AC-1A Connecting a Reader/Keypad Reader/Keypad Inputs The AC-1A includes a full interface to a single Wiegand access card reader and a keypad. The modules were designed to allow Integral reader/keypad units to be connected directly. Separate keypads that have similar interfaces (Wiegand) can be connected through the keypad connections provided on the terminal block. The Wiegand reader, keypad and/or reader/keypad unit is connected to the AC-1A module as shown below: + 5V
GND
+V
Wiegand Reader or Wiegand Keypad or Reader with Keypad
GND
DATA / I
DATA I DATA 0 LED CLK / 0
LED
Andover Continuum I/O System Reference
153
Page 158
AC-1A
Connecting Two Readers or a Keypad and a Reader The AC-1A can interface to both a keypad and a reader simultaneously. This assumes that they are both Wiegand devices of similar voltage range. Similarly, two readers can be connected. This allows a site to slowly introduce a different type of reader (i.e., proximity) while allowing access through the normal reader. The connections are as shown below: AC-1A
1
+ 5V
GND +V
2
GND
Wiegand Reader or Wiegand Keypad
LED DATA 1 CLK 0 7
3
LED
DATA / I CLK / 0
4 5
DATA / I CLK / 0
6
DATA 1
Wiegand Reader or Wiegand Keypad
CLK 0 LED GND +V
154
Schneider Electric
Page 159
AC-1A
Connecting Two Readers for a Dual Reader Door With the addition of another AC-1A module, a door can be configured as a dual reader door. A door is a dual reader door when it has been configured with an entry and exit IOU module. A dual reader door is connected as shown below:
AC-1A Entry IOU
Request to Exit Device
Supervised Input REX
Supervised Input Door
Entry Reader
Reader
Out2
Door Switch
Alarm Out
1-Door
AC-1A Exit IOU
Exit Reader
Door Strike
Reader 1-Door
Note: As the door switch connects only to the Entry IOU, the door switch operation at the Exit IOU is not supported in degrade mode.
Andover Continuum I/O System Reference
155
Page 160
AC-1A Connecting Supervisory Inputs All AC-1A inputs are supervisory inputs. The following drawings depict the three types of supervisory inputs that exist - two normally closed and one normally open type. NOTE: All resistor values are to be 10K ± 5%.
Normally Closed Supervised Inputs NC Series With this type of input wiring, a resistor is placed in series with the input being monitored. When the input contact presents a short circuit (normal closed position), the input is assumed to be in a normal closed state, the circuit presents a reading of 10 K Ωs at the input.
Circuit Action
Input Senses
Condition
Switch Closed Switch Opened Wire Cut Input Shorted
External Resistance Infinite Resistance Infinite Resistance Zero Ωs
Input contact Closed Input contact Open Input contact Open ‘Violation’ Violation or error
When the input contact is opened, the circuit opens and an infinite resistance is measured. If the wires to the input contact are cut it also appears as an “input contact open” condition. In this case there would be an input contact open without a valid card swipe or valid keypad entry resulting in an “input contact violation”. Shorting the input causes a zero Ω resistance, which also results in an input contact violation. When configuring for this type of contact select: ElecType: Resistor Type:
156
Supervised NCSeries
Schneider Electric
Page 161
AC-1A
Normally Closed Supervised Inputs NC Series Parallel With this type of input wiring, two external resistors are added to the input, one in series and the other in parallel. When the input contact switch is closed (normal position), the input contact is assumed to be closed. The circuit presents a reading composed of both resistances in parallel that works out to be half the value of one of them (5 KΩ).
Circuit Action
Input Senses
Condition
Switch Closed Switch Opened Wire Cut Input Shorted
External Resistance ÷ 2 External Resistance Infinite Resistance Zero Ωs
Input contact Closed Input contact Open Violation or error Violation or error
When the input contact is opened, the switch opens and the value of the parallel resistor is measured. If the wires to the input contact are cut it appears as an infinite resistance. Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance (open) should result in an error condition. When configuring for this type of contact select: ElecType: Resistor Type:
Supervised NCSerPar
Andover Continuum I/O System Reference
157
Page 162
AC-1A Normally Open Supervised Inputs NO Series Parallel With this type of input wiring, two external resistors are added to the input, one in series and the other in parallel. When the input contact switch is open (normal position) the input contact is assumed to be closed. The circuit reads the value of the parallel resistor.
