Page 14
AC-1A
I/O MODULE
The AC-1A provides full I/O for an access controlled door or portal in one compact module. The AC-1A can be located near an access controlled door for localized control and reduced wiring costs; or several AC-1A modules can be grouped together and DIN rail-mounted for centralized control. The AC-1A provides a Wiegand card input for Wiegand swipe and proximity type cards, reading up to 64 bits per card. Reader power is 50 mA at 5V. The module itself can be powered by a voltage source that can range from 10-28 VDC. The AC-1A has two 5 A, Form C relays, one for the door lock and a second for local alarm annunciation. Each output has an integral hand-off-auto switch for manual operation, and software feedback of the switch position. Up to three supervised alarm inputs can be used for door status contacts, request-to-exit devices, a cabinet tamper switch, or any other two-state or three-state (on/off/trouble) alarm device.
KEYPAD CONTROL
The AC-1A supports Wiegand output keypads. To simplify installation and reduce wiring costs, a combination Wiegand output reader/keypad may be used. In this case, the keypad data comes into the module via the reader data lines. In addition, the AC-1A allows separate wiring of both a Wiegand output keypad and reader.
ACCESS CONTROL
During normal operation of the AC-1A, access decisions are made in the Continuum NetController CPU , which provides storage for up to 75,000 “local” personnel records. In addition, the NetController’s event buffer is software-configurable to allow for the most optimized memory usage. If network communications are interrupted, the AC-1A will revert to a programmable degrade mode of operation, providing uninterrupted card access using site codes and other degrade mode parameters stored in nonvolatile EEPROM in each AC-1A module. A door can be configured to operate based on site code only, site code plus card, card plus personal ID number (PIN), or keypad only. The door’s operating mode can even be changed based on time-of-day or other events for optimum flexibility through Andover Controls’ easy-to-use Plain English® programming language. Each keypad can also permit entry of a duress alarm code that can initiate an alarm sequence at any AC-1A controller or at the Continuum workstation. Time-based anti-passback and entry/egress anti-passback are available to prevent tailgating. Entry/egress anti-passback is system-wide and can be performed by readers located on different AC-1A controllers across the network. Using Plain English, the AC-1A can also be used for custom access control sequences such as two-man rule, optical turnstile control, and man trap configurations. SPECIFICATIONS ELECTRICAL
Power Consumption:
2.0 W at 10-28VDC plus reader power consumption.
Overload Protection:
0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection
INPUTS/OUTPUTS
Inputs
14
Card Readers:
1
Card Reader Type:
Supports Wiegand swipe and proximity readers
Maximum Number of bits/Card:
64
Page 15
AC-1A I/O MODULE CONTINUED
Card Reader Power:
5 VDC, ± 3%, 50 mA, Current Limited
Distance, Card Reader to AC-1A:
500 ft. max. using 18-ga. wire 200 ft. max. using 22-ga. wire
Alarm Inputs:
Up to 3 supervised inputs. Single or double resistor supervision, series or parallel.
Input Protection:
Transient voltage suppressor (TVS) on each input
Outputs Door Outputs:
2 Form C relays
Output Rating:
5 A @ 24 V AC/DC
Output Protection:
5,000 V isolation 270 V metal oxide varistors (MOVs) on each output
Overrides:
3-position manual override switch on each output for manual control of relay. LED override status indicator.
Override Feedback:
Override detection and software feedback provided for each output.
Reader LED Output:
Open collector; up to 100 mA.
