Page 167
AC-1A
Wiring Dual Reader Door Outputs The following represents a typical door output installation when the dual reader door circuit is controlling a fail-secure lock: Exit IOU
Entry IOU MOV (Andover #01-2020-095)
C Door Strike Fail-Secure Lock (UL listedDoor burglary-resistant (Energize unlock) electric to locking mechanism (CVXY)) UL-listed burglary-resistant Electric locking mechanism (CVXY)
12/24V Power Supply (UL listed power supply (APHV))
Andover Continuum I/O System Reference
163
Page 168
AC-1A
The following represents a typical door output installation when the dual reader door circuit is controlling a fail-safe lock: Exit IOU
MOV (Andover #01-2020-095)
Entry IOU C Electromagnetic Fail-Safe Door LockDoor Lock (UL listed (Energize toburglary-resistant lock) electric locking mechanism (CVXY)) UL-listed burglary-resistant Electric locking mechanism (CVXY)
12/24V Power Supply (UL listed power supply (APHV))
164
Schneider Electric
Page 169
AC-1A Status/Control Panel Status Indicators The AC-1A module includes a complete indicator status panel on the front of the module.
This panel includes indicators reporting on the status of the following: POWER
This green indicator illuminates when DC power is applied through the I/O Bus.
COMM
This yellow indicator illuminates when data is transmitted from the module to the NetController. In normal operation, data is only transmitted when an input value changes. This indicator will also flash periodically as the NetController checks the I/O bus.
OVERRIDE
This red indicator illuminates whenever any of the override switches is in a position other than AUTO.
STATUS
This red indicator is normally off. If it is always on or flashing at a fast rate, there is a problem with the module. This indicator can be manually illuminated from the CyberStation workstation or Command Terminal and used as a troubleshooting aid when locating a particular module.
OUTPUT
These red indicators (one for each channel) illuminate when an output relay is energized.
READER POWER +5V
This green indicator illuminates when the reader power source is operational. Andover Continuum I/O System Reference
165
Page 170
AC-1A
This panel also includes two operator switches that perform the following: COMMISSION
After physical installation and during configuration through the CyberStation workstation or Command Terminal, pressing this button registers the module’s address with the system. For more information, refer to the section on Module Configuration found earlier in this manual.
RESET
If the module becomes inoperable, pressing this button resets the module. It does not erase its memory.
166
Schneider Electric
Page 171
AC-1 Plus AC-1 Plus Access Control Module The AC-1 Plus, Access Control Module, provides full I/O for an access controlled door or portal in one compact module. The AC-1 Plus can be remotely located at a door reader for localized control and reduced wiring costs; or several AC-1 Plus modules can be grouped together and DIN rail-mounted for centralized control. The AC-1 Plus provides a reader input connection for Wiegand/ABA/CK34 and Proximity type cards, reading up to 64 bits per card for Wiegand cards and 255 bits per card for ABA cards. Reader power (5 volts) is provided to meet most card reader power requirements. The AC-1 Plus includes two 5 Amp, Form C relays⎯one for the door lock and a second for local alarm annunciation. Each output has an integral hand-off-auto switch for manual operation, and software feedback of the switch position. Up to five supervised alarm inputs can be used for door status contacts, ADA request-toexit devices, a cabinet tamper switch, and any other two-state or three-state (on/off/trouble) alarm device. Keypad Control The AC-1Plus supports Wiegand output keypads. To simplify installation and reduce wiring costs, the keypad data comes into the module via the reader data lines. FEATURES •
1 Card Reader Input*
•
1 Keypad Input* ♦
*Only one of these two devices can be active at any given moment.
•
Wiegand/ABA or CK34 formats supported
•
+5 V reader power
•
2 Card Reader LED control outputs
•
Up to 5 Supervised Inputs
•
2 FormC Relay Outputs rated 24 VAC/DC @ 5A
•
Override Toggle Switches w/Override Detection and Feedback
•
Supports Bond Sensor and ADA input switches
Andover Continuum I/O System Reference
167
Page 172
AC-1 Plus SPECIFICATIONS ELECTRICAL Power Supply Range:
Input Voltage Range: 10-28V. 24V for UL294 installations.
Power Consumption:
2.2 Watts + (Input Voltage) * (Reader Current) max.@ 24 VDC; normally provided by Andover Continuum power supply module.
Overload Protection:
0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection
INPUTS/OUTPUTS Inputs Card Readers:
1*
Keypad:
1*
* Only one of these two devices can be active at any given moment. Card Reader Type:
Wiegand, ABA or CardKey (switch selectable) **
Maximum Number of bits/Card:
64 (Wiegand) 255 (ABA)
Card Reader Power: +5 V (±3%) @50 mA (max.) Wiring Distance Card Reader to AC-1 Plus:
500 ft. max. using 18-gauge wire 200 ft. max. using 22-gauge wire
Alarm Inputs:
Up to 5 supervised inputs. Single or double resistor supervision, series or parallel.
Input Protection:
Transient voltage suppressor (TVS) on each input
** The following reader and keypad models are the only approved devices for use in UL 294 Access Control applications: Essex KTP-163-SN keypad; HID Epic 32985 Wiegand reader; Indala ASR-500 Wiegand reader.
