Andover Continuum I/O System Reference: Mixed Modules, pages 197 to 206

Pages 197 to 206 of 222, from Andover Continuum I/O System Reference

The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Andover Controls AC-1, Andover Controls DO-4, Andover Controls UI-8 and Schneider UI-8

Page 197

VS-8-4

VS-8-4, VS-8-4-T Video Switcher The VS-8-4, Andover Continuum’s video switcher module, includes eight input channels and four high-speed, buffered, output channels. Any one of the eight input lines can be connected to any of the four outputs. Each output has a gain of two and is capable of driving 75 Ω, back-terminated, lines. The VS-8-4 is an I/O module used with the Andover Continuum Product line and can be integrated into systems requiring video security. Up to eight surveillance, cameras can be connected to the VS-8-4 inputs. The VS-8-4 video output can then be connected directly to a video monitor or other video display or recording device. The VS-8-4-T version provides the capability of time/date stamping the video signal. In addition, a title may be added to the video signal to identify the area where the camera is being directed.

FEATURES •

Eight (8) Video inputs

•

Four (4) Video outputs

•

Any one input can be connected to any of the four outputs

•

10–28 V Power Supply Range

Andover Continuum I/O System Reference

193

Page 198

VS-8-4 SPECIFICATIONS ELECTRICAL Power Supply Range:

Input Voltage Range: 10-28V. 24V for UL294 installations.

Power Consumption:

2 Watts (83 mA) @ 24 VDC (max.); provided by Andover Continuum power supply module.

Overload Protection:

0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection.

INPUTS Impedence:

75 Ω

Connection:

BNC connector

Bandwidth (-3dB):

> 75 MHz (Rload=150 Ω)

Single Channel Crosstalk:

> -60 dB @ 10 MHz.

All Channel Crosstalk:

> -50 dB @ 10 MHz.

All Channel Off Isolution:

> -55 dB @ 10 MHz.

OUTPUTS

194

Impedence:

75 Ω

Connection:

BNC connector

Signal:

2V pk/pk

Schneider Electric

Page 199

VS-8-4

I/O Connections The video input and output connections are located on the bottom of the module. A quick disconnect spade lug connector allows for an Earth ground connection. The diagram below indicates where each input and output is located on the module. These connections are also listed below.

VIDEO OUTPUTS Earth Ground

1

1

2

2

3

3

4

5

4

6

7

8

VIDEO INPUTS

Standard BNC connections are used for each input and output.

Andover Continuum I/O System Reference

195

Page 200

VS-8-4 Programming/Use Video Switching The outputs of the VS-8-4 module can have up to eight input sources. These outputs are represented as Numerics in the system. Entering a value of 1–8 selects the input source for the particular output. Values other than 1–8 turn off the video for that output. Refer to the programming table on the following page for specifics. Configure each video output point with an Electrical Type of Numeric. Title & DateTime Programming (VS-8-4-T Only) The VS-8-4-T version of the switch provides the capability of superimposing the time/date and a textual title over the video signal of each output. The video area is divided into twelve “lines” where this information can be displayed. Line one is at the top of the screen, line twelve is at the bottom. The position of the date and time for all outputs is specified as a line numbered 1 though 12. Values other than 1–12 turn off the display of the datetime. The VS-8-4-T updates the Date and Time automatically, however, it is only accurate to 1.5 seconds per hour. You can send updated datetime readings to the unit though Plain English. Titles consist of one line composed up to 24 characters. Receiving more than 24 displays only the first 24 received. Text consists of white characters of 12 (horizontally) by 18 (vertical) dots (pixels). The character set supported includes all Alphanumeric (upper and lower case A–Z, 0–9) characters plus the following punctuation symbols: , ; < . > / ? : The display position of the title text is specified as a line numbered 1 though 12. Values other than 1–12 turn off the display of the title. Refer to the programming table on the following page for specifics.

196

Schneider Electric

Page 201

VS-8-4 VS-8-4-T Configuration Programming Table Function

Channel

Object

Video Select Output 1

1

Numeric

Direction

Values

IOOutput

1–8 ; corresponding to input channel number.

Type

Other values turn off this output. Video Select Output 2

2

Numeric

IOOutput

1–8 ; corresponding to input channel number. Other values turn off this output.

Video Select Output 3

3

Numeric

IOOutput

1–8 ; corresponding to input channel number. Other values turn off this output.

Video Select Output 4

4

Numeric

IOOutput

1–8 ; corresponding to input channel number. Other values turn off this output.

Date/Time Position (All four outputs)

5

Numeric

IOOutput

1–12 ; corresponding to display line number. Other values turn off the display of datetime.