Circuit Action
Input Senses
Condition
Switch Closed Switch Opened Wire Cut Input Shorted
External Resistance ÷ 2 External Resistance Infinite Resistance Zero Ωs
Input contact Open Input contact Closed Violation or error Violation or error
When the input contact is opened the switch closes and a reading results that is composed of both resistances in parallel that works out to be half the value of one of them (5 KΩ). If the wires to the input contact are cut it appears as an infinite resistance. Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance (open) should result in an error condition. When configuring for this type of contact select: ElecType: Resistor Type:
158
Supervised NOSeriPar
Schneider Electric
Page 163
AC-1A Wiring Door Switches There are three supervisory inputs for door switches. The maximum length wire you can use is 500 ft of #18 gauge wire (152 m of 1.0 mm2 wire) or 200 ft of #22 gauge wire (60 m of 0.35 mm2 wire). Some switches have built-in resistors that facilitate Series Parallel connections as shown below: Switch with Built-In Resistor
AUX or DOOR or REX
10 KΩ
RET
Wiring Motion Detectors Motion detectors are devices that close a switch contact when motion is detected. Wiring is similar to a normal door switch input, however, the motion sensor requires an external power supply of 12 VDC or 24 VDC (UL listed under APHV). The maximum length wire you may use is 500 ft of #18 gauge wire (152 m of 1.0 mm2 wire) or 200 ft of #22 gauge wire (60 m of 0.35 mm2 wire). The following shown a typical motion detector circuit: AUX or DOOR or REX
No Motion Detected Normally Open PIR Motion Detector
10 KΩ
RET
AUX or DOOR or REX
Motion Detected
Normally Open PIR Motion Detector
10 KΩ
RET
Andover Continuum I/O System Reference
159
Page 164
AC-1A Connecting Outputs The AC-1A module includes two Form C single-pole double-throw relay outputs. The following is a simplified schematic of each output channel: OUT x NC
OUT x NO
OUT x COM
Both channels resemble the circuit shown above. To use the Form C output in your system, configure an output point with an Electrical Type of Digital. These output contacts operate as a standard relay. When the output is set to an “ON” state, the normally open contacts close and the normally closed contacts open. NOTE: When configuring a Digital point, there is a ‘Polarity’ attribute. If this attribute is enabled, the operation of the outputs are reversed.
Override Controls The AC-1A module includes an output override switch for each output. ON OFF AUTO
The output of the module can be directed from program control or manual control. The output can be disabled completely as well.
160
Schneider Electric
Page 165
AC-1A The following describes the actions associated with each position of the override controls: ON
The output relay is energized to an “ON” state manually by setting the switch to ON. Programs have no effect on the output when the switch is in this position.
OFF
The output relay is de-energized to an “OFF” state manually by setting the switch to OFF. Programs have no effect on the output when the switch is in this position.
AUTO
The action of the output relay is determined as a direct result of program control.
Wiring Door Outputs The following represents a typical door output installation when the circuit is normally open:
MOV (Andover #01-2020-095)
C Door Strike (UL listed burglary-resistant electric locking mechanism (CVXY))
12/24V Power Supply (UL listed power supply (APHV))
This configuration shows a normally de-energized lock (when secured) in a fail secure mode. If power loss occurs, the lock closes. Always be sure to use “panic” hardware that allows emergency exit from the secured area.
Andover Continuum I/O System Reference
161
Page 166
AC-1A
The following represents a typical door output installation when the circuit is normally closed: MOV (Andover #01-2020-095)
C Electromagnetic Door Lock (UL listed burglary-resistant electric locking mechanism (CVXY))
12/24V Power Supply (UL listed power supply (APHV))
This configuration shows a normally de-energized lock (when secured), in a fail safe mode. If power loss occurs, the lock opens.
162