AC-1 The following describes the actions associated with each position of the override controls: ON
The output relay is energized to an “ON”’ state manually by setting the switch to ON. Programs have no effect on the output when the switch is in this position.
OFF
The output relay is de-energized to an “OFF” state manually by setting the switch to OFF. Programs have no effect on the output when the switch is in this position.
AUTO
The action of the output relay is determined as a direct result of program control.
Andover Continuum I/O System Reference
143
Page 148
AC-1 Wiring Door Outputs The following represents a typical door output installation when the circuit is normally open:
This configuration shows a normally de-energized lock (when secured) in a fail secure mode. If power loss occurs, the lock closes. Always be sure to use “panic” hardware that allows emergency exit from the secured area.
144
Schneider Electric
Page 149
AC-1 Wiring Dual Reader Door Outputs The following represents a typical door output installation when the dual reader door circuit is controlling a fail-secure lock:
Andover Continuum I/O System Reference
145
Page 150
AC-1 Status/Control Panel Status Indicators The AC-1 module includes a complete indicator status panel on the front of the module.
This panel includes indicators reporting on the status of the following: POWER
This green indicator illuminates when DC power is applied through the I/O Bus.
COMM
This yellow indicator illuminates when data is transmitted from the module to the NetController. In normal operation, data is only transmitted when an input value changes. This indicator will also flash periodically as the NetController checks the I/O bus.
OVERRIDE
This red indicator illuminates whenever any of the override switches is in a position other than AUTO.
STATUS
This red indicator is normally off. If it is always on or flashing at a fast rate, there is a problem with the module. This indicator can be manually illuminated from the CyberStation workstation or Command Terminal and used as a troubleshooting aid when locating a particular module.
OUTPUT
These red indicators (one for each channel) illuminate when an output relay is energized.
READER POWER +5V, +12V
146
These green indicators illuminate when either voltage is selected as the reader power source.
Schneider Electric
Page 151
AC-1
This panel also includes two operator switches that perform the following: COMMISSION
After physical installation and during configuration through the CyberStation workstation or Command Terminal, pressing this button registers the module’s address with the system. For more information, refer to the section on Module Configuration found earlier in this manual.
RESET
Should the module become inoperable, pressing this button resets the module. It does not erase its memory.
Andover Continuum I/O System Reference
147
Page 152
AC-1A AC-1A Access Control Module The AC-1A, Access Control Module, provides full I/O for an access controlled door or portal in one compact module. The AC-1A can be remotely located at a door reader for localized control and reduced wiring costs; or several AC-1A modules can be grouped together and DIN rail-mounted for centralized control. The AC-1A provides a Wiegand card input for Wiegand and Proximity type cards, reading up to 64 bits per card. Reader power (5 volts) is provided to meet most card reader power requirements. The AC-1A includes two 5 Amp, Form C relays⎯one for the door lock and a second for local alarm annunciation. Each output has an integral hand-off-auto switch for manual operation, and software feedback of the switch position. Up to three supervised alarm inputs can be used for door status contacts, request-to-exit devices, a cabinet tamper switch, and any other two-state or three-state (on/off/trouble) alarm device. Keypad Control The AC-1A supports Wiegand output keypads. To simplify installation and reduce wiring costs, the AC-1A has a second set of connections.
FEATURES •
1 Card Reader Input*
•
1 Keypad Input* * Only one of these two devices can be active at any given moment.
148
Schneider Electric
•
+5 V reader power
•
1 Card Reader LED control output
•
Up to 3 Supervised Inputs
•
2 FormC Relay Outputs rated 24 VAC/DC @ 5A
•
Override Toggle Switches w/Override Detection and Feedback
•
10–28 V Power Supply Range
Page 153
AC-1A SPECIFICATIONS ELECTRICAL Power Supply Range:
Input Voltage Range: 10-28V. 24V for UL864 and UL294 installations.
Power Consumption:
2.0 Watts + (Input Voltage) * (Reader Current) max. @ 24 VDC; normally provided by Andover Continuum power supply module.
