Page 187
AC-1 Plus
Connecting Supervisory Inputs All AC-1 Plus inputs are supervisory inputs. The following drawings depict the three types of supervisory inputs that exist - two normally closed and one normally open type. NOTE: All resistor values are to be 10KΩ ± 5%.
Normally Closed Supervised Inputs NC Series With this type of input wiring, a resistor is placed in series with the input being monitored. When the input contact presents a short circuit (normal closed position) the input is assumed in a normal closed state, the circuit presents a reading of 10 KΩs at the input.
Circuit Action
Input Senses
Condition
Switch Closed Switch Opened Wire Cut Input Shorted
External Resistance Infinite Resistance Infinite Resistance Zero Ωs
Input contact Closed Input contact Open Input contact Open ‘Violation’ Violation or error
When the input contact is opened, the circuit opens and an infinite resistance is measured. If the wires to the input contact are cut it also appears as an “input contact open” condition. In this case there would be a input contact open without a valid card swipe or valid keypad entry resulting in an “input contact violation”. Shorting the input causes a zero Ω resistance, which also results in an input contact violation. When configuring for this type of contact select: ElecType: Resistor Type:
Supervised NCSeries
Andover Continuum I/O System Reference
183
Page 188
AC-1 Plus
Normally Closed Supervised Inputs NC Series Parallel With this type of input wiring, two external resistors are added to the input, one in series and the other in parallel. When the input contact switch is closed (normal position) the input contact is assumed to be closed. The circuit presents a reading composed of both resistances in parallel that works out to be half the value of one of them (5 KΩ).
Circuit Action
Input Senses
Condition
Switch Closed Switch Opened Wire Cut Input Shorted
External Resistance ÷ 2 External Resistance Infinite Resistance Zero Ωs
Input contact Closed Input contact Open Violation or error Violation or error
When the input contact is opened the switch opens and the value of the parallel resistor is measured. If the wires to the input contact are cut it appears as an infinite resistance. Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance (open) should result in an error condition. When configuring for this type of contact select: ElecType: Resistor Type:
184
Supervised NCSerPar
Schneider Electric
Page 189
AC-1 Plus Normally Open Supervised Inputs NO Series Parallel With this type of input wiring, two external resistors are added to the input, one in series and the other in parallel. When the input contact switch is open (normal position) the input contact is assumed to be closed. The circuit reads the value of the parallel resistor.
Circuit Action
Input Senses
Condition
Switch Closed Switch Opened Wire Cut Input Shorted
External Resistance ÷ 2 External Resistance Infinite Resistance Zero Ωs
Input contact Open Input contact Closed Violation or error Violation or error
When the input contact is opened the switch closes and a reading results that is composed of both resistances in parallel that works out to be half the value of one of them (5 KΩ). If the wires to the input contact are cut it appears as an infinite resistance. Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance (open) should result in an error condition. When configuring for this type of contact select: ElecType: Resistor Type:
Supervised NOSeriPar
Andover Continuum I/O System Reference
185
Page 190
AC-1 Plus Wiring Door Switches There are three supervisory inputs for door switches. The maximum length wire you may use is 500 ft of #18 gauge wire (152 m of 1.0 mm2 wire) or 200 ft of #22 gauge wire (60 m of 0.35 mm2 wire). Some switches have built-in resistors that facilitate Series Parallel connections as shown below: Switch with Built-In Resistor
AUX or DOOR or REX
10 KΩ
RET
Wiring Motion Detectors Motion detectors are devices that close a switch contact when motion is detected. Wiring is similar to a normal door switch input, however, the motion sensor requires an external power supply of 12 VDC or 24 VDC (UL listed under APHV). The maximum length wire you may use is 500 ft of #18 gauge wire (152 m of 1.0 mm2 wire) or 200 ft of #22 gauge wire (60 m of 0.35 mm2 wire). The following shown a typical motion detector circuit: AUX or DOOR or REX
No Motion Detected Normally Open PIR Motion Detector
10 KΩ
RET
AUX or DOOR or REX
Motion Detected
Normally Open PIR Motion Detector
10 KΩ
RET
186
Schneider Electric
Page 191
AC-1 Plus
Connecting Outputs The AC-1 Plus module includes two Form C single-pole double-throw relay outputs. The following is a simplified schematic of each output channel: OUT x NC
OUT x NO
OUT x COM
Both channels resemble the circuit shown above. To use the Form C output in your system, configure an output point with an Electrical Type of Digital. These output contacts operate as a standard relay. When the output is set to an “ON” state, the normally open contacts close and the normally closed contacts open. Note: When configuring a Digital point, there is a “‘Polarity” attribute. If this attribute is enabled, the operation of the outputs are reversed.
