Manual · Andover Controls
Andover Controls AC-1, CPU-4M, CPU-8M, DO-4, UI-8 and Schneider UI-8 Manual
Manual2 pagesPDF 132 KB
Both pages are below, each with its text.
Names · 3 models
The models it names
Filed with · 3 models
Also filed with these models on the old site
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Two-page installation sheet for Andover Continuum I/O modules from Schneider Electric. It shows DIN mounting, I/O bus connections, grounding, wiring rules, module power use and wiring diagrams for the UI-8-10 / UI-8-10-10V, DIO-20, DM-20, DI-6-AC, DI-8, MI-6, AO-4-8, DO-4-R, DO-6-TR, LO-2 and VT-1 modules.
- Document
- Installation sheet for Andover Continuum I/O modules (doc 30-3001-716) p. 2
- Modules per CPU
- Up to 32, fewer if power supply capacity runs out; 32 may need an auxiliary supply p. 1
- I/O bus pin-out
- 1 COMM A, 2 COMM B, 3 SHIELD, 4 24 VDC RETURN, 5 +24 VDC p. 1
- Remote bus cable
- Shielded twisted pair; RS-485 at 100-120 ohm impedance, or FTT-10A low capacitance p. 1
- Max cable lengths
- 2000 ft. (610 m); 8858 ft. (2700 m) bus topology; 1640 ft. (500 m) free topology p. 1
- RS-485 termination
- 120 ohm resistor across pins 1 and 2 at both ends of a remote cable p. 1
- UI-8 max input voltage
- UI-8-10: 5V; UI-8-10-10V: 10V p. 1
- Power draw
- UI-8-10 and UI-8-10-10V 0.7 W; DO-4-R 2.8 W; CPU 10 W p. 1
- DO-4-R contacts
- 5A @ 240 VAC, 5A @ 30 VDC p. 2
- DI-6-AC input range
- DI-6-AC 20-132 Vrms; DI-6-AC-HV 90-250 Vrms p. 2
- Cable connector
- ACC # 01-0010-840 (20 pcs.) p. 1
What this manual walks you through
- Connecting I/O modules to the CPU directly or by remote cable p. 1
- Grounding the modules p. 1
- Following the wiring guidelines for reliable operation p. 1
- Terminating an RS-485 remote connection p. 1
- Wiring universal inputs, including supervised contact circuits p. 1
- Connecting a DM-20 to a DIO-20 p. 1
- Checking the power budget of the modules on one CPU p. 1
- Wiring LO-2 override switches and external relays p. 2
Good to know
- Never ground an input signal externally; it can damage the unit. p. 1
- Earth ground must be connected to avoid damaging the module. p. 1
- In 10V mode the UI-8-10-10V input impedance drops to 4.4K, which may affect the driving device. p. 1
- Remote power hookups need a listed power-limited supply, sized for a maximum voltage drop of 2 VDC. p. 1
- The sheet states that only the UI-8-10, UI-8-10-10V, DI-8 (UL294 only) and DO-4 here were evaluated by UL for UL 294 and UL 1076. p. 2
Questions this manual answers
How many I/O modules can one Continuum CPU take?
Up to 32, but the power supply capacity may lower that, and 32 modules may need an auxiliary power source. p. 1
What is the maximum input voltage of the UI-8-10?
5V for the UI-8-10 and 10V for the UI-8-10-10V. p. 1
How do I terminate a remote RS-485 I/O cable?
Put a 120 ohm resistor across pins 1 and 2 at the start and at the end of the remote cable. p. 1
How much power does a UI-8-10 module use?
0.7 W, for both the UI-8-10 and the UI-8-10-10V. p. 1
What is the contact rating of the DO-4-R relay output module?
5A at 240 VAC and 5A at 30 VDC. p. 2
The file
Size and text
Every page · 2
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 2
Open in the PDF
The text of page 1, from the PDF itself
Mechanical DIN243Wiring RulesI/O Bus
These modules are intended for installation within the UL Listed enclosure model UL-ENCL for UL 294 and UL 1076.
I/O Modules connect in the following configurations:
Direct Connect
Direct Connect
Do not remotely ground any part of the input sensor wiring.