Overload Protection:
0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection
INPUTS/OUTPUTS Inputs Card Readers:
1*
Keypads:
1*
Card Reader Type:
Wiegand and Proximity readers
Maximum Number of bits/Card:
64
Card Reader Power: +5 V (±3%) @50 mA (max.) Wiring Distance: To Card Reader:
500 ft. max. using 18-gauge wire 200 ft. max. using 22-gauge wire
Alarm Inputs:
Up to 3 supervised inputs. Single or double resistor supervision, series or parallel.
Input Protection:
Transient Voltage Suppressor (TVS) on each input
* Only one of these two devices can be active at any given moment.
Outputs Door Outputs:
2 Form C relays
Output Rating:
24 VAC/VDC @ 5 Amp
Reader LED Output: Open collector; up to 100 mA. Output Protection:
5000 V isolation 270 V MOVs on each output
Overrides:
3-position manual override switch on each output for manual control of relay. LED override status indicator.
Override Feedback:
Override detection and software feedback provided for each output.
Andover Continuum I/O System Reference
149
Page 154
AC-1A I/O Connections The actual I/O connections are located on an eighteen-position removable screw terminal connector located at the bottom of the module. Wires should enter from either the top or bottom wiring troughs, and outputs should come from the right side of the rack, inputs from the left (by convention). The diagram below indicates where each output number is located in the terminal block.
Connection
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17.
150
Description Earth Ground Reader +5V Reader GND Reader DATA (Wiegand I) Reader CLK (Wiegand 0) Keypad DATA (Wiegand I) Keypad CLK (Wiegand 0) Reader LED Sup Input 1 Aux Sup Input 2 Door Sup Input 3 REX Sup Input RETURN 1-Door NC 1-Door NO 1-Door COM OUT2 NC OUT2 NO OUT2 COM
Schneider Electric
Page 155
AC-1A Using the AC-1A AC-1A is a complete card access control module designed to interface with the Schneider Electric NetController where an internal firmware-based Access Control supervisor resides. During normal operation, access control decisions are made in the Andover Continuum NetController CPU module database, which provides storage for up to 75,000 “local” personnel records (up to 4 million records may be created per database). The AC-1A is designed to control a single door. The door can be configured to allow entrance based on card only, card plus personal ID number (PIN), or keypad only. The door’s operating mode can even be changed based on time-of-day or other events for optimum flexibility through Schneider Electric’s easy-to-use Plain English programming language. Each keypad can also permit entry of a duress alarm code that can initiate an alarm sequence at any AC-1A controller or at the CyberStation workstation. Time-based anti-passback and entry/egress anti-passback are available to prevent tailgating. Entry/egress anti-passback is system-wide and can be performed by readers located on different AC-1A controllers across the network. Using Plain English, the AC-1A can also be used for custom access control sequences such as two-man rule, optical turnstile control, and man trap configurations. The AC-1A also supports inverted door output installations.
Degrade Mode If network communications are interrupted, as a fail-safe mode, the AC-1A will revert to a programmable degraded mode of operation. System operation during degrade mode provides uninterrupted card access using site codes, cards formats, and other degrade mode parameters stored in non-volatile EEPROM in each AC-1A module. Degrade mode parameters are configured from the “Access Validation” section of the door editor’s “Entry Reader” tab. For dual reader doors, configurable degrade mode parameters are available from the “Access Validation” section of the door editor’s “Exit Reader” tab.
Andover Continuum I/O System Reference
151
Page 156
AC-1A During degrade mode, the AC-1A module supports: ƒ
Two of the site codes entered on the “Card Formats” tab of the door editor (out of four supported by the door during normal operation). The site codes supported are Site1 and Site2.
ƒ
One card type (determined below)
Note: In the NetController version 1.4 and forward, when more than one card type is selected at the door, the following procedure determines which one of the card types the AC-1A stores for degrade mode operation: 1. Open the door editor and de-select all card types except the one that you want the AC-1A to store for degrade mode operation. 2. Save the door settings by clicking “Apply”. 3. Select the other card types that will be allowed at the door in normal operation. 4. Save the door settings again by clicking “Apply” or “OK” to save and close the door editor.
152