Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 19 of 27

Andover Continuum I/O System Reference: Mixed Modules, pages 137 to 146

Pages 137 to 146 of 222, from Andover Continuum I/O System Reference

The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Andover Controls AC-1, Andover Controls DO-4, Andover Controls UI-8 and Schneider UI-8

Page 137

AC-1

Degrade Mode If network communications are interrupted, as a fail-safe mode, the AC-1 will revert to a programmable degraded mode of operation. System operation during degrade mode provides uninterrupted card access using site codes, cards formats, and other degrade mode parameters stored in non-volatile EEPROM in each AC-1 module. Degrade mode parameters are configured from the “Access Validation” section of the door editor’s “Entry Reader” tab. For dual reader doors, configurable degrade mode parameters are available from the “Access Validation” section of the door editor’s “Exit Reader” tab. During degrade mode, the AC-1 module supports: ƒ

Two of the site codes entered on the “Card Formats” tab of the door editor (out of four supported by the door during normal operation). The site codes supported are Site1 and Site2.

ƒ

One card type (determined below)

In NetController version 1.4 and forward, when more than one card type is selected at the door, the following procedure determines which one of the card types the AC-1 stores for degrade mode operation: 1. Open the door editor and de-select all card types except the one that you want the AC-1 to store for degrade mode operation. 2. Save the door settings by clicking “Apply”. 3. Select the other card types that will be allowed at the door in normal operation. 4. Save the door settings again by clicking “Apply” or “OK” to save and close the door editor.

WARNING:

The AC-1 is not recommended for use with inverted door output installations. For inverted door output installations, use the AC-1A or AC1 Plus modules.

Andover Continuum I/O System Reference

133

Page 138

AC-1

Connecting a Reader/Keypad Reader/Keypad Inputs The AC-1 includes a full interface to a single Wiegand access card reader. The modules were designed to allow integral reader/keypad units to be connected directly. Separate keypads that have similar interfaces (Wiegand) can be connected in parallel with a reader through the use of the Keypad Interface Module as shown on the following page. The Wiegand reader and/or reader/keypad unit is connected to the AC-1 module as shown below: +V

5V 12 V

GND

+V

Wiegand Reader or Reader with Keypad

GND

DATA / I

DATA I DATA 0 LED CLK / 0

LED

134

Schneider Electric

Page 139

AC-1

Connecting Two Readers or a Keypad and a Reader With the addition of the Keypad Interface Module (KIM), the AC-1 can interface to both a keypad and a reader simultaneously. This assumes that they are both Wiegand devices of similar voltage range. The KIM module presents the AC-1 with one pair of signals. Similarly, two readers can be connected with the KIM. This allows a site to slowly introduce a different type of reader (i.e., proximity) while allowing access through the normal reader. The KIM connects as shown below: Note: The KIM is not approved for use with UL 294 Access Control Systems. AC-1 +V

GND +V

Wiegand Reader or Reader with Keypad or Keypad only

GND LED DATA 1 CLK 0 LED

Keypad Interface Module P3 DATA / I CLK / 0

P1 DATA / I

DATA / I

CLK / 0

CLK / 0

P2 DATA / I CLK / 0

DATA 1

Wiegand Reader or Reader with Keypad or Keypad only

CLK 0 LED GND +V

Andover Continuum I/O System Reference

135

Page 140

AC-1

Connecting a CardKey Reader via the EMX34 With the addition of the Schneider Electric EMX34 CardKey to Wiegand interface you can connect a CardKey reader to the AC-1. The reader connects as shown below:

136

Schneider Electric

Page 141

AC-1 Connecting a Dual Reader Door With the addition of another AC-1 module, a door can be configured as a dual reader door. A door is a dual reader door when it has been configured with an entry and exit IOU module. A dual reader door is connected as shown below: AC-1 Entry IOU Supervised Input REX

Supervised Input Door

Entry Reader

Reader

Out2

Door Switch

Alarm Out

1-Door

AC-1 Exit IOU

Supervised Input

Exit Reader

Reader

Door Strike

Resistor Configuration (Corresponds to type of supervised input on AC-1 Entry IOU)

1-Door

NOTE: As the door switch connects only to the Entry IOU, the door switch operation at the Exit IOU is not supported in degrade mode. NOTE: The resistor configuration on the AC-1 Exit IOU matches the resistor configuration of the supervised input type. (Examples: NC Series, NC Series Parallel, or NO Series Parallel.) Connect only the resistor across the input, not any other wire connections.

Andover Continuum I/O System Reference

137

Page 142

AC-1

Connecting Supervisory Inputs All AC-1 inputs are supervisory inputs. The following drawings depict the three types of supervisory inputs that exist - two normally closed and one normally open type. NOTE: All resistor values are to be 10K ± 5%.

