The text of a spec sheet · part 2 of 3
Continuum I/O Modules: Modules, pages 4 to 13
Pages 4 to 13 of 22, from Continuum I/O Modules
The original document is the PDF (388 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Andover Controls DO-4, Andover Controls UI-8 and Schneider UI-8
Page 4
UI-8-10
I/O MODULE
The UI-8-10, Continuum’s universal input module, provides 8 universal inputs, software configurable as voltage, thermistor, digital, or counter point types. Each point can also be configured as a supervised input for security monitoring, providing separate indication of alarm and trouble conditions. This module is a perfect choice for any mix of temperature, pressure, flow, status points, and similar inputs in a control system, with a 0–5 volt input range and 10-bit A/D conversion. A UI-8-10-10V model is also available for 0–10 volt applications. It provides the identical point type selection, but is equipped with individual voltage divider DIP switches on each input, allowing each to be configured for a 0-10 volt range. SPECIFICATIONS ELECTRICAL
Power Consumption:
0.7 W @ 10-28VDC max.
Overload Protection:
0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection.
INPUTS
Number of Inputs:
8 Universal inputs; 10 bit resolution
Input Types:
Voltage, Thermistor, Digital, Counter, and Supervised
Input Protection:
24 V AC/DC allowed to any single input (40V TVS on each input – UI-8-10-10V model only)
Input Impedance
UI-8-10 (0–5V): UI-8-10-10V (0–10V):
Input Connections:
Two-piece, 13-position removable terminal block
Voltage: Range: Resolution: Accuracy: Thermistor:
Type: Range: Resolution: Accuracy:
5 MΩ w/pullup disabled; 10 KΩ w/pullup enabled 4.4 KΩ
UI-8-10 (0–5V) 0–5 V 5 mV ±15 mV (±0.3% FSR)
10 KΩ, Type III Thermistor -30 to 230°F (-34 to 110°C) 40 to 100°F range 0.20°F typical (4 to 38°C) (0.11°C typical) 40 to 100°F range ± 1.0°F (4 to 38°C) (±0.55°C)
Digital & Counter:
Input Type: Frequency: Pulse Width:
Contact Closure 4 Hz (max.) 125 ms ( min.) (Digital pulse widths are based on Scan Time.)
Supervised:
Input Type:
Single or Double Resistor Supervision, Parallel or Series Circuit
Power Comm Status
Power Indicator TD Indicator Service/Wink Indicator
USER LEDS/SWITCHES
Status Indicator LEDS
Push-Button Switches Commission Reset MODELS
4
UI-8-10-10V (0–10V) 0–10 V 10 mV ±40 mV (±0.4% FSR)
UI-8-10
8 Universal inputs; 0-5 Volt input range
UI-8-10-10V
8 Universal inputs; 0-10 Volt input range
Page 5
DI-8
I/O MODULE
The DI-8, Continuum’s digital input module, is used for cost-effective sensing of multiple dry digital inputs in applications such as equipment status monitoring or alarm point monitoring. The DI-8 has eight digital inputs - each can be software configured to accept a digital (contact closure or 0–5 volt input) or counter signal. Counter frequency is 10 Hz on all eight inputs. In addition, high speed counting up to 10KHz max. is available (via a DIP switch) on Channels 1 and 2 for high-speed metering and industrial applications. 40 V bipolar transorbs on all eight inputs protect against high voltage short duration transient events. The DI-8 is designed to accept dry contact inputs or 0-5 volts, but can withstand up to 24 VAC/VDC continuous voltage on four channels.
SPECIFICATIONS
ELECTRICAL
Power Consumption:
0.8 W @ 10–28 VDC max.
Overload Protection:
0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection
INPUTS
Number of Inputs:
8 Digital inputs
Input Types:
Digital or Counter, software selectable
Input Protection:
24 V AC/DC applied to 4 channels max. (40V TVS on each input)
Input Impedance:
10KΩ pull-up resistor referenced to +5 VDC
Inputs Connections:
Two-piece, 13-position removable terminal block
Digital:
Input Type: Pulse Width: Current:
Counter:
Input Type: Contact closure or 0–5 VDC input Channels 1 and 2 in HI-speed mode (selectable via dip switch): Frequency: 10kHz (max.) Pulse Width: 50 µS (min.) Current: 0.5 mA Channels 3 through 8; and Channel 1 and 2 in LO-speed mode: Frequency: 10 Hz (max.) Pulse Width: 50 mS (min.) Currrent: 0.5 mA
Contact closure or 0–5V input 50 ms ( min.) 0.5mA (max.)
