Page 120
LO-2 Electrical Installation External Power The GE relays are powered by an external 28 VAC source. The LO-2 module has been designed to utilize this external power source as its own module supply source as well. It is not necessary to power the module in this way. However, if the LO-2 is located remotely from your main power source, you may want to power the module locally thereby eliminating the two extra wires necessary to bring power to the module from the Andover Continuum power supply. It also lessens the load requirements on that supply. 28 VAC Relay Power Connect the output of a 28 VAC transformer to the module power inputs as shown: 28 VAC Transformer PWR 24-30 VAC GND
This ground connection must be the same point as the ground for the Continuum Power Supply
External Control Power Externally mounted sensors such as proximity sensors require power to operate as well. The LO-2 module provides a connection for these devices to receive half wave rectified 28 V power as indicated below:
28 VDC (half-wave rectified AC) to External Sensors
116
Schneider Electric
28 VAC RECT
Page 121
LO-2 Relays The GE relays are mounted externally and are connected to the LO-2 via a connecting cable. This cable terminates in a five-pin Molex-style connector that mates easily with one of the two headers provided at the bottom of the module as shown below:
The connector is keyed so that it locks into place after insertion. The connector on the left is output relay #1 and the one on the right is output relay #2. External relays are attached to the provided cable by matching the colors to those attached to the relay. The following indicates the connections for each pin of the relay connector: 1 2 3 4 5
1 2 3 4 5
Blue Red Black Yellow * Yellow *
1 2 3 4 5
24VAC Rectified On Off Pilot Contact Return Pilot Contact Source
* These connections only apply to the RR9 relay.
Andover Continuum I/O System Reference
117
Page 122
LO-2 Wiring External Controls The relays can each be controlled by external momentary switches or other momentary device such as a proximity detector. Each relay contains a set of input connections for the control. Connect the external control(s) as shown: Mechanical Switch without Integral Indicator: Momentary Switch
OFF
ON RED
BLK OVERRIDE YEL
WHT
Mechanical Switch with Integral Indicator: Momentary Switch
OFF
ON RED
BLK OVERRIDE
Indicator YEL
WHT
118
Schneider Electric
Page 123
LO-2 Controlling both Outputs with One Switch
RED
BLK OVERRIDE YEL
Momentary Switch
OFF
WHT
ON RED
BLK OVERRIDE YEL
WHT
Andover Continuum I/O System Reference
119
Page 124
LO-2 Occupancy Sensor Connection
RED (ON)
RED
BLK (OFF)
BLK OVERRIDE
Occupancy Sensor YEL
WHT (COM)
BLU (POWER)
WHT
28 VAC RECT.
Controlling both Outputs with One Occupancy Sensor To control both relays with the same Occupancy sensor, simply wire the red and black connections of each input bank together as indicated on the drawing on the previous page.
120
Schneider Electric
Page 125
LO-2
Status/Control Panel Status Indicators The LO-2 module includes a complete indicator status panel on the front of the module.
This panel includes indicators reporting on the status of the following: POWER
This green indicator illuminates when DC power is applied through the I/O Bus.
COMM
This yellow indicator illuminates when data is transmitted from the module to the NetController. In normal operation, data is only transmitted when an input value changes. This indicator will also flash periodically as the NetController checks the I/O bus.
STATUS
This red indicator is normally off. If it is always on or flashing at a fast rate, there is a problem with the module. This indicator can be manually illuminated from CyberStation or Command Terminal and used as a troubleshooting aid when locating a particular module.
OUTPUT
These red indicators (one for each channel) illuminate when an ‘ON’ condition is set. These indicators operate with RR-9 relays only.
28 VAC
This green indicator illuminates when 24–30 VAC power is supplied to the module by an external source.
Andover Continuum I/O System Reference
121
Page 126
LO-2 This panel also includes two operator switches that perform the following: COMMISSION
After physical installation and during configuration through the CyberStation workstation or Command Terminal, pressing this button registers the module’s address with the system. For more information, refer to the section on Module Configuration found earlier in this manual.
RESET
If the module becomes inoperable, pressing this button resets the module. It does not erase its memory.
122
Schneider Electric