Outputs Door Outputs:
2 Form C relays
Output Rating:
24 VAC/VDC @ 5 Amp
Reader LED Output: (2) each, open collector; up to 100 mA.
168
Output Protection:
5000 V isolation 270 V MOVs on each output
Overrides:
3-position manual override switch on each output for manual control of relay. LED override status indicator.
Override Feedback:
Override detection and software feedback provided for each output.
Schneider Electric
Page 173
AC-1 Plus I/O Connections The actual I/O connections are located on a sixteen-position removable screw terminal connector located at the bottom of the module. Wires should enter from either the top or bottom wiring troughs, and outputs should come from the right side of the rack, inputs from the left (by convention). The diagram below indicates where each output number is located in the terminal block.
Connection
Description
1. 2. 3. 4. 5. 6. 7. 8.
Reader +5V Reader GND Reader DATA (Wiegand I) Reader CLK (Wiegand 0) Keypad DATA (Wiegand I) Keypad CLK (Wiegand 0) Reader LED1 Reader LED2
9. 10. 11. 12. 13. 14. 15. 16.
Earth Ground IN1 IN2 RET IN3 IN4 RET IN5
17. 18. 19. 20. 21. 22.
OUT1 NC OUT1 NO OUT1 COMM OUT2 NC OUT2 NO OUT2 COMM
Andover Continuum I/O System Reference
169
Page 174
AC-1 Plus Using the AC-1 Plus AC-1 Plus is a complete card access control module designed to interface with the Schneider Electric NetController where an internal firmware-based Access Control supervisor resides. During normal operation, access control decisions are made in the Andover Continuum NetController CPU module database, which provides storage for up to 75,000 “local” personnel records (up to 4 million records can be created per database). The AC-1 Plus is designed to control a single door. The door can be configured to allow entrance based on card only, card plus personal ID number (PIN), or keypad only. The door’s operating mode can even be changed based on time-of-day or other events for optimum flexibility through Schneider Electric’s easy-to-use Plain English programming language. Each keypad can also permit entry of a duress alarm code that can initiate an alarm sequence at any AC-1 Plus controller or at the Andover Continuum CyberStation. The AC-1 Plus also supports ADA (Alternate Door Access) and inverted door output installations and Bond Sensor circuitry. A bond sensor detects the actual status (locked or unlocked) of the door. Time-based anti-passback and entry/egress anti-passback are available to prevent tailgating. Entry/egress anti-passback is system-wide and can be performed by readers located on different AC-1 and AC-1 Plus controllers across the network. Using Plain English, the AC-1 Plus can also be used for custom access control sequences such as two-man rule, optical turnstile control, and man trap configurations.
Reader Power The AC-1 Plus module supports 5 volt DC readers. Reader Type Switch The AC-1 Plus supports three card formats. The Reader Type switch selects either Wiegand/ABA or CardKey (CK34) format.
170
Schneider Electric
Page 175
AC-1 Plus
Degrade Mode If network communications are interrupted, as a fail-safe mode, the AC-1 Plus will revert to a programmable degraded mode of operation. System operation during degrade mode provides uninterrupted card access using site codes, cards formats, and other degrade mode parameters stored in non-volatile EEPROM (such as the settings of the AccessLEDPattern Numeric) in each AC-1 Plus module. Degrade mode parameters are configured from the “Access Validation” section of the door editor’s “Entry Reader” tab. For dual reader doors, configurable degrade mode parameters are available from the “Access Validation” section of the door editor’s “Exit Reader” tab. During degrade mode, the AC-1 Plus module supports: ƒ
All four site codes entered on the “Card Formats” tab of the door editor
ƒ
All card types selected on the “Card Formats” tab of the door editor
ƒ
ADA functionality
ƒ
General codes (Keypad)
ƒ
Door Switch operation on both the Entry and Exit IOU of a dual-reader door
Andover Continuum I/O System Reference
171
Page 176
AC-1 Plus
Reader LED Pattern For the AC-1 Plus, the LED pattern of the reader is determined by the creation of an InfinityNumeric called AccessLEDPattern. The settings are described as follows: Schneider Electric LED Pattern (AccessLEDPattern = 0) This pattern is transaction based, meaning the reader LED indicates the state of the access transaction.
ReaderLED
Description
Solid Red
No door configured on this reader channel. The system will not process any transaction coming from this reader
Solid Green
Door configured on this reader channel. System is ready to process an access transaction (i.e. card swipe)
Solid Red for 3 seconds following an access transaction
Invalid Attempt
Rapid Flashing following an access transaction
Valid Access
Slow Flashing following an access transaction
System is waiting for information needed to process the transaction. I.e. Transaction is being processed (remote validation) or the system is waiting for user entry (PIN needed after card swipe).
NOTE1:
Starting in V1.1, LED2 will turn ON whenever the door is open. This can be used to control another indicator LED, such as a keypad LED.
NOTE2:
A manual override does not affect the Reader LED for the Schneider Electric LED pattern.
172
Schneider Electric