USER LEDS/SWITCHES
Status Indicator LEDS Power Comm Status Input Status 1–8 Switches
5
Commission Reset
Power Indicator TD Indicator Service/Wink Indicator Input Status Indicator (Closed circuit=ON)
Page 6
DI-6-AC
I/O MODULE
The DI-6-AC, Continuum’s digital AC input module, has six digital (“wet”) AC inputs for cost-effective ON-OFF status indication of fan motor starters, solenoid valves, control relays, or external power supplies, and similar applications that require a quick and easy way to detect voltage. The DI-6-AC monitors the absence or presence of AC or DC voltage levels directly, with no interposing relays needed. The DI-6-AC can monitor voltages from 24–120V. A DI-6-AC-HV model is also available for sensing higher voltages - 120–240V. Both models can also accept DC voltages. All inputs are optically coupled with 2500V isolation on each input for noise-free operation. SPECIFICATIONS ELECTRICAL
Power Consumption:
0.7 W @ 24 VDC (max).; when provided by Continuum power supply module.
Overload Protection:
0.5 A re-settable fuse with transient voltage suppressor (TVS) and reverse polarity protection
INPUTS
Number of Inputs:
6 Digital AC or DC voltage inputs
Input Protection:
2500 V isolation on each input. Each input has a 270 V metal oxide varistor (MOV.)
Input Connections:
Two-piece, 13-position removable terminal block
AC Inputs AC Input Range: AC Input Current:
DI-6-AC 20–132 Vrms 5 mA (max.)
DI-6-AC-HV 90–250 Vrms 2 mA (max.)
AC Voltage “ON” Threshold:
16 Vrms 75 Vrms (Above this voltage is considered “ON”)
AC Voltage “OFF” Threshold:
8 Vrms 30 Vrms (Below this voltage is considered “OFF”)
Input Resistance (±5%):
30KΩ
200KΩ
Maximum Turn ON Time:
20 ms
20 ms
Maximum Turn OFF Time:
60 ms
60 ms
DC Input Voltage Range:
20–132 V
90–250 V
DC Input Current:
5 mA (max.)
2 mA (max.)
DC Voltage “ON” Threshold:
20 V 90 V (Above this voltage is considered “ON”)
DC Voltage “OFF” Threshold:
12 V 45 V (Below this voltage is considered “OFF”)
USER LEDS/SWITCHES
Status Indicator LEDS Power Comm Status Input Status 1–:6
Power Indicator TD Indicator Service/Wink Indicator Input Status Indicator (Above voltage threshold = ON)
Switches Commission Reset
MODELS
6
DI-6-AC
6 Digital AC Inputs, 24–120 V input signal
DI-6-AC-HV
6 Digital AC Inputs, 120–240 V input signal
Page 7
MI-6
I/O MODULE
The MI-6, Continuum’s milliamp input module, allows for a direct connection of a 2-wire 0–20mA or 4–20mA sensor to any of the module’s six inputs. The need for an external resistor and an external power supply is eliminated. The MI-6 module is a perfect match for temperature transmitters, humidity and pressure transducers, gas monitors, and other industry-standard sensors with either a 0–20mA or 4–20mA output. The six inputs on the MI-6 module have a 0-20mA range and 10 bit A/D conversion.
SPECIFICATIONS ELECTRICAL
Power Consumption:
3.8 W @ 24 VDC max. (Including up to 20mA sensor power for each input).
Overload Protection:
0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection.
INPUTS
Number of Inputs:
6 Milliamp inputs
Input Range:
0–20 mA
Resolution:
20 µA
Accuracy:
±80 µA (max.)
Drift:
±50ppm/DegC (max.)
