Page 1 of Continuum I/O Modules

Spec sheet · Andover Controls

Continuum I/O Modules

Spec sheet22 pagesPDF 388 KB

Data sheet for the Andover Controls Continuum I/O modules, including the UI-8-10 universal input and DO-4-R relay output modules.

Download the PDF388 KB

Covers · 3 models

The models it covers

Summary

What is in it

An Andover Controls data sheet for the Continuum intelligent building system I/O modules. It lists the specifications all modules share (environment, size, weight, mounting, RS-485 and FTT-10A communications, agency listings) and an outline drawing, then gives a page of specifications for each module: UI-8-10 universal input, DI-8, DI-6-AC, MI-6, AO-4-8, DO-6-TR, DO-4-R, DM-20, the AC-1 access control family, LO-2, VS-8-4 and VT-1.

Its parts

  1. Overview
  2. Specifications
  3. Modules

From the sheet

Key facts from this sheet

Each line names its page in the PDF.

An Andover Controls specification sheet for the Continuum I/O modules, the DIN rail modules of the Continuum building control system. It gives the specifications all modules share, then one page per module, including the UI-8-10 universal input module (and UI-8-10-10V), the DI-8, the DO-4-R relay output module (and DO-4-R-O) and others such as the DI-6-AC, MI-6, AO-4-8, DO-6-TR, DM-20, AC-1 family, LO-2, VS-8-4 and VT-1.

Read for this summary: pages 1 to 5 and 10 of 22.

System
DIN rail I/O module for the Andover Continuum building control system, linked to the Continuum NetController CPU module p. 1
Network media
RS-485 (39k baud, 2,000 ft) or FTT-10A (78k baud, up to 8858 ft in bus topology), chosen per module p. 2
Operating environment
32 to 120°F (0 to 49°C), 10 to 95% RH non-condensing p. 2
Size
3.8 in W (with connectors) x 6.2 in H (clips closed, 7.2 in extended) x 2.5 in D p. 2
Weight
.75 lbs (0.34 kg) p. 2
Mounting
DIN rail or wall mount with the attached clips; optional NEMA 1-style Continuum enclosure p. 2
Module connections
5-position plug-in power/communication connectors on both sides; two-piece 13-position removable field terminal block p. 2, 4
UI-8-10 inputs
8 universal inputs, 10-bit, each set in software as voltage, thermistor, digital, counter or supervised p. 4
UI-8-10 ranges
0-5 V on the UI-8-10; 0-10 V on the UI-8-10-10V, set by a DIP switch per input p. 4
UI-8-10 thermistor
10 KΩ Type III thermistor, -30 to 230°F (-34 to 110°C) p. 4
UI-8-10 power
0.7 W at 10-28 VDC max; 0.5 A resettable fuse with reverse polarity protection p. 4
DO-4-R outputs
4 Form C relay outputs, 5 A at 240 VAC or 5 A at 30 VDC; 2.8 W module power p. 10
DO-4-R control
On/off or pulse-width modulation at 0.1 second resolution; two outputs can form a tri-state output p. 10
DO-4-R-O overrides
Hand-off-auto switch on each output with override feedback and status LED p. 10

What this sheet walks you through

  • Mounting modules remotely with approved cable p. 1
  • Choosing RS-485 or FTT-10A media and topology p. 1, 2
  • Configuring UI-8-10 inputs as supervised security points p. 4
  • Setting the UI-8-10-10V voltage divider DIP switches p. 4
  • Enabling DI-8 high-speed counting on channels 1 and 2 p. 5
  • Pairing DO-4-R relays as a tri-state output p. 10
  • Module dimension drawings p. 3

Good to know

  • RS-485 and FTT-10A modules cannot be mixed on the same I/O bus. p. 1
  • Remotely mounted RS-485 modules need 120 ohm termination at both ends of the network. p. 2
  • FTT-10A runs beyond the stated bus lengths need a repeater. p. 2
  • Any single UI-8-10 input tolerates 24 V AC/DC. p. 4
  • UI-8-10 digital and counter inputs take contact closures at up to 4 Hz. p. 4

Questions this sheet answers

What inputs does the UI-8 accept?

The UI-8-10 has 8 universal inputs, each set in software as voltage (0-5 V), 10 KΩ Type III thermistor, digital, counter or supervised. p. 4

Is there a 0-10 V version of the UI-8?

Yes, the UI-8-10-10V, with a voltage divider DIP switch on each input. p. 4

What can the DO-4 relays switch?

The DO-4-R has four Form C relays rated 5 A at 240 VAC or 5 A at 30 VDC. p. 10

How do Continuum I/O modules connect to the controller?

They slide together on side connectors and talk to the NetController CPU over ACC-LON, on RS-485 or FTT-10A. p. 1, 2

What is the operating temperature of Continuum I/O modules?

32 to 120°F (0 to 49°C) at 10 to 95% RH, non-condensing. p. 2

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Overview1
  2. Specifications2
    1. Outline Drawing3
  3. Modules4
    1. UI-8-104
    2. DI-85
    3. DI-6-AC6
    4. MI-67
    5. AO-4-88
    6. DO-6-TR9
    7. DO-4-R10
    8. DM-2011
    9. AC-1Family12
    10. LO-218
    11. VS-8-420
    12. VT-121

From the PDF’s own bookmarks.

The whole text · 3 parts

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 31-3
  2. Modules, pages 4 to 134-13
  3. Modules, pages 14 to 2214-22

The file

Revision and size

Revision#DS-C-I/O MODULE-F, copyright 2002
PublisherAndover Controls Corporation
Pages22
PDF388 KB
TextText from the PDF itself.

The first pages · 4 of 22

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 22
Page 2
Page 2of 22
Page 3
Page 3of 22
Page 4
Page 4of 22