Andover Continuum I/O System Reference: Mixed Modules, pages 177 to 186

Pages 177 to 186 of 222, from Andover Continuum I/O System Reference

The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Andover Controls AC-1, Andover Controls DO-4, Andover Controls UI-8 and Schneider UI-8

Page 177

AC-1 Plus Alternate LED Pattern (AccessLEDPattern = 1) This pattern follows the state of the door lock itself. ReaderLED

Description

Solid Red

Door is locked

Solid Green

Door is unlocked

Rapid Flashing following an access transaction

Invalid attempt

Slow Flashing following an access transaction

System is waiting for information needed to process the transaction. I.e. Transaction is being processed. (remote validation) or the system is waiting for user entry. (PIN needed after card swipe)

NOTE:

Starting in V1.1, LED2 will turn ON whenever the door is open. This can be used to control another indicator LED, such as a keypad LED.

Andover Continuum I/O System Reference

173

Page 178

AC-1 Plus CardKey LED Pattern (AccessLEDPattern = 2)

ReaderLED – Red

ReaderLED - Green

Description

OFF

OFF

Door is locked

OFF

ON

Door is unlocked

ON

OFF

Invalid attempt

Slow Flashing following an access transaction

OFF

System is waiting for information needed to process the transaction. I.e. Transaction is being processed. (remote validation) or the system is waiting for user entry. (PIN needed after card swipe)

NOTE1:

The 12V incandescent lamp power is not provided by the AC-1plus.

NOTE2:

The RED lamp is controlled by the LED1 output and the GREEN lamp is controlled by the LED2 output.

174

Schneider Electric

Page 179

AC-1 Plus Dorado780 LED Pattern (AccessLEDPattern = 3) This LED pattern was designed to be used with the Dorado Model 780 ABA Reader/Keypad.

“Slide Card”

“Enter Code”

“Open Door”

Description

LED - Red

LED – Amber

LED – Green

ON

OFF

OFF

Waiting for card swipe

Slow Flashing

OFF

OFF

System is validating the card swipe

OFF

ON

OFF

Waiting for PIN entry

OFF

Slow Flashing

OFF

System is validating the PIN entry

OFF

OFF

ON

Door is unlocked

Rapid Flashing

Rapid Flashing

OFF

Invalid attempt

NOTE1:

The dipswitches on the Dorado Model 780 must be set for CLOCK/DATA operation.

NOTE2:

The LED1 output on the AC-1plus is wired to the LED A input on the Dorado Model 780, and the LED2 output is wired to the LED B input.

Andover Continuum I/O System Reference

175

Page 180

AC-1 Plus Entering an Input String at a Keypad for Use in PE Programs From a keypad connected to an AC-1 Plus, you (the user) may also send additional data to a controller, which in turn passes it to a Plain English (PE) program for execution in an Andover Continuum control application. This capability enables you to use the keypad to send input to a PE program for any purpose. For example: • •

A user can enter a string that a PE program uses to turn lights or fans on or off, or to control other HVAC equipment. A user can enter a string indicating the user’s purpose for entering an area. The PE program can capture this information as input to a PE program for tracking reasons for activity in a secure area.

Handling String Input at the Controller Before you can use the keypad for PE program input, you must create a Plain English program that processes the string entered at the keypad and returns a value to the AC-1 Plus based on the entry. In addition, you must create the following objects in the controller: • •

An InfinityString object that stores the input from channel 7 of the AC-1 Plus and that your PE program reads to obtain the content of the string An InfinityOutput object that stores a numeric value specified in the PE program and sent to channel 4 of the AC-1 Plus (See “PE Feedback to the AC-1 Plus” later in this section.)

You can use Continuum Explorer in CyberStation to create the InfinityString and InfinityOutput objects in the controller.

Entering String Input from Keypad The process for entering string input at a keypad has the following steps: 1. The user presents a valid access card and/or PIN (if a PIN is required) to the door reader. 2. The controller for this reader accepts the user’s credentials, and the door unlocks. 3. Within three seconds of the door unlocking, the user enters two consecutive asterisks ( ** ) at the keypad to enter escape sequence mode. 176

Schneider Electric

Page 181

AC-1 Plus

4. The keypad LED flashes slowly to indicate that it is waiting for input. 5. The user enters a numeric string of up to 30 characters (not including the two asterisks), and then terminates the string with the pound sign (#). For example: **10# or **6986310# 6. The AC-1 Plus sends the string to the controller (and its PE program) via channel 7, the string input channel for Plain English. Entry Rules for String Input The following rules apply to using a keypad connected to the AC-1 Plus to enter string input: •

After the door unlocks, if more than 3 seconds elapse before the user enters two asterisks, the AC-1 Plus exits escape sequence mode. The user must begin the process for string input again.

