Page 1
ª
I/O Modules The Continuum intelligent building system allows you to mix and match various combinations of DIN rail-mounted modules, flexible I/O, CPU and power supply, and your choice of several user interface modules, in a single controller location to meet your building’s • Flexible, Modular Design control and monitoring needs. With the Continuum system, as your network grows, simply
Fits Every Application add or replace I/O modules as needed. • User-Configurable I/O Selection
The Continuum I/O modules feature a sleek, lightweight casing designed for natural to Meet Specific Control Needs convection cooling, and a 3-position front cover for easy access. Built-in quick-release • DIN Rail Mounting Provides Easy Installation and System Expansion fasteners at the back of each I/O module are provided for DIN rail mounting, no tools required. These fasteners also snap into a locked position for panel mounting. Input and output connectors are located at the bottom of each I/O module and are removable for easy
• NEMA 1-Style Enclosure Available field access and maintenance. All Continuum modules are designed for mounting in an • Three-Position Front Cover for optional NEMA 1-style Continuum enclosure.
Easy Access
The Continuum I/O modules communicate with the Continuum NetController CPU module using Andover LON communications. Like all Continuum modules, the I/O modules slide
• Built-in Quick-Release Fasteners - No Tools Required!
together via built-in connectors on either side so network expansion is quick and easy. Both power transmission and communication signals feed through these connectors. For added
• Removable Input/Output Connectors for Easy Installation convenience, in applications such as door control or lighting control, a single module or groups of I/O modules can be remotely located and connected using approved cable, and
• Slide-Together Power/ powered from a local power supply. Each I/O module features its own push-button for quick
Communications Connections and easy network commissioning. • Optional Remote Mounting
COMMUNICATION CHOICES
All Continuum modules are available in either the standard RS-485 or the Free Topology • Push-Button Network
(FTT-10A) media interface. RS-485 is perfect for local mounting applications and is a lower
Commissioning cost media choice. FTT-10A provides increased flexibility and reliability. FTT modules are • Choice of RS-485 or FTT-10A Media connected using a twisted-pair cable and can be wired in a bus, star, distributed star, or even a ring topology for added resilience. Note: You cannot mix and match both media types on the same I/O bus. 1
Page 2
All Continuum I/O modules share the following specifications: MECHANICAL
Operating Environment:
32–120°F (0 to 49°C), 10–95%RH (non-condensing)
Size*:
3.8”W (96.5mm) including connectors 7.2”H (182.88mm) with mounting clips extended 6.2”H (157.48mm) with mounting clips closed 2.5”D (96.5 x 170.2 x 63.5mm) *With the exception of the VS-8-4 models, 9.0”W x7.2”H (6.2”H closed) x 2.5”D (228.7 x 182.88mm (157.48 mm closed) x 63.5mm)
Weight*:
.75 lbs (0.34kg) *With the exception of the PO-2 models - 1.02lbs (0.46kg) and the VS-8-4 models - 1.32lbs (0.60kg)
Enclosure Type:
UL open class, flammability rating of UL94-5V, IP 10
Mounting:
Mount on DIN rail or wall-mount using attached clips. Continuum NEMA 1-style enclosure available.
B ATTERY BACKUP
Via Continuum UPS power supply COMMUNICATIONS
Communications Interface:
Andover Controls Corporation (ACC)-LON communications with Continuum CPU module. Choice of RS-485 or FTT-10A interface
Comm. Error Checking:
International Standard CRC 16
RS-485:
Communications Speed: 39k baud Bus Length: 2,000 ft. (610m). Bus Media: Shielded, twisted pair cable. 120Ω termination required at both ends of the ACC-LON network (when modules are mounted remotely).
FTT-10A:
Communications Speed: 78k baud Bus Length: Up to 8858 ft. (2700m) – bus topology Up to 1640 ft (500m) – free topology Repeater required for longer distances. Bus Media: Refer to FTT-10A documentation in Continuum I/O System Reference Guide (P/N: 30-3001-4999--Rev D or higher)
Power/Communications Connections: 5-position plug-in connectors on left and right sides allow Continuum modules to be directly connected to each other or remotely connected via approved cable. CPU
3120E2 MCU with internal ROM, EEPROM, and SRAM Except VT-1 and AC-1Plus: 3150BFU1 with internal EEPROM and external FLASH and SRAM AGENCY LISTINGS
UL/CUL 916, FCC CFR 47 Part 15, ICES-003, EN55022, AS/NZS 3548, and VCCI Class A, CE UL 864 - (UI-8-10-S, DI-8-S, MI-6-S, AO-4-8-S, DO-6-TR-S, DO-4-R-S, DM-20-S, DO-4-R-O-S, UI-8-10-10V-S, AO-4-8-0-S, PO-2-D-O-S, and PO-2-S only) UL 294 - (UI-8-10, DI-8, DO-4-R, DM-20, AC-1, AC-1Plus, AC-1A, UI-8-10-10V, DO-4-R-O, VS-8-4, and VS-8-4-T only) UL-1076 - (UI-8-10, UI-8-10-10V, DO-4-R, DO-4-R-O, AC-1, AC-1a, and AC-1Plus only)
2
Page 3
D I M E N S I O N D R AW I N G S
6.2” (157.48 mm) Mounting Clips Closed 7.2” (182.88 mm) Mounting Clips Extended
3.50” (88.5 mm)
2.50” (63.5 mm) Small I/O Packaging
6.2” (157.48 mm) Mounting Clips Closed 7.2” (182.88 mm) Mounting Clips Extended
2.50” (63.5 mm)
9.0” (228.7 mm)
Large I/O Packaging (VS-8)