Title Position (All four outputs)

6

Numeric

IOOutput

1–12 ; corresponding to display line number. Other values turn off the display of the title.

Set Datetime

7

DateTime

IOOutput

Used to send Datetime to VS-8. See text.

Title Text Input Source 1

8

String

IOOutput

Up to 24 characters

Title Text Input Source 2

9

String

IOOutput

Up to 24 characters

Title Text Input Source 3

10

String

IOOutput

Up to 24 characters

Title Text Input Source 4

11

String

IOOutput

Up to 24 characters

Title Text Input Source 5

12

String

IOOutput

Up to 24 characters

Title Text Input Source 6

13

String

IOOutput

Up to 24 characters

Title Text Input Source 7

14

String

IOOutput

Up to 24 characters

Title Text Input Source 8

15

String

IOOutput

Up to 24 characters

Andover Continuum I/O System Reference

197

Page 202

VS-8-4

Status/Control Panel Status Indicators The VS-8-4 module includes a complete indicator status panel on the front of the module.

This panel includes indicators reporting on the status of the following: POWER

This green indicator illuminates when DC power is applied through the I/O Bus.

COMM

This yellow indicator illuminates when data is transmitted from the module to the NetController. In normal operation, data is only transmitted when an input value changes. This indicator will also flash periodically as the NetController checks the I/O bus.

STATUS

This red indicator is normally off. If it is always on or flashing at a fast rate, there is a problem with the module. This indicator can be manually illuminated from the CyberStation workstation or Command Terminal and used as a troubleshooting aid when locating a particular module.

INPUTx

Each input includes four red indicators (one for each output channel). Illumination indicates a connection between input and output.

This panel also includes two operator switches that perform the following: COMMISSION

After physical installation and during configuration through the CyberStation workstation or Command Terminal, pressing this button registers the module’s address with the system. For more information, refer to the section on Module Configuration found earlier in this manual.

RESET

If the module becomes inoperable, pressing this button resets the module. It does not erase its memory.

198

Schneider Electric

Page 203

VT-1 VT-1 Voice Telecom Module The VT-1, Andover Continuum’s voice-output/touch-tone input telecom module, provides users with easy-to-use remote data entry capabilities for their Andover Continuum system using the familiar touch-tone keypad on any standard or cellular telephone. The VT-1 provides built-in prompt messages and pre-recorded vocabulary words, which can be used individually or combined to form phrases and sentences. In addition, custom messages (up to 3 minutes total) can be pre-recorded to inform the user of building conditions and/or to prompt the user for additional input.

FEATURES •

Provides a Telephone Command Interface to Andover Continuum

•

Accepts DTMF menu selection

•

Standard RJ-11 Telephone Interface

•

Recording via Telephone

•

Dial Out and Call Progress Capability

Andover Continuum I/O System Reference

199

Page 204

VT-1 SPECIFICATIONS ELECTRICAL Power Supply Range:

Input Voltage Range: 20-26V.

Power Consumption:

1.5 Watts (63 mA) @ 24 VDC (max.); provided by Andover Continuum power supply module.

Overload Protection:

0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection.

INPUTS

200

Interface:

Local Telephone System Interface

Connection:

RJ-11 connector

Schneider Electric

Page 205

VT-1 Telephone Line Connection The VT-1 connects to the local telephone line via an internal RJ-11 jack.

To install the telephone line, open the cover of the module and plug an RJ-11 cable into the jack located at the lower left as indicated below.

Connect the other end of the cable to a local telephone jack.

Andover Continuum I/O System Reference

201

Page 206

VT-1

Programming/Use Technical Description The VT-1 module acts as an interface to the Andover Continuum system by allowing a user to control functions via telephone. It can be configured to operate like an auto attendant for a telephone system. As the phone line is answered, a series of voice prompts are played indicating various options that may be selected by pressing touch tone (DTMF) keys on the caller’s telephone. The DTMF numbers received by the module represent a desired command or function. The module is equipped to decode the DTMF responses and send them off to an attending controller. The module can also be commanded to dial out and provide callback numbers to a paging system. The VT-1 operates in either of two modes: Supervisor Mode Supervisor Mode provides a method for recording the messages that may be played back at a later time. These messages may be application specific phrases that the controller can select for communicating with the user. It is these messages that are played to inform the caller of the various control options available. User Mode User mode is the normal operating mode of the VT-1. In this mode, the VT-1 is under the control of a Plain English program. When a user calls into the module, messages are played and touch-tone digits are captured.

202

Schneider Electric