Input Resistance:
249Ω, 0.1%
Maximum Input Current:
±30 mA
Voltage Supply to Sensors:
19–26 VDC
Input Protection:
Each input: A transient voltage suppressor (TVS) and a resettable fuse. Sensor voltage output: TVS and resettable fuse
Input Connections:
Two-piece, 13-position removable terminal block
USER LEDS/SWITCHES
Status Indicator LEDS Power Comm Status Switches Commission Reset
7
Power Indicator TD Indicator Service/Wink Indicator
Page 8
AO-4-8
I/O MODULE
The AO-4-8, Continuum’s analog output module, has four analog outputs with eight-bit resolution, which can be configured as either voltage (0–10 VDC) or current (0–20 mA) outputs. The AO-4-8 is the perfect choice for valves, dampers, variable speed drives, and similar equipment that demand high control accuracy. An AO-4-8-O model with full override capabilities is also available. Each output contains a three-position manual override switch and override potentiometer. In addition, the AO-4-8-O provides software override feedback to Andover’s Plain English® programming language for each output. SPECIFICATIONS ELECTRICAL
Power Consumption:
3.8 W @ 24 VDC max.
Overload Protection:
0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection
OUTPUTS
AO-4-8:
4 Analog outputs; 8 bit resolution
AO-4-8-O:
4 Analog outputs with overrides; 8 bit resolution
Output Protection:
1/8 pico fuse per channel (40V TVS on each output - AO-4-8-O model only)
Output Connections:
Two-piece, 13-position removable terminal block
Output Types:
Voltage or current
Voltage: Range: Resolution: Accuracy: Output Current: Load Resistance:
0–10 VDC 0.05 V ±0.10V (1%FSR) +5 mA (sourcing) -1 mA (sinking) 2KΩ .(sourcing, min.)
Range: Resolution: Accuracy: Load Resistance:
0–20 mA 0.1 mA ±0.2 mA 650Ω (max.)
Current:
Output Overrides:
3-position manual override switch and override potentiometer on each output, with software feedback. LED override status indicator. (AO-4-8-O only)
USER LEDS/SWITCHES
Status Indicator LEDS Power Comm Override Status
Power Indicator TD Indicator Common Override Indicator Service/Wink Indicator
Switches Commission Reset MODELS
8
AO-4-8:
4 Analog outputs
AO-4-8-O:
4 Analog outputs with overrides
Page 9
DO-6-TR I/O MODULE
The DO-6-TR, Continuum’s triac output module, has six Form A triac-based outputs, rated at 0.5 A @ 24 VAC, for cost-effective on/ off or pulse-width modulation (PWM) control of lighting, heat, and fan units. The PWM feature permits the modulation of valves and dampers to 0.1 second resolution. Adjacent outputs can also be configured in pairs to provide up to three Form K, Tri-state outputs for bi-directional control of dampers and valves. Metal oxide varistors and optocouplers on the DO-6-TR provide 2500V isolation on each output, ensure noise-free operation, and, in most cases, eliminate the need to install MOVs in the field. SPECIFICATIONS ELECTRICAL
Power Consumption:
1.1 W @ 24 VDC max.
Overload Protection:
0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection.
OUTPUTS
Output Type:
6 Form A optically isolated triac outputs (can be configured up to 3 Form K Tri-State outputs)
Output Rating:
0.5 A @ 24 VAC (Cannot switch DC loads)
Output Accuracy:
0.1 sec. for Pulse Width Modulation (PWM) control
Output Protection:
2,500 V optical isolation Metal oxide varistor and snubber on each output
Output Connections:
Two-piece, 13-position removable terminal block
USER LEDS/SWITCHES
Status Indicator LEDS Power Comm Status Out1-Out6 Switches Commission Reset
9
Power Indicator TD Indicator Service/Wink Indicator Six Output Status Indicators
Page 10
DO-4-R
I/O MODULE
The DO-4-R, Continuum’s digital output module, has four Form C relay outputs, rated at 5 A @ 240 VAC. These versatile outputs make the DO-4-R an excellent choice for switching motor starters and other inductive loads up to 240 VAC, with either two position (on/off) or pulse-width modulation (PWM) control. The PWM feature permits the modulation of valves and dampers to 0.1 second resolution. Two adjacent Form C relay outputs can be combined in software to provide a Tri-state output, for bi-directional control of valves and dampers and other end devices. Metal oxide varistors and 5,000 V isolation on each output ensures reliable noise-free operation. A DO-4-R-O model with full override capability is also available. Each output has a local hand-off-auto switch, which enables service personnel to override the output. The switch also provides override feedback of the output value for use in troubleshooting or test conditions. A local indicator light for each output displays relay status. Another LED provides override status. SPECIFICATIONS ELECTRICAL
Power Consumption:
