percentage On-Time Tenant Billing Reports Custom Control Strategies
These programs can be easily modified to fit the exact needs of your project.
Andover Continuum I/O System Reference
115