Max. Number of I/O Modules Number of modules is limited to 32 per CPU but may be reduced due to the capacity of the Power Supply**
Direct Connect
Power Supply PS 120/240 AC 50-U PS 120/240 AC 50 1 PS 120/240 AC 85-U PS 120/240 AC 85 PS –48 DC 50
Remote grounds connected to the return terminal could make the system operate incorrectly or damage the equipment.
Power Supply
The signal return is not true earth ground. It is an electronic reference point necessary to interpret the sensor properly.
15PANEL
For reliable operation, follow these wiring guidelines: · Never lay wires across the surface of a printed circuit board. · Wires should never be within 1 in. or 25 mm of any component on a printed circuit board.
Remote Cable
4 24 VDC RETURN 3 SHIELD
I/O2 COMM BI/O
Caution Do not externally ground any input signal. This may damage the unit. Signal return terminals are not connected to earth ground.
4 3 2 1
Technical Specifications
UI-8-10 / UI-8-10-10V
Digital Input/Output Module
Universal Input ModuleI/O xGND5V+24 VDC+24 V ReturnContact ClosureRET+5V
IN x Reference Resistor = OFF
DC VoltageV -INx Contact ClosureRETDIO-20LED IndicatorI/O xMax DC Voltage: GNDUI-8-10UI-8-10-10V *5V10VINxIN1 IN2 RETIN3 IN4 RETIN5 IN6 RETIN7 IN8 RET1471035689RET
Series-Parallel Circuits
10 KW111210 KW 10 KWContact Closure!INx10 KWContact Closure RET210 KWRET
- Note: In the 10V mode the input impedance is reduced to 4.4K. This may affect the performance of the driving device.
GNDINx Contact Closure10 KW10KI/O xRETParallel Circuits +Digital logic InputINxI/O xGND
DM-20 to DIO-20 Power Connection
Normally Closed 10 KWContact ClosureContact Closure
24VDC @ .36 Amps TO DI0-20
Reference Resistor = ON
INx
Reference Resistor = ON
ThermistorSeries Circuits10 KWRETDIO-202Normally OpenIN xDM-201
8858 ft. (2700 m) bus topology 1640 ft. (500 m) free topology
IN x
10K
Cable Connector: ACC # 01-0010-840 (20 pcs.)
2000 ft. (610 m)Supervised Circuits5VContact ClosureConnectorsMax. Cable Lengths
COMM A&B Lines: Shielded, Twisted Pair RS-485 Impedance= 100-120 W FTT-10A Low Capacitance Power Lines: Remote hookups require Listed UL294 UL1076 power limited power supply. Calculate f for maximum voltage drop of 2 VDC
DM-20
- -
- Wattage does not include external devices ** 32 modules may require an auxiliary power source.
Local & Remote Cable Information
120 W EOL Resistor
Module Power Req. CPU (NetController) 10 W UI-8-10 & UI-8-10-10V 0.7 W DI-6 AC & DI-6 AC HV 0.7 W DI-8; Digital Input Module 0.8 W MI-6; MilliAmp Input Module 3.8 W DM-20 0.5 W * AO-4-8 & AO-4-8-O 3.8 W DO-4-R & DO-4-R-O 2.8 W DO-6-TR 1.1 W LO-2 & LO-2-O 0.4 W VT-1 1.5 W AC-1 2.6 W * AC-1A 2.0 W * AC-1 Plus 2.2 W * 1 The PS 120/240 AC 85-U model is only to be used for UL294 applications.
RS-485 Remote configuration (outside the Continuum enclosure) requires a 120 W resistor across pin 1 & 2 at the begining and at the end of the remote cable.
30-3001-716 Rev G.1Digital logic SignalRemote Connect
Remote Connection Line Termination
Some modules include an integral ground clip. All modules include a screw terminal connection for earth ground. It is important that this connection be made as close to the module as possible.
