Page 127
DIO-20
DIO-20 Input/Output Expansion Module The DIO 20 provides a connection for up to 20 solid state input or output modules for the Andover Continuum DM-20 Digital I/O module. The DIO 20 module can be mounted via a DIN Rail or directly to a panel. The DIO 20 includes individually fused sockets for up to 20 solid state input/output modules from manufacturers such as Opto 22, Grayhill, Gordos, Crydom and Potter & Brumfield.
FEATURES • 20* General Purpose Digital Inputs/Outputs • Each point may be configured as an input or an output • Direct connection to DM-20 Expansion Module •
*The actual number of modules that a DM20 can power depends on the mix of input and outputs modules desired. Refer to the DM-20/DIO-20 Power Requirements section found on page 94.
Andover Continuum I/O System Reference
123
Page 128
DIO-20 SPECIFICATIONS ELECTRICAL Power Supply Range: Power Consumption:
24 VDC All input modules installed: 12.7 Watts (529 mA) max; provided by an external power supply module. All output modules installed: 8.5 Watts (354 mA) max; provided by an external power supply module. DIO-20 board alone: 20mA Input Module max current: 23mA Output Module max current: 16mA
External Power Connector:
Two-position terminal block
Overload Protection:
5A fuse on all input/outputs.
INPUTS/OUTPUTS
20 total points; user-selectable channel-by-channel as inputs or outputs
Inputs: Input Type:
Outputs: Output Type:
I/O Connections:
Input ratings depend on input module(s) selected.
Output ratings depend on input module(s) selected.
25-position DB25 Female to DM-20 40-position screw-type terminal block for I/O
Compatible* Modules: Opto-22 Inputs
IDC24; 10-30VDC IAC24; 90-140VAC or VDC IAC24A; 180-240VAC
Opto-22 Outputs
ODC5; 60VDC@3A ODC5A; 200VDC@1A OAC5; 120VAC@3A OAC5A; 240VAC@3A OAC5A5; 120/240VAC@3A
* These manufacturers and model numbers represent devices that should be compatible. Their physical and electrical specifications appear to meet those of our product. However, this list does not constitute an endorsement of the product nor does it imply that the specifications listed are accurate. Ratings listed are nominal. Refer to manufacturer’s data sheets for limitations.
124
Schneider Electric
Page 129
DIO-20 DIO-20 Installation The DIO-20 (which includes the DIO 20 printed circuit board, three plastic PCB mounting brackets, and three plastic DIN rail mounting brackets) can be mounted to either a DIN Rail or directly to a bulkhead. The following are additional items required for installing the DIO-20: • • • • • • • •
Andover Continuum DM-20 I/O module 24 VDC Power Source Input/Output Wires 25-pin Interface cable Input/Output Modules Two DIN End Clamps DIN Rail Enclosure
Mounting to a DIN Rail 1. Slide an end clamp into position on the DIN Rail. Tighten the holding screws.
End Clamp DIN Rail
PCB Mounting Bracket
DIN Rail Mounting Bracket
2. Slide a DIN Rail Mounting Bracket under the PCB mounting bracket until flush on the back side.
Andover Continuum I/O System Reference
125
Page 130
DIO-20 3. Slide the DIN rail mounting bracket/PCB bracket assembly onto the DIN rail until flush with the end clamp. 4. Insert one end of the module PCB into the PCB bracket. Slide the board into the middle channel of the mounting bracket. Slide the DIN rail/PCB mounting bracket assembly onto the board and DIN rail. Carefully slide the assembled brackets into the center of the module board. 5. Slide the remaining bracket onto the DIN rail and position it at the end of the board. 6. Mount another end clamp. Tighten the screws on the end clamp.
Mounting Directly to a Panel There are four #6-sized holes (0.156” (4mm)) provided at the corners and one in the center for mounting using stand-offs directly to a flat surface. The following illustrates the mounting dimensions of the module.
Output
8.05 “ (204) 15.7 “ (399) 2.05”(52)
4.3” (108)
3.88 “ (98)
16.1 “ (409)
126
Schneider Electric
Page 131
DIO-20 I/O Connections The connections to the DM-20 are located on a 25-position DB25-type female connector located at the left side of the module. A separate two-conductor screw-type terminal connector provides 24VDC power. The input/output connections are located on a 40-position terminal block connector along the bottom of the module. These connections are labeled I/O1, I/O2, I/O3, and so forth. Each input/output occupies two adjacent positions of the connector. The diagram below indicates where each input number is located on the module. 24VDC * Connection
Main Power Fuse LED
Status LEDs
25-pin D Cable from DO80-LED or DM-20 Module
Output Fuses
Input/Output 1 typical
Input/Output Connection Screw Terminals
25-Pin D Connector
Connection
Description
Connection
Description
1 2 3 4 5 6 7 8 9 10 11 12
I/O 1 I/O 2 I/O 3 I/O 4 I/O 5 I/O 6 I/O 7 I/O 8 I/O 9 I/O 10 I/O 11 I/O 12
13 14 15 16 17 18 19 20 21 22 23 24 25
I/O 13 I/O 14 I/O 15 I/O 16 I/O 17 I/O 18 I/O 19 I/O 20 Ground Ground Ground Ground Ground
Andover Continuum I/O System Reference
127
Page 132
DIO-20 40-Position Terminal Block Connection 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
128
Description I/O 1 I/O 1 I/O 2 I/O 2 I/O 3 I/O 3 I/O 4 I/O 4 I/O 5 I/O 5 I/O 6 I/O 6 I/O 7 I/O 7 I/O 8 I/O 8 I/O 9 I/O 9 I/O 10 I/O 10
Schneider Electric
Connection 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
Description I/O 11 I/O 11 I/O 12 I/O 12 I/O 13 I/O 13 I/O 14 I/O 14 I/O 15 I/O 15 I/O 16 I/O 16 I/O 17 I/O 17 I/O 18 I/O 18 I/O 19 I/O 19 I/O 20 I/O 20
Page 133
AC-1 AC-1 Access Control Module The AC-1, Access Control Module, provides full I/O for an access controlled door or portal in one compact module. The AC-1 can be remotely located at a door reader for localized control and reduced wiring costs; or several AC-1 modules can be grouped together and DIN rail-mounted for centralized control. The AC-1 provides a Wiegand card input for Wiegand and Proximity type cards, reading up to 64 bits per card. Reader power is switch-selectable between 5 volts and 12 Volts to meet most card reader power requirements. The AC-1 provides two 5 Amp, Form C relays⎯one for the door lock and a second for local alarm annunciation. Each output has an integral hand-off-auto switch for manual operation, and software feedback of the switch position. Up to three supervised alarm inputs can be used for door status contacts, request-to-exit devices, a cabinet tamper switch, and any other two-state or three-state (on/off/trouble) alarm device. Keypad Control The AC-1 supports Wiegand output keypads. To simplify installation and reduce wiring costs, the keypad data comes into the module via the reader data lines.