Inputs/Output Connections:
Two-piece, 18-position removable terminal block
USER LEDS/SWITCHES
Status Indicator LEDS Power Comm Override Status Out1 - Out2 +5 V Reader Power Switches Commission Reset
15
Power Indicator TD Indicator Common Override Indicator Service/Wink Indicator Two Output Status Indicators 5 V Reader Power Indicator
Page 16
AC-1Plus I/O MODULE
The AC-1Plus, Continuum’s full-feature access control module, provides full I/O for an access controlled door or portal in one compact module. The AC-1Plus supports multiple card formats, ADA (Alternate Door Access) doors, and multiple reader LED patterns. In addition, built-in reader supervision is provided - one LED will periodically check for voltage, absence of voltage, or shorts, and expose any of these conditions to the user for security purposes.The AC-1Plus can be located near an access controlled door for localized control and reduced wiring costs; or several AC-1Plus modules can be grouped together and DIN railmounted for centralized control. The AC-1Plus provides a Wiegand card input for Wiegand swipe and proximity type cards, reading up to 64 bits per card. The AC1Plus also supports CardKey cards, reading up to 34 bits per card, and ABA card readers. Card reader power is 50 mA at 5V . The AC-1Plus has two 5 A, Form C relays, one for the door lock and an auxiliary output for local alarm annunciation, for example. Each output has an integral hand-off-auto switch and software feedback of the switch position. The AC-1Plus provides five supervised input channels, configurable as an exit request, door switch sensor, ADA exit request, bond sensor, or as a general purpose supervised input point.
KEYPAD CONTROL
The AC-1Plus supports Wiegand or ABA output keypads. To simplify installation and reduce wiring costs, a combination Wiegand (or ABA) output reader/keypad may be used. In this case, the keypad data comes into the module via the reader data lines. In addition, the AC-1Plus allows separate wiring of both a Wiegand (or ABA) output keypad and reader.
ACCESS CONTROL
During normal operation of the AC-1Plus, access decisions are made in the Continuum NetController CPU, which provides storage for up to 75,000 “local” personnel records. In addition, the NetController’s event buffer is software-configurable to allow for the most optimized memory usage. If network communications are interrupted, the AC-1Plus will revert to a programmable degrade mode of operation, providing uninterrupted card access using site codes, card formats, and other degrade mode parameters stored in non-volatile EEPROM such as multiple card types (including custom format) and four site codes per each card type. ADA doors are also supported in degrade mode. A door can be configured to operate based on site code only, site code plus card, card only, card plus personal ID number (PIN), or keypad only. The door’s operating mode can even be changed based on time-of-day or other events for optimum flexibility through Andover Controls’ easy-to-use Plain English® programming language. Each keypad can also permit entry of a duress alarm code that can initiate an alarm sequence at any AC-1Plus controller or at the Continuum workstation. Time-based anti-passback and entry/egress anti-passback are available to prevent tailgating. Entry/egress anti-passback is system-wide and can be performed by readers located on different AC-1Plus controllers across the network. Using Plain English, the AC-1Plus can also be used for custom access control sequences such as two-man rule, optical turnstile control, and man trap configurations.
16
Page 17
AC-1PLUS I/O MODULE CONTINUED
SPECIFICATIONS
ELECTRICAL
Power Consumption:
2.2 W at 10-28VDC plus reader power consumption.
Overload Protection:
0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection
INPUTS/OUTPUTS
Inputs Card Readers:
1
Card Reader Type:
Supports Wiegand, Proximity, CardKey, and ABA readers
Maximum Number of bits/Card:
64 for Wiegand and Proximity; 34 for CardKey
Card Reader Power:
5 VDC, ± 3%, 50 mA, Current Limited
Distance, Card Reader to AC-1Plus:
500 ft. max. using 18-ga. wire 200 ft. max. using 22-ga. wire
Alarm Inputs:
5 supervised inputs. Single or double resistor supervision, series or parallel.
Input Protection:
Transient voltage suppressor (TVS) on each input
Outputs Door Outputs:
2 Form C relays
Output Rating:
5 A @ 24 V AC/DC
Output Protection:
5,000 V isolation 270 V metal oxide varistors (MOVs) on each output
Overrides:
3-position manual override switch on each output. LED override status indicator.
Override Feedback:
Override detection and software feedback provided for each output.