DM-20 to DIO-20 Data Connection
I/O1 COMM A5General Purpose I/OI/OLocal Cable5 +24 VDC
· Use shielded wire. · Terminate the shield of the wires at one end of the run only - preferably at the end where your I/O module is located. · Be careful when stripping wire not to drop small pieces of wire inside the cabinet. · Don’t run your wiring in the same conduit with AC power. · Don’t run your input wiring in the same conduit with your output wiring.
DIO-20 ConnectionsI/ODirect ConnectModule I/O Bus Pin-OutGrounding the ModulesI/O InstallationCPU
Power Avail. 35 W 50 W 70 W 85 W 50 W
RET
Caution: Earth ground ( ) must be connected to avoid module damage
Page2of 2
Open in the PDF
The text of page 2, from the PDF itself
DI-6 AC / DI-6-AC-HVMI-6DO-4-R / DO-4-R-OVT-1
AC Digital Input Module
MilliAmp Input ModuleRelay Output ModuleVoice Telecom ModulePolarity IndependentLOADSupplyAC SignalDC SignalIN x
24V Loop-Powered Sensor
IN xINxOUT xSignal
- Voltage Range
- LOAD
DI-6-ACDI-6-AC-HV
- Max Current
- 20 mA
20-132 Vrms
90-250 Vrms
Voltage Supply to Sensor: 19 - 26V
- Contact Rating
- DI-8
AO-4-8 / AO-4-8-ODO-6-TRDigital Input ModuleAnalog Output ModuleTriac Output ModuleVoltage OutputDigital logic Signal
5A @ 240 VAC 5A @ 30 VDC
RJ-11 Telephone Line+ ONCurrent OutputEarth GroundOUT 1IN x OUTx IOUTx IIN x Contact Closure
OUTx V Device Load Resistance
RET
³ 2KW
Device Load Resistance £ 650W
OUT xLOADOUTx VCommonFORM AOUT 2GNDGNDON
Using Two Outputs to make FORM K
IN1 IN2 RETIN3 IN4 RETIN5 IN6 RETIN7 IN8 RET
- Current Output
- 0 - 20 mA
- Output Rating
- 24 VAC, 0.5 A (Cannot switch DC Loads)
14710
- Voltage Output
- 0 - 10V
- Minimum Load Current
- 30 mA
2356891112
LO-2 / LO-2-O Lighting Output Module
For more information on these Andover Continuum products, see the I/O Systems Reference, 30-3001-499, and the Power Supply Reference, 30-3001-702. For documentation specific to Underwriters Laboratories (UL) evaluation, see the Note below.
Override Switch Connections
Module External Power Connections 28 VAC Transformer
Momentary Switch
UL 916 Listed product for the United States and Canada, Open Energy Management Equipment.
PWR 24-30 VACOFFONREDGND
UL 294 (Access Control System Unit Subassemblies for the United States) and UL 1076 (Proprietary Burglar Alarm System Unit Subassemblies for the United States) and C22.2 No. 205-M1983 (Signal Equipment for Canada)
BLK
This ground connection must be the same as the ground for the Continuum Power Supply
28 VDC (half-wave rectified AC) to External Sensors
- Output Rating
- OVERRIDE
Indicator
Lamp Load – 20 Amp Tungsten Filament @125 VAC Resistive Load – 20 Amp Ballast @ 277 VAC (20 amp @347 VAC, Canada) Motor Load – 0.5 Hp @ 110-125 VAC 0.5 HP @ 220-277 VAC (0.5 Hp @ 347 VAC, Canada)
YELWHT28 VAC RECTRED (ON)
External Relay Assy. Connections
Note: Refer to the UL Listed Access Control/Proprietary Burglar Alarm System’s installation manual (the UL294 Access Control and UL 1076 Proprietary Burglar Alarm Systems Reference, 30-3001-504) for specific wiring, operation, and compatibility information.
REDBLK (OFF)BLK OVERRIDEOccupancy Sensor YELWHT (COM)BLU (POWER)WHT28 VAC RECT.
Note: Only these products mentioned in this document are evaluated by UL for UL 294 and UL 1076 applications: UI-8-10 UI -8-10-10V DI-8 (UL294 only) DO-4
© 2011 Schneider Electric All Rights Reserved. Schneider Electric § One High St. § North Andover MA USA 01845