Normally Closed Supervised Inputs NC Series With this type of input wiring, a resistor is placed in series with the input being monitored. When the input contact presents a short circuit (normal closed position) the input is assumed in a normal closed state, the circuit presents a reading of 10 K Ωs at the input.

Circuit Action

Input Senses

Condition

Switch Closed Switch Opened Wire Cut Input Shorted

External Resistance Infinite Resistance Infinite Resistance Zero Ωs

Input contact Closed Input contact Open Input contact Open ‘Violation’ Violation or error

When the input contact is opened, the circuit opens and an infinite resistance is measured. If the wires to the input contact are cut it also appears as an “Input Contact Open” condition. In this case there would be an input contact open without a valid card swipe or valid keypad entry resulting in an “Input Contact Violation”. Shorting the input causes a zero Ω resistance, which also results in an input contact violation. When configuring for this type of contact select: ElecType: Resistor Type:

138

Supervised NCSeries

Schneider Electric

Page 143

AC-1 Normally Closed Supervised Inputs NC Series Parallel With this type of input wiring, two external resistors are added to the input, one in series and the other in parallel. When the input contact switch is closed (normal position) the input contact is assumed to be closed. The circuit presents a reading composed of both resistances in parallel that works out to be half the value of one of them (5 KΩ).

Circuit Action

Input Senses

Condition

Switch Closed Switch Opened Wire Cut Input Shorted

External Resistance ÷ 2 External Resistance Infinite Resistance Zero Ωs

Input contact Closed Input contact Open Violation or error Violation or error

When the input contact is opened the switch opens and the value of the parallel resistor is measured. If the wires to the input contact are cut it appears as an infinite resistance. Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance (open) should result in an error condition. When configuring for this type of contact select: ElecType: Resistor Type:

Supervised NCSerPar

Andover Continuum I/O System Reference

139

Page 144

AC-1

Normally Open Supervised Inputs NO Series Parallel With this type of input wiring, two external resistors are added to the input, one in series and the other in parallel. When the input contact switch is open (normal position), the input contact is assumed to be closed. The circuit reads the value of the parallel resistor.

Circuit Action

Input Senses

Condition

Switch Closed Switch Opened Wire Cut Input Shorted

External Resistance ÷ 2 External Resistance Infinite Resistance Zero Ωs

Input contact Open Input contact Closed Violation or error Violation or error

When the input contact is opened, the switch closes and a reading results that is composed of both resistances in parallel that works out to be half the value of one of them (5 KΩ). If the wires to the input contact are cut it appears as an infinite resistance. Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance (open) should result in an error condition. When configuring for this type of contact select: ElecType: Resistor Type:

140

Supervised NOSeriPar

Schneider Electric

Page 145

AC-1 Wiring Door Switches There are three supervisory inputs for door switches. The maximum length wire you can use is 500 ft of #18 gauge wire (152 m of 1.0 mm2 wire) or 200 ft of #22 gauge wire (60 m of 0.35 mm2 wire). Some switches have built-in resistors that facilitate Series Parallel connections as shown below: Switch with Built-In Resistor

AUX or DOOR or REX

10 KΩ

RET

Wiring Motion Detectors Motion detectors are devices that close a switch contact when motion is detected. Wiring is similar to a normal door switch input; however, the motion sensor requires an external power supply of 12 VDC or 24 VDC (UL listed under APHV). The maximum length wire you may use is 500 ft of #18 gauge wire (152 m of 1.0 mm2 wire) or 200 ft of #22 gauge wire (60 m of 0.35 mm2 wire). The following shows a typical motion detector circuit: AUX or DOOR or REX

No Motion Detected Normally Open PIR Motion Detector

10 KΩ

RET

AUX or DOOR or REX

Motion Detected

Normally Open PIR Motion Detector

10 KΩ

RET

Andover Continuum I/O System Reference

141

Page 146

AC-1 Connecting Outputs The AC-1 module includes two Form C single-pole double-throw relay outputs. The following is a simplified schematic of each output channel: OUT x NC

OUT x NO

OUT x COM

Both channels resemble the circuit shown above. To use the Form C output in your system, configure an output point with an Electrical Type of Digital. These output contacts operate as a standard relay. When the output is set to an “ON” state, the normally open contacts close and the normally closed contacts open. Note: When configuring a Digital point, there is a “Polarity” attribute. If this attribute is enabled, the operation of the outputs are reversed.

Override Controls The AC-1 module includes an output override switch for each output. ON OFF AUTO

The output of the module can be directed from program control or manual control. The output can be disabled completely as well.

142

Schneider Electric