Andover Continuum I/O System Reference: Mixed Modules, pages 157 to 166

Pages 157 to 166 of 222, from Andover Continuum I/O System Reference

The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Andover Controls AC-1, Andover Controls DO-4, Andover Controls UI-8 and Schneider UI-8

Page 157

AC-1A Connecting a Reader/Keypad Reader/Keypad Inputs The AC-1A includes a full interface to a single Wiegand access card reader and a keypad. The modules were designed to allow Integral reader/keypad units to be connected directly. Separate keypads that have similar interfaces (Wiegand) can be connected through the keypad connections provided on the terminal block. The Wiegand reader, keypad and/or reader/keypad unit is connected to the AC-1A module as shown below: + 5V

GND

+V

Wiegand Reader or Wiegand Keypad or Reader with Keypad

GND

DATA / I

DATA I DATA 0 LED CLK / 0

LED

Andover Continuum I/O System Reference

153

Page 158

AC-1A

Connecting Two Readers or a Keypad and a Reader The AC-1A can interface to both a keypad and a reader simultaneously. This assumes that they are both Wiegand devices of similar voltage range. Similarly, two readers can be connected. This allows a site to slowly introduce a different type of reader (i.e., proximity) while allowing access through the normal reader. The connections are as shown below: AC-1A

1

+ 5V

GND +V

2

GND

Wiegand Reader or Wiegand Keypad

LED DATA 1 CLK 0 7

3

LED

DATA / I CLK / 0

4 5

DATA / I CLK / 0

6

DATA 1

Wiegand Reader or Wiegand Keypad

CLK 0 LED GND +V

154

Schneider Electric

Page 159

AC-1A

Connecting Two Readers for a Dual Reader Door With the addition of another AC-1A module, a door can be configured as a dual reader door. A door is a dual reader door when it has been configured with an entry and exit IOU module. A dual reader door is connected as shown below:

AC-1A Entry IOU

Request to Exit Device

Supervised Input REX

Supervised Input Door

Entry Reader

Reader

Out2

Door Switch

Alarm Out

1-Door

AC-1A Exit IOU

Exit Reader

Door Strike

Reader 1-Door

Note: As the door switch connects only to the Entry IOU, the door switch operation at the Exit IOU is not supported in degrade mode.

Andover Continuum I/O System Reference

155

Page 160

AC-1A Connecting Supervisory Inputs All AC-1A inputs are supervisory inputs. The following drawings depict the three types of supervisory inputs that exist - two normally closed and one normally open type. NOTE: All resistor values are to be 10K ± 5%.

Normally Closed Supervised Inputs NC Series With this type of input wiring, a resistor is placed in series with the input being monitored. When the input contact presents a short circuit (normal closed position), the input is assumed to be in a normal closed state, the circuit presents a reading of 10 K Ωs at the input.

Circuit Action

Input Senses

Condition

Switch Closed Switch Opened Wire Cut Input Shorted

External Resistance Infinite Resistance Infinite Resistance Zero Ωs

Input contact Closed Input contact Open Input contact Open ‘Violation’ Violation or error

When the input contact is opened, the circuit opens and an infinite resistance is measured. If the wires to the input contact are cut it also appears as an “input contact open” condition. In this case there would be an input contact open without a valid card swipe or valid keypad entry resulting in an “input contact violation”. Shorting the input causes a zero Ω resistance, which also results in an input contact violation. When configuring for this type of contact select: ElecType: Resistor Type:

156

Supervised NCSeries

Schneider Electric

Page 161

AC-1A

Normally Closed Supervised Inputs NC Series Parallel With this type of input wiring, two external resistors are added to the input, one in series and the other in parallel. When the input contact switch is closed (normal position), the input contact is assumed to be closed. The circuit presents a reading composed of both resistances in parallel that works out to be half the value of one of them (5 KΩ).