Reader LED Outputs:
2 open collector; up to 100 mA. Choice of 3 LED patterns
Inputs/Output Connections:
Removable terminal blocks: (2) 8-position; (1) 6-position
USER LEDS/SWITCHES
Status Indicator LEDS Power Comm Override Status Out1 - Out2 +5 V Reader Power Switches Commission Reset
17
Power Indicator TD Indicator Common Override Indicator Service/Wink Indicator Two Output Status Indicators 5 V Reader Power Indicator
Page 18
LO-2
I/O MODULE
The LO-2, Continuum’s lighting control module, can control 2 high voltage lighting circuits, using externally mounted GE RR7 or RR9 lighting relays, rated for 20 A @ 277 VAC (347 VAC option for Canada). These relays are connected to the LO-2 via two three foot, 5-conductor wires provided. The RR9 relay provides status feedback of the relay position, using a built-in pilot contact. The RR7 relay provides control of the circuit with no feedback. An on-board status LED for each output is provided when RR9 relays are used, as well as pilot light voltage for wall switches that have status indication. External 28 VAC is required to power the GE relays. This same transformer can power the LO-2 when the module is located remotely. An LO-2-O model, with on-board momentary override toggle switches, is also available.
EXTERNAL OVERRIDE CAPABILITIES
Two Class II low voltage manual override inputs, one for each relay output, are provided for override capabilities. These inputs directly control the lighting relays, independent of any schedule or program. Wall switches, occupancy sensors, or a combination of both may be wired to these inputs.
LIGHTING CONTROL
The LO-2 can be coupled with Continuum’s programmable input modules to provide flexible lighting control strategies such as: • Outdoor Lighting Control with a Photocell • Daylight Control • After-Hours Lighting Usage with Card Swipe Readers • Adjustable Override Time with Flick Warning • Cleaning Crew Override • Data Logging and Reporting • Run time Analysis, including Accumulated On-Time and Percentage On-Time • Tenant Billing Reports • Custom Control Strategies These programs can be easily modified to fit the exact needs of your project. SPECIFICATIONS ELECTRICAL
Power Consumption:
0.4 W @ 24 VDC max. Consumes no DC power when external AC power is present.
External AC Power:
28 VAC powers both module and lighting relays; can also power the LO-2 module when mounted remotely.
External Transformer:
40 VA transformer provides power for up to 5 LO-2 modules (10 GE relays and associated devices).
Overload Protection:
DC: 0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection. AC: 0.5 A resettable fuse with MOV.
INPUTS/OUTPUTS
18
Inputs:
2 Class II Low Voltage override inputs, providing direct control of lighting relays
Input Protection:
Transient voltage suppressors (TVS) with reverse polarity protection
Page 19
LO-2 I/O MODULE CONTINUED
Outputs Output Type:
2 pulsed lighting control outputs compatible with externally mounted GE RR7 or RR9 relays
Output Rating(Lighting Relay): Lamp Load – 20 A Tungsten Filament @125 VAC Resistive Load – 20 A ballast @ 277 VAC (@347 VAC, Canada) Motor Load – 0.5 HP @ 110-125 VAC 0.5 HP @ 220-277 VAC (0.5 HP @ 347 VAC, Canada) Pilot Contact Rating (RR9 only): 1 A @ 24 VAC, isolated Output Feedback:
RR9 relays have LED status indication and software feedback for relay status
Output Protection:
Transient voltage suppressors (TVS) on outputs. GE relays provide isolation.
Overrides:
Momentary override toggle switches (LO-2-O model only)
AC Power/External Override Input Connections: Lighting Relay Connections:
Two-piece, 12-position removable terminal block
5-position male connector accepts standard GE female plug-in connector. (Two 3-foot, 5-conductor wires with female connectors provided. Wires color-coded to match GE relays.)
USER LEDS/SWITCHES
Status Indicator LEDS Power Comm Status Out1-Out2 24 VAC
Power Indicator TD Indicator Service/Wink Indicator Two Output Status Indicators (RR-9 only) External 24-30 VAC Indicator
Switches Commission Reset MODELS
19
LO-2
2 pulsed lighting control outputs
LO-2-O
2 pulsed lighting control outputs with overrides
Page 20
VS-8-4
I/O MODULE
The VS-8-4 , Continuum’s video switch module, integrates low-cost, high quality video security directly into your Continuum system. The VS-8-4 switches eight video signal inputs and four high-speed, buffered outputs. Any one of the eight input lines can be connected to any of the four outputs. Each output has a voltage gain of two and is capable of driving 75Ω backterminated lines. Up to eight surveillance cameras and four video monitors or VCRs can be connected to a single VS-8-4 module. The VS-8-4 can be ordered with optional date/time and caption display. Captions are selectable, allowing different displays based on events or alarms. Both models can be ordered to support either the PAL or NTSC standard. SPECIFICATIONS ELECTRICAL
Power Consumption:
2 W @ 10-28VDC max.
Overload Protection:
0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection.