•

If a user enters more than 30 characters (not including the first two asterisks), the AC-1 Plus detects when the 31st digit is entered. The AC-1 Plus then replaces the 30th character with T to indicate Tamper, and sends the string to the controller (no # is needed). Subsequent characters entered as part of the string are ignored. For example, if the user enters **123456789012345678901234567890123, the AC-1 Plus sends **12345678901234567890123456789T to the controller.

•

The user can enter asterisks within the string if needed. These asterisks are converted to periods when sent to the PE program. For example: 69*8*6310 is converted to 69.8.6310 when sent to the PE program.

•

If more than 4 seconds elapse between keystrokes, the AC-1 Plus exits escape sequence mode. The user must begin the process for string input again.

•

If a user presents an access card to the card reader while the AC-1 Plus is in escape sequence mode, the AC-1 Plus exits escape sequence mode. The user must begin the process for string input again.

Andover Continuum I/O System Reference

177

Page 182

AC-1 Plus

PE Feedback to the AC-1 Plus After the PE program receives the string input and interprets its value, the program assigns an appropriate value to the InfinityOutput object. One of the following values is transmitted back to the AC-1 Plus through channel 4: ƒ

1 – Clear string.

ƒ

2 – Recognize the escape sequence entry (success).

ƒ

3 – Do not recognize the escape sequence entry (fail).

NOTE: Clearing the string in the AC-1 Plus using the Clear String command is recommended after each string input in escape sequence mode. Based on the numeric value returned to the AC-1 Plus through channel 4, the AC-1 Plus also uses the reader LEDs to indicate to the user whether or not the string input is valid or invalid. The LED pattern to indicate valid/invalid entry is the same as the selected access control LED pattern used to indicate valid/invalid card and PIN entry.

178

Schneider Electric

Page 183

AC-1 Plus

Connecting a Reader/Keypad Reader/Keypad Inputs The AC-1 Plus includes a full interface to a single Wiegand, ABA or CardKey access card reader. The module is designed to allow Integral reader/keypad units to be connected directly. Separate keypads that have similar interfaces can be connected in parallel with a reader by using the auxiliary input connector as shown on the following page. The reader and/or reader/keypad unit is connected to the AC-1 Plus module as shown below: 5V

GND

+V

Reader or Reader with Keypad

GND

DATA / I

DATA I DATA 0 LED CLK / 0

LEDx

Andover Continuum I/O System Reference

179

Page 184

AC-1 Plus Connecting Two Readers or a Keypad and a Reader The AC-1 Plus can interface to both a keypad and a reader simultaneously. This assumes that they are both format compatible devices of similar voltage range. Similarly, two readers can be connected. This allows a site to slowly introduce a different type of reader (i.e., proximity) while allowing access through the normal reader. AC-1 Plus

1 5V

2 GND +V

Reader or Reader with Keypad or Keypad only

GND LED DATA 1 CLK 0 7 LED1

3 DATA / I 4 CLK / 0

5 DATA / I 6 CLK / 0

8 LED2

DATA 1

Reader or Reader with Keypad or Keypad only

180

Schneider Electric

CLK 0 LED GND +V

Page 185

AC-1 Plus Connecting a CardKey Reader You can connect a CardKey reader directly to the AC-1 Plus, however, the CardKey reader requires a +12VDC supply for the red and green lamps. The AC-1 Plus does not supply 12 VDC, therefore it is necessary to connect an external power supply to provide the necessary power for the lamps. Make sure the reader type switch is set to the CK34 position when using a CardKey reader.

Andover Continuum I/O System Reference

181

Page 186

AC-1 Plus Connecting Two Readers for a Dual Reader Door With the addition of another AC-1 Plus module, a door can be configured as a dual reader door. A door is a dual reader door when it has been configured with an entry and exit IOU module. A dual reader door is connected as shown below: AC-1 Plus Entry IOU

* Entry Reader

Supervised Input IN2

Termination

Supervised Input IN1

Termination

Door Switch

Reader

* Alarm Out

Out2

Out1

Door Strike AC-1 Plus Exit IOU

* Exit Reader

Supervised Input IN2

Termination

Supervised Input IN1

Termination

Reader

*

Out1

* TERMINATION Each input must be terminated using your chosen Supervised Input resistor arrangement. It is important that BOTH AC-1 Plus modules include termination where they share door switches and/or Bond sensors. For more information on input termination, refer to the section on Supervised Inputs.

182

Schneider Electric

Bond Sensor