2.8 W @ 10–-28 VDC max.
Overload Protection:
0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection
OUTPUTS
DO-4-R:
4 Form C relay outputs
DO-4-R-O:
4 Form C relay outputs with overrides
Output Rating:
5 A @ 240 VAC; 5 A @ 30 VDC
Output Resolution:
0.1 sec. For Pulse Width Modulation (PWM) control
Output Protection:
270 V varistors across contacts. 5000 Vrms isolation @ 60 Hz between relay contacts and relay coil.
Output Overrides:
3-position manual override switch on each output, with software feedback. LED override status indicator (DO-4-R-O only)
Override Feedback:
Override detection and feedback provided for each output.
Output Connections:
Two-piece, 13-position removable terminal block
USER LEDS/SWITCHES
Status Indicator LEDS Power Comm Override Status Out1-Out4
Power Indicator TD Indicator Common Override Indicator Service/Wink Indicator Four Output Status Indicators
Switches Commission Reset MODELS
10
DO-4-R
4 Form C relay outputs
DO-4-R-O
4 Form C relay outputs with overrides
Page 11
DM-20
I/O MODULE
The DM-20, Continuum’s Digital Input and Output module, provides high density, versatile I/O for many control applications.The DM-20 can control any combination of 20 inputs and outputs. When coupled with the optional DIO-20 Expansion Board, the DM-20 allows you to mix and match up to 20* digital inputs and outputs using standard off-the-shelf digital I/O blocks to meet a wide range of applications, including ON-OFF or pulse-width modulation (PWM) control of equipment and for switching inductive loads up to 240VAC. The DM-20 provides 24 VDC power to the DIO-20 via a three-position cable assembly. * Actual number of modules depends on the mix of inputs/outputs used. See Continuum I/O System Reference Manual (Rev D or higher) for more information.
SPECIFICATIONS
ELECTRICAL
Power Consumption:
0.5 W @ 24VDC max. Up to 9 W @ 24 VDC when the DIO-20 is powered from the DM-20 .
External Power Connector:
Three-position removable connector
Overload Protection:
0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection for both DM-20 power and DIO-20 power.
LED Power Supply:
Customer-provided external 5 V power supply when using the DM-20 to drive LEDs.
INPUTS/OUTPUTS
20 total points; user-selectable channel-by-channel as inputs or outputs Inputs w/o DIO-20
Input Type:
Digital 0–5 VDC w/DIO-20
24 VDC logic voltage (DIO-20). Input rating depends on input module(s) selected
Pulse Width:
125 ms ( min.) 125 ms ( min.) (Digital pulse widths are based on Scan Time.)
Current:
10µA
N/A
Outputs w/o DIO-20 w/DIO-20
Output Type:
Digital Open- collector transistor with series 330 ohm 1/8 W resistor; 15 mA (max.) @ 5 V DC
5 VDC logic voltage. Output range depends on output module selected.
Output Resolution:
0.1 sec. For Pulse Width Modulation (PWM) control
Output Protection:
Transient voltage suppressor (TVS) and current limiting resistor on each channel.
Input/Output Connections:
One female 25-pin D-subminiature connector
USER LEDS/SWITCHES
Status Indicator LEDS Power Comm Status Switches 11
Commission Reset
Power Indicator TD Indicator Service/Wink Indicator
Page 12
The AC-1 Family of Access Control Modules Andover Controls offers three access control modules to meet the demands of different access requirements: Use the AC-1 when powering modules from a Continuum power supply. (AC-1 has a 24VDC power input only. ) The AC-1 supports
AC-1:
Wiegand/Prox cards and 5 V/12 V reader power (switch-selectable). AC-1A:
Use the AC-1A if you are powering modules from a local 12VDC power supply. The AC-1A offers an extended 10-28VDC power input. (Power supply can also power any 12 V prox readers you may be using.) The AC-1A supports Wiegand/Prox cards, and 5 V reader power only.
