Page 187

AC-1 Plus

Connecting Supervisory Inputs All AC-1 Plus inputs are supervisory inputs. The following drawings depict the three types of supervisory inputs that exist - two normally closed and one normally open type. NOTE: All resistor values are to be 10KΩ ± 5%.

Normally Closed Supervised Inputs NC Series With this type of input wiring, a resistor is placed in series with the input being monitored. When the input contact presents a short circuit (normal closed position) the input is assumed in a normal closed state, the circuit presents a reading of 10 KΩs at the input.

Circuit Action

Input Senses

Condition

Switch Closed Switch Opened Wire Cut Input Shorted

External Resistance Infinite Resistance Infinite Resistance Zero Ωs

Input contact Closed Input contact Open Input contact Open ‘Violation’ Violation or error

When the input contact is opened, the circuit opens and an infinite resistance is measured. If the wires to the input contact are cut it also appears as an “input contact open” condition. In this case there would be a input contact open without a valid card swipe or valid keypad entry resulting in an “input contact violation”. Shorting the input causes a zero Ω resistance, which also results in an input contact violation. When configuring for this type of contact select: ElecType: Resistor Type:

Supervised NCSeries

Andover Continuum I/O System Reference

183

Page 188

AC-1 Plus

Normally Closed Supervised Inputs NC Series Parallel With this type of input wiring, two external resistors are added to the input, one in series and the other in parallel. When the input contact switch is closed (normal position) the input contact is assumed to be closed. The circuit presents a reading composed of both resistances in parallel that works out to be half the value of one of them (5 KΩ).

Circuit Action

Input Senses

Condition

Switch Closed Switch Opened Wire Cut Input Shorted

External Resistance ÷ 2 External Resistance Infinite Resistance Zero Ωs

Input contact Closed Input contact Open Violation or error Violation or error

When the input contact is opened the switch opens and the value of the parallel resistor is measured. If the wires to the input contact are cut it appears as an infinite resistance. Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance (open) should result in an error condition. When configuring for this type of contact select: ElecType: Resistor Type:

184

Supervised NCSerPar

Schneider Electric

Page 189

AC-1 Plus Normally Open Supervised Inputs NO Series Parallel With this type of input wiring, two external resistors are added to the input, one in series and the other in parallel. When the input contact switch is open (normal position) the input contact is assumed to be closed. The circuit reads the value of the parallel resistor.

Circuit Action

Input Senses

Condition

Switch Closed Switch Opened Wire Cut Input Shorted

External Resistance ÷ 2 External Resistance Infinite Resistance Zero Ωs

Input contact Open Input contact Closed Violation or error Violation or error

When the input contact is opened the switch closes and a reading results that is composed of both resistances in parallel that works out to be half the value of one of them (5 KΩ). If the wires to the input contact are cut it appears as an infinite resistance. Shorting the input causes a zero Ω resistance. Both a short and an infinite resistance (open) should result in an error condition. When configuring for this type of contact select: ElecType: Resistor Type:

Supervised NOSeriPar

Andover Continuum I/O System Reference

185

Page 190

AC-1 Plus Wiring Door Switches There are three supervisory inputs for door switches. The maximum length wire you may use is 500 ft of #18 gauge wire (152 m of 1.0 mm2 wire) or 200 ft of #22 gauge wire (60 m of 0.35 mm2 wire). Some switches have built-in resistors that facilitate Series Parallel connections as shown below: Switch with Built-In Resistor

AUX or DOOR or REX

10 KΩ

RET

Wiring Motion Detectors Motion detectors are devices that close a switch contact when motion is detected. Wiring is similar to a normal door switch input, however, the motion sensor requires an external power supply of 12 VDC or 24 VDC (UL listed under APHV). The maximum length wire you may use is 500 ft of #18 gauge wire (152 m of 1.0 mm2 wire) or 200 ft of #22 gauge wire (60 m of 0.35 mm2 wire). The following shown a typical motion detector circuit: AUX or DOOR or REX

No Motion Detected Normally Open PIR Motion Detector

10 KΩ

RET

AUX or DOOR or REX

Motion Detected

Normally Open PIR Motion Detector

10 KΩ

RET

186

Schneider Electric

Page 191

AC-1 Plus

Connecting Outputs The AC-1 Plus module includes two Form C single-pole double-throw relay outputs. The following is a simplified schematic of each output channel: OUT x NC

OUT x NO

OUT x COM

Both channels resemble the circuit shown above. To use the Form C output in your system, configure an output point with an Electrical Type of Digital. These output contacts operate as a standard relay. When the output is set to an “ON” state, the normally open contacts close and the normally closed contacts open. Note: When configuring a Digital point, there is a “‘Polarity” attribute. If this attribute is enabled, the operation of the outputs are reversed.