Circuit Action

Input Senses

Condition

Switch Closed Switch Opened Wire Cut Input Shorted

External Resistance ÷ 2 External Resistance Infinite Resistance Zero Ωs

Input contact Closed Input contact Open Violation or error Violation or error

When the input contact is opened, the switch opens and the value of the parallel resistor is measured. If the wires to the input contact are cut it appears as an infinite resistance. Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance (open) should result in an error condition. When configuring for this type of contact select: ElecType: Resistor Type:

Supervised NCSerPar

Andover Continuum I/O System Reference

157

Page 162

AC-1A Normally Open Supervised Inputs NO Series Parallel With this type of input wiring, two external resistors are added to the input, one in series and the other in parallel. When the input contact switch is open (normal position) the input contact is assumed to be closed. The circuit reads the value of the parallel resistor.

Circuit Action

Input Senses

Condition

Switch Closed Switch Opened Wire Cut Input Shorted

External Resistance ÷ 2 External Resistance Infinite Resistance Zero Ωs

Input contact Open Input contact Closed Violation or error Violation or error

When the input contact is opened the switch closes and a reading results that is composed of both resistances in parallel that works out to be half the value of one of them (5 KΩ). If the wires to the input contact are cut it appears as an infinite resistance. Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance (open) should result in an error condition. When configuring for this type of contact select: ElecType: Resistor Type:

158

Supervised NOSeriPar

Schneider Electric

Page 163

AC-1A Wiring Door Switches There are three supervisory inputs for door switches. The maximum length wire you can use is 500 ft of #18 gauge wire (152 m of 1.0 mm2 wire) or 200 ft of #22 gauge wire (60 m of 0.35 mm2 wire). Some switches have built-in resistors that facilitate Series Parallel connections as shown below: Switch with Built-In Resistor

AUX or DOOR or REX

10 KΩ

RET

Wiring Motion Detectors Motion detectors are devices that close a switch contact when motion is detected. Wiring is similar to a normal door switch input, however, the motion sensor requires an external power supply of 12 VDC or 24 VDC (UL listed under APHV). The maximum length wire you may use is 500 ft of #18 gauge wire (152 m of 1.0 mm2 wire) or 200 ft of #22 gauge wire (60 m of 0.35 mm2 wire). The following shown a typical motion detector circuit: AUX or DOOR or REX

No Motion Detected Normally Open PIR Motion Detector

10 KΩ

RET

AUX or DOOR or REX

Motion Detected

Normally Open PIR Motion Detector

10 KΩ

RET

Andover Continuum I/O System Reference

159

Page 164

AC-1A Connecting Outputs The AC-1A module includes two Form C single-pole double-throw relay outputs. The following is a simplified schematic of each output channel: OUT x NC

OUT x NO

OUT x COM

Both channels resemble the circuit shown above. To use the Form C output in your system, configure an output point with an Electrical Type of Digital. These output contacts operate as a standard relay. When the output is set to an “ON” state, the normally open contacts close and the normally closed contacts open. NOTE: When configuring a Digital point, there is a ‘Polarity’ attribute. If this attribute is enabled, the operation of the outputs are reversed.

Override Controls The AC-1A module includes an output override switch for each output. ON OFF AUTO

The output of the module can be directed from program control or manual control. The output can be disabled completely as well.

160

Schneider Electric

Page 165

AC-1A The following describes the actions associated with each position of the override controls: ON

The output relay is energized to an “ON” state manually by setting the switch to ON. Programs have no effect on the output when the switch is in this position.

OFF

The output relay is de-energized to an “OFF” state manually by setting the switch to OFF. Programs have no effect on the output when the switch is in this position.

AUTO

The action of the output relay is determined as a direct result of program control.

Wiring Door Outputs The following represents a typical door output installation when the circuit is normally open:

MOV (Andover #01-2020-095)

C Door Strike (UL listed burglary-resistant electric locking mechanism (CVXY))

12/24V Power Supply (UL listed power supply (APHV))

This configuration shows a normally de-energized lock (when secured) in a fail secure mode. If power loss occurs, the lock closes. Always be sure to use “panic” hardware that allows emergency exit from the secured area.

Andover Continuum I/O System Reference

161

Page 166

AC-1A

The following represents a typical door output installation when the circuit is normally closed: MOV (Andover #01-2020-095)

C Electromagnetic Door Lock (UL listed burglary-resistant electric locking mechanism (CVXY))

12/24V Power Supply (UL listed power supply (APHV))

This configuration shows a normally de-energized lock (when secured), in a fail safe mode. If power loss occurs, the lock opens.

162

Schneider Electric