AC-1Plus: The enhanced version. Use the AC-1Plus when using mag stripe or Cardkey readers, ADA sequences that require extra inputs, special door unlock/door ajar times for disabled persons, and jobs that require reader tamper detection. The AC-1Plus offers an extended 10-28VDC power input (power supply can also power 12 V prox readers), and supports 5 V reader power only.
AC-1
I/O MODULE
The AC-1provides full I/O for an access controlled door or portal in one compact module. The AC-1 can be located near an access controlled door for localized control and reduced wiring costs; or several AC-1 modules can be grouped together and DIN railmounted for centralized control. The AC-1 provides a Wiegand card input for Wiegand swipe and proximity type cards, reading up to 64 bits per card. Reader power is switch-selectable between 5V and 12V to meet most card reader power requirements. The AC-1 has two 5 A, Form C relays - one for the door lock and a second for local alarm annunciation. Each output has an integral hand-off-auto switch for manual operation, and software feedback of the switch position. Up to three supervised alarm inputs can be used for door status contacts, request-to-exit devices, a cabinet tamper switch, or any other two-state or three-state (on/off/trouble) alarm device.
KEYPAD CONTROL
The AC-1 supports Wiegand output keypads. To simplify installation and reduce wiring costs, the keypad data comes into the module via the reader data lines.
ACCESS CONTROL
During normal operation of the AC-1, access decisions are made in the Continuum NetController CPU , which provides storage for up to 75,000 “local” personnel records. In addition, the NetController’s event buffer is software-configurable to allow for the most optimized memory usage. If network communications are interrupted, the AC-1 will revert to a programmable degrade mode of operation, providing uninterrupted card access using site codes and other degrade mode parameters stored in non-volatile EEPROM in each AC-1 module. A door can be configured to operate based on site code only, site code plus card, card plus personal ID number (PIN), or keypad only. The door’s operating mode can even be changed based on time-of-day or other events for optimum flexibility through Andover Controls’ easy-to-use Plain English® programming language. Each keypad can also permit entry of a duress alarm code that can initiate an alarm sequence at any AC-1 controller or at the Continuum workstation. Time-based anti-passback and entry/egress anti-passback are available to prevent tailgating. Entry/egress anti-passback is system-wide and can be performed by readers located on different AC-1 controllers across the network. Using Plain English, the AC-1 can also be used for custom access control sequences such as two-man rule, optical turnstile control, and man trap configurations. 12
Page 13
AC-1 I/O MODULE CONTINUED SPECIFICATIONS ELECTRICAL
Power Consumption:
2.6 W plus reader power consumption at 24VDC max.
Overload Protection:
0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection
INPUTS/OUTPUTS
Inputs Card Readers:
1
Card Reader Type:
Supports Wiegand swipe and proximity readers
Maximum Number of bits/Card:
64
Card Reader Power:
5 VDC or 12 VDC (switch selectable) Switch Setting Output Voltage +5 V +5.20 V ±0.05 V +12 V +12.0 V ±5%
Distance, Card Reader to AC-1:
Output Current 120 mA (max.) 180 mA (max.)
500 ft. max. using 18-ga. wire 200 ft. max. using 22-ga. wire
Alarm Inputs:
Up to 3 supervised inputs. Single or double resistor supervision, series or parallel.
Input Protection:
Transient voltage suppressor (TVS) on each input
Outputs Door Outputs:
2 Form C relays
Output Rating:
5 A @ 24 V AC/DC
Output Protection:
5,000 V isolation 270 V metal oxide varistors (MOVs) on each output
Overrides:
3-position manual override switch on each output for manual control of relay. LED override status indicator.
Override Feedback:
Override detection and software feedback provided for each output.
Reader LED Output:
Open collector; up to 50 mA.
Inputs/Output Connections:
Two-piece, 16-position removable terminal block
USER LEDS/SWITCHES
Status Indicator LEDS Power Comm Override Status Out1 - Out2 +5 V Reader Power +12 V Reader Power Switches Commission Reset 13
Power Indicator TD Indicator Common Override Indicator Service/Wink Indicator Two Output Status Indicators 5 V Reader Power Indicator 12 V Reader Power Indicator