Override Controls The AC-1 Plus module includes an output override switch for each output. ON OFF AUTO

The output of the module can be directed from program control or manual control. The output can be disabled completely as well.

Andover Continuum I/O System Reference

187

Page 192

AC-1 Plus The following describes the actions associated with each position of the override controls: ON

The output relay is energized to an “ON” state manually by setting the switch to ON. Programs have no effect on the output when the switch is in this position.

OFF

The output relay is de-energized to an “OFF” state manually by setting the switch to OFF. Programs have no effect on the output when the switch is in this position.

AUTO

The action of the output relay is determined as a direct result of program control.

Wiring Door Outputs The following represents a typical door output installation when the circuit is normally open:

MOV (Andover #01-2020-095)

C Door Strike (UL listed burglary-resistant electric locking mechanism (CVXY))

12/24V Power Supply (UL listed power supply (APHV))

This configuration shows a normally de-energized lock (when secured) in a fail secure mode. If power loss occurs, the lock closes. Always be sure to use “panic” hardware that allows emergency exit from the secured area.

188

Schneider Electric

Page 193

AC-1 Plus

The following represents a typical door output installation when the circuit is normally closed: MOV (Andover #01-2020-095)

C Electromagnetic Door Lock (UL listed burglary-resistant electric locking mechanism (CVXY))

12/24V Power Supply (UL listed power supply (APHV))

This configuration shows a normally de-energized lock (when secured) in a fail safe mode. If power loss occurs, the lock opens.

Andover Continuum I/O System Reference

189

Page 194

AC-1 Plus Wiring Dual Reader Door Outputs The following represents a typical door output installation when the dual reader door circuit is controlling a fail-safe lock: Exit IOU

Entry IOU MOV (Andover #01-2020-095)

C Door Strike Fail-Safe Lock (UL listed Door burglary-resistant (Energize to lock) electric locking mechanism (CVXY)) UL-listed burglary-resistant Electric locking mechanism (CVXY)

12/24V Power Supply (UL listed power supply (APHV))

190

Schneider Electric

Page 195

AC-1 Plus The following represents a typical door output installation when the dual reader door circuit is controlling a fail-secure lock: Exit IOU

MOV (Andover #01-2020-095)

Entry IOU C Electromagnetic Door Lock Fail-Secure Door Lock (UL listed (Energize toburglary-resistant unlock) electric locking mechanism (CVXY)) UL-listed burglary-resistant Electric locking mechanism (CVXY)

12/24V Power Supply (UL listed power supply (APHV))

Andover Continuum I/O System Reference

191

Page 196

AC-1 Plus Status/Control Panel Status Indicators The AC-1 Plus module includes a complete indicator status panel on the front of the module.

This panel includes indicators reporting on the status of the following: POWER COMM

OVERRIDE STATUS

OUTPUT READER POWER

This green indicator illuminates when DC power is applied through the I/O Bus. This yellow indicator illuminates when data is transmitted from the module to the NetController. In normal operation, data is only transmitted when an input value changes. This indicator will also flash periodically as the NetController checks the I/O bus. This red indicator illuminates whenever any of the override switches is in a position other than AUTO. This red indicator is normally off. If it is always on or flashing at a fast rate, there is a problem with the module. This indicator can be manually illuminated from the CyberStation workstation or Command Terminal and used as a troubleshooting aid when locating a particular module. These red indicators (one for each channel) illuminate when an output relay is energized. This green indicator illuminates when +5VDC power is available to the reader.

This panel also includes two operator switches that perform the following: COMMISSION

RESET

192

After physical installation and during configuration through the CyberStation workstation or Command Terminal, pressing this button registers the module’s address with the system. For more information, refer to the section on Module Configuration found earlier in this manual. If the module becomes inoperable, pressing this button resets the module. It does not erase its memory.

Schneider Electric