INPUTS/OUTPUTS
Inputs:
8 Video inputs
Input Impedence:
75Ω
Bandwidth (-3dB):
>75MHz (Rload=150Ω)
Single Channel Crosstalk:
>-60dB@10MHz
All Channel Crosstalk:
>-55dB@10MHz
All Channel Off Isolution:
>-55dB@10MHz
Outputs:
4 Video outputs
Output Impedence:
75Ω
Signal:
1 V peak-peak when terminated into 75Ω
Input/Output Connections:
75Ω BNC connectors
Input/Output Protection:
ESD protection provided
USER LEDS/SWITCHES
Status Indicator LEDS Power Comm Status Input Status 1-8 Switches
Power Indicator TD Indicator Service/Wink Indicator Input Status Indicator ( 4 LEDs per input)
Commission Reset
MODELS
20
VS-8-4
8 Video inputs; 4 Video outputs, NTSC or PAL video inputs
VS-8-4-TN
8 Video inputs; 4 Video outputs with date/time- and text-stamping for NTSC video inputs
VS-8-4-TP
8 Video inputs; 4 Video outputs with date/time- and text-stamping for PAL video inputs
Page 21
VT-1
MODULE
The Continuum VT-1 Interactive Voice Response (IVR) module provides users with easy-to-use remote data entry capabilities for their Continuum system using the familiar touch-tone keypad on any North American standard or cellular telephone. The VT-1 also allows spoken messages to be pre-recorded to inform the user of current system conditions and/or to prompt the user for additional input. The VT-1 can be used, for example, to change building setpoints or schedules; arm or disarm alarms; unlock doors; request status or determine operating conditions of equipment; and to report alarm or event conditions or history. The VT-1 provides 10 built-in prompt messages and 50 pre-recorded vocabulary words, which can be used individually or combined to form phrases and sentences. In addition, up to 50 custom messages (up to 3.5 minutes total) can be pre-recorded, played, and erased in the VT-1’s Message Management Mode - all over the telephone!
SPECIFICATIONS ELECTRICAL
Power Consumption:
1.5 W @ 24 VDC max.
Overload Protection:
0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection
INPUTS/OUTPUTS
Phone Line Connections:
1 RJ-11 connector with SIDAC and resettable telecom fuses
USER LEDS/SWITCHES
Status LEDS Power Communications Service/Wink indicator Record mode Play mode Erase mode Ring Off-hook
Switches Commission Reset
Note: VT-1 approved for use in North American phone systems only.
21
Page 22
Andover Controls Corporation World Headquarters 300 Brickstone Square • Andover, Massachusetts 01810 USA Tel: +1 978 470 0555 • Fax: +1 978 470 0946 http://www.andovercontrols.com Andover Controls Ltd. Smisby Road • Ashby-de-la-Zouch • Leicestershire LE65 2UG, England Tel: +44 1530 417733 • Fax: +44 1530 415436 Andover Control GmbH Am Seerhein 8 • D-78467 Konstanz, Germany Tel: +49 7531 99370 • Fax: +49 7531 993710 Andover Control S.A. Immeuble Dolomites 2 • 58 Rue Roger Salengro • 94126 Fontenay Sous • Bois Cedex, France Tel: +33 153 99 16 16 • Fax: +33 153 99 16 15 Andover Controls Asia Unit 1201-02, Phase I, Cheuk Nang Centre • 9 Hillwood Road, Tsim Sha Tsui • Kowloon, Hong Kong Tel: +852 2739 5497 • Fax: +852 2739 7350 Andover Controls Mexico Insurgentes Sur 1722-501 • Col. Florida • Mexico D.F. 01030, Mexico Tel: +525 661 56 72 • Fax: +525 661 54 15 Copyright 2002, Andover Controls Corporation. Data subject to change without notice. All brand names, trademarks and registered trademarks are the property of their respective holders. Consult Andover Product Installation Guides for exact installation instructions and specifications. #DS-C-I/O MODULE-F