An Andover Controls data sheet for the Continuum intelligent building system I/O modules. It lists the specifications all modules share (environment, size, weight, mounting, RS-485 and FTT-10A communications, agency listings) and an outline drawing, then gives a page of specifications for each module: UI-8-10 universal input, DI-8, DI-6-AC, MI-6, AO-4-8, DO-6-TR, DO-4-R, DM-20, the AC-1 access control family, LO-2, VS-8-4 and VT-1.
Its parts
- Overview
- Specifications
- Modules
From the sheet
Key facts from this sheet
Each line names its page in the PDF.
An Andover Controls specification sheet for the Continuum I/O modules, the DIN rail modules of the Continuum building control system. It gives the specifications all modules share, then one page per module, including the UI-8-10 universal input module (and UI-8-10-10V), the DI-8, the DO-4-R relay output module (and DO-4-R-O) and others such as the DI-6-AC, MI-6, AO-4-8, DO-6-TR, DM-20, AC-1 family, LO-2, VS-8-4 and VT-1.
- System
- DIN rail I/O module for the Andover Continuum building control system, linked to the Continuum NetController CPU module p. 1
- Network media
- RS-485 (39k baud, 2,000 ft) or FTT-10A (78k baud, up to 8858 ft in bus topology), chosen per module p. 2
- Operating environment
- 32 to 120°F (0 to 49°C), 10 to 95% RH non-condensing p. 2
- Size
- 3.8 in W (with connectors) x 6.2 in H (clips closed, 7.2 in extended) x 2.5 in D p. 2
- Weight
- .75 lbs (0.34 kg) p. 2
- Mounting
- DIN rail or wall mount with the attached clips; optional NEMA 1-style Continuum enclosure p. 2
- Module connections
- 5-position plug-in power/communication connectors on both sides; two-piece 13-position removable field terminal block p. 2, 4
- UI-8-10 inputs
- 8 universal inputs, 10-bit, each set in software as voltage, thermistor, digital, counter or supervised p. 4
- UI-8-10 ranges
- 0-5 V on the UI-8-10; 0-10 V on the UI-8-10-10V, set by a DIP switch per input p. 4
- UI-8-10 thermistor
- 10 KΩ Type III thermistor, -30 to 230°F (-34 to 110°C) p. 4
- UI-8-10 power
- 0.7 W at 10-28 VDC max; 0.5 A resettable fuse with reverse polarity protection p. 4
- DO-4-R outputs
- 4 Form C relay outputs, 5 A at 240 VAC or 5 A at 30 VDC; 2.8 W module power p. 10
- DO-4-R control
- On/off or pulse-width modulation at 0.1 second resolution; two outputs can form a tri-state output p. 10
- DO-4-R-O overrides
- Hand-off-auto switch on each output with override feedback and status LED p. 10
What this sheet walks you through
- Mounting modules remotely with approved cable p. 1
- Choosing RS-485 or FTT-10A media and topology p. 1, 2
- Configuring UI-8-10 inputs as supervised security points p. 4
- Setting the UI-8-10-10V voltage divider DIP switches p. 4
- Enabling DI-8 high-speed counting on channels 1 and 2 p. 5
- Pairing DO-4-R relays as a tri-state output p. 10
- Module dimension drawings p. 3
Good to know
- RS-485 and FTT-10A modules cannot be mixed on the same I/O bus. p. 1
- Remotely mounted RS-485 modules need 120 ohm termination at both ends of the network. p. 2
- FTT-10A runs beyond the stated bus lengths need a repeater. p. 2
- Any single UI-8-10 input tolerates 24 V AC/DC. p. 4
- UI-8-10 digital and counter inputs take contact closures at up to 4 Hz. p. 4
Questions this sheet answers
What inputs does the UI-8 accept?
The UI-8-10 has 8 universal inputs, each set in software as voltage (0-5 V), 10 KΩ Type III thermistor, digital, counter or supervised. p. 4
Is there a 0-10 V version of the UI-8?
Yes, the UI-8-10-10V, with a voltage divider DIP switch on each input. p. 4
What can the DO-4 relays switch?
The DO-4-R has four Form C relays rated 5 A at 240 VAC or 5 A at 30 VDC. p. 10
How do Continuum I/O modules connect to the controller?
They slide together on side connectors and talk to the NetController CPU over ACC-LON, on RS-485 or FTT-10A. p. 1, 2
What is the operating temperature of Continuum I/O modules?
32 to 120°F (0 to 49°C) at 10 to 95% RH, non-condensing. p. 2