Override Controls The AC-1 Plus module includes an output override switch for each output. ON OFF AUTO
The output of the module can be directed from program control or manual control. The output can be disabled completely as well.
Andover Continuum I/O System Reference
187
Page 192
AC-1 Plus The following describes the actions associated with each position of the override controls: ON
The output relay is energized to an “ON” state manually by setting the switch to ON. Programs have no effect on the output when the switch is in this position.
OFF
The output relay is de-energized to an “OFF” state manually by setting the switch to OFF. Programs have no effect on the output when the switch is in this position.
AUTO
The action of the output relay is determined as a direct result of program control.
Wiring Door Outputs The following represents a typical door output installation when the circuit is normally open:
MOV (Andover #01-2020-095)
C Door Strike (UL listed burglary-resistant electric locking mechanism (CVXY))
12/24V Power Supply (UL listed power supply (APHV))
This configuration shows a normally de-energized lock (when secured) in a fail secure mode. If power loss occurs, the lock closes. Always be sure to use “panic” hardware that allows emergency exit from the secured area.
188
Schneider Electric
Page 193
AC-1 Plus
The following represents a typical door output installation when the circuit is normally closed: MOV (Andover #01-2020-095)
C Electromagnetic Door Lock (UL listed burglary-resistant electric locking mechanism (CVXY))
12/24V Power Supply (UL listed power supply (APHV))
This configuration shows a normally de-energized lock (when secured) in a fail safe mode. If power loss occurs, the lock opens.
Andover Continuum I/O System Reference
189
Page 194
AC-1 Plus Wiring Dual Reader Door Outputs The following represents a typical door output installation when the dual reader door circuit is controlling a fail-safe lock: Exit IOU
Entry IOU MOV (Andover #01-2020-095)
C Door Strike Fail-Safe Lock (UL listed Door burglary-resistant (Energize to lock) electric locking mechanism (CVXY)) UL-listed burglary-resistant Electric locking mechanism (CVXY)
12/24V Power Supply (UL listed power supply (APHV))
190
Schneider Electric
Page 195
AC-1 Plus The following represents a typical door output installation when the dual reader door circuit is controlling a fail-secure lock: Exit IOU
MOV (Andover #01-2020-095)
Entry IOU C Electromagnetic Door Lock Fail-Secure Door Lock (UL listed (Energize toburglary-resistant unlock) electric locking mechanism (CVXY)) UL-listed burglary-resistant Electric locking mechanism (CVXY)
12/24V Power Supply (UL listed power supply (APHV))
Andover Continuum I/O System Reference
191
Page 196
AC-1 Plus Status/Control Panel Status Indicators The AC-1 Plus module includes a complete indicator status panel on the front of the module.
This panel includes indicators reporting on the status of the following: POWER COMM
OVERRIDE STATUS
OUTPUT READER POWER
This green indicator illuminates when DC power is applied through the I/O Bus. This yellow indicator illuminates when data is transmitted from the module to the NetController. In normal operation, data is only transmitted when an input value changes. This indicator will also flash periodically as the NetController checks the I/O bus. This red indicator illuminates whenever any of the override switches is in a position other than AUTO. This red indicator is normally off. If it is always on or flashing at a fast rate, there is a problem with the module. This indicator can be manually illuminated from the CyberStation workstation or Command Terminal and used as a troubleshooting aid when locating a particular module. These red indicators (one for each channel) illuminate when an output relay is energized. This green indicator illuminates when +5VDC power is available to the reader.
This panel also includes two operator switches that perform the following: COMMISSION
RESET
192
After physical installation and during configuration through the CyberStation workstation or Command Terminal, pressing this button registers the module’s address with the system. For more information, refer to the section on Module Configuration found earlier in this manual. If the module becomes inoperable, pressing this button resets the module. It does not erase its memory.
Schneider Electric