FEATURES •
1 Card Reader Input
•
+5 V or +12 V reader power (switch selectable)
•
1 Card Reader LED control output
•
Up to 3 Supervised Inputs
•
2 FormC Relay Outputs rated 24 VAC/DC @ 5A
•
Override Toggle Switches w/Override Detection and Feedback
Andover Continuum I/O System Reference
129
Page 134
AC-1 SPECIFICATIONS ELECTRICAL Power Supply Range:
Input Voltage Range: 20-26V. 24V UL294 installations.
Power Consumption:
2.6 Watts + (15 Volts) * (Reader Current) max. @ 24 VDC; normally provided by Andover Continuum power supply module.
Overload Protection:
0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection
INPUTS/OUTPUTS Inputs Card Readers:
1
Card Reader Type:
Wiegand and Proximity readers *
Maximum Number of bits/Card:
64
Card Reader Power: +5 V or +12 V (switch selectable) Switch Setting +5 V +12 V
Output Voltage +5.20 V ±0.05V +12.0 V ±5%
Output Current 120 mA (max.) 180 mA (max.)
Wiring Distance: Card Reader to AC-1: 500 ft. max. using 18-gauge wire 200 ft. max. using 22-gauge wire Alarm Inputs:
Up to 3 supervised inputs. Single or double resistor supervision, series or parallel.
Input Protection:
Transient Voltage Suppressor (TVS) on each input
Outputs Door Outputs:
2 Form C relays
Output Rating:
24 VAC/VDC @ 5 Amp
Reader LED Output: Open collector; up to 50 mA. Output Protection:
5000 V isolation 270 V MOVs on each output
Overrides:
3-position manual override switch on each output for manual control of relay. LED override status indicator.
Override Feedback:
Override detection and software feedback provided for each output.
* The following reader and keypad models are the only approved for use in UL 294 Access Control applications: Essex KTP-163-SN keypad; HID Epic 32985 reader; Indala ASR-500 reader.
130
Schneider Electric
Page 135
AC-1 I/O Connections The actual I/O connections are located on a sixteen-position removable screw terminal connector located at the bottom of the module. Wires should enter from either the top or bottom wiring troughs, and outputs should come from the right side of the rack, inputs from the left (by convention). The diagram below indicates where each output number is located in the terminal block.
Connection
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15.
Description Earth Ground Reader +V Reader GND Reader DATA (Wiegand I) Reader CLK (Wiegand 0) Reader LED Sup Input Aux Sup Input Door Sup Input REX Sup Input RETURN Door NC Door NO Door COM OUT2 NC OUT2 NO OUT2 COM
Andover Continuum I/O System Reference
131
Page 136
AC-1 Using the AC-1 AC-1 is a complete card access control module designed to interface with the Schneider Electric NetController where an internal firmware-based Access Control supervisor resides. During normal operation, access control decisions are made in the Andover Continuum NetController CPU module database, which provides storage for up to 75,000 “local” personnel records (up to 4 million records may be created per database). The AC-1 is designed to control a single door. The door can be configured to allow entrance based on card only, card plus personal ID number (PIN), or keypad only. The door’s operating mode can even be changed based on time-of-day or other events for optimum flexibility through Schneider Electric’s easy-to-use Plain English programming language. Each keypad can also permit entry of a duress alarm code that can initiate an alarm sequence at any AC-1 controller or at the CyberStation workstation. Time-based anti-passback and entry/egress anti-passback are available to prevent tailgating. Entry/egress anti-passback is system-wide and can be performed by readers located on different AC-1 controllers across the network. Using Plain English, the AC-1 can also be used for custom access control sequences such as two-man rule, optical turnstile control, and man trap configurations.
Reader Power Switch Readers are available in both 5 Volt and 12 Volt varieties. The AC-1 module supports both by allowing the selection of a reader power source. A voltage selector switch is located on the front panel of the module. Insert the tip of a small screwdriver to slide the internal power switch into the desired position. Caution: Make sure the Reader Power switch is set properly. Setting the switch to 12 V for a 5 V reader may damage the unit. READER POWER + 5V, 120mA + 12V, 180mA
Internal switch slides up and down to make selection
132
Schneider Electric