Two-page installation sheet for Andover Continuum I/O modules from Schneider Electric. It shows DIN mounting, I/O bus connections, grounding, wiring rules, module power use and wiring diagrams for the UI-8-10 / UI-8-10-10V, DIO-20, DM-20, DI-6-AC, DI-8, MI-6, AO-4-8, DO-4-R, DO-6-TR, LO-2 and VT-1 modules.

Document
Installation sheet for Andover Continuum I/O modules (doc 30-3001-716) p. 2
Modules per CPU
Up to 32, fewer if power supply capacity runs out; 32 may need an auxiliary supply p. 1
I/O bus pin-out
1 COMM A, 2 COMM B, 3 SHIELD, 4 24 VDC RETURN, 5 +24 VDC p. 1
Remote bus cable
Shielded twisted pair; RS-485 at 100-120 ohm impedance, or FTT-10A low capacitance p. 1
Max cable lengths
2000 ft. (610 m); 8858 ft. (2700 m) bus topology; 1640 ft. (500 m) free topology p. 1
RS-485 termination
120 ohm resistor across pins 1 and 2 at both ends of a remote cable p. 1
UI-8 max input voltage
UI-8-10: 5V; UI-8-10-10V: 10V p. 1
Power draw
UI-8-10 and UI-8-10-10V 0.7 W; DO-4-R 2.8 W; CPU 10 W p. 1
DO-4-R contacts
5A @ 240 VAC, 5A @ 30 VDC p. 2
DI-6-AC input range
DI-6-AC 20-132 Vrms; DI-6-AC-HV 90-250 Vrms p. 2
Cable connector
ACC # 01-0010-840 (20 pcs.) p. 1

What this manual walks you through

  • Connecting I/O modules to the CPU directly or by remote cable p. 1
  • Grounding the modules p. 1
  • Following the wiring guidelines for reliable operation p. 1
  • Terminating an RS-485 remote connection p. 1
  • Wiring universal inputs, including supervised contact circuits p. 1
  • Connecting a DM-20 to a DIO-20 p. 1
  • Checking the power budget of the modules on one CPU p. 1
  • Wiring LO-2 override switches and external relays p. 2

Good to know

  • Never ground an input signal externally; it can damage the unit. p. 1
  • Earth ground must be connected to avoid damaging the module. p. 1
  • In 10V mode the UI-8-10-10V input impedance drops to 4.4K, which may affect the driving device. p. 1
  • Remote power hookups need a listed power-limited supply, sized for a maximum voltage drop of 2 VDC. p. 1
  • The sheet states that only the UI-8-10, UI-8-10-10V, DI-8 (UL294 only) and DO-4 here were evaluated by UL for UL 294 and UL 1076. p. 2

Questions this manual answers

How many I/O modules can one Continuum CPU take?

Up to 32, but the power supply capacity may lower that, and 32 modules may need an auxiliary power source. p. 1

What is the maximum input voltage of the UI-8-10?

5V for the UI-8-10 and 10V for the UI-8-10-10V. p. 1

How do I terminate a remote RS-485 I/O cable?

Put a 120 ohm resistor across pins 1 and 2 at the start and at the end of the remote cable. p. 1

How much power does a UI-8-10 module use?

0.7 W, for both the UI-8-10 and the UI-8-10-10V. p. 1

What is the contact rating of the DO-4-R relay output module?

5A at 240 VAC and 5A at 30 VDC. p. 2

The file

Size and text

Pages2
PDF132 KB
TextText from the PDF itself.

Every page · 2

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Andover Controls AC-1, CPU-4M, CPU-8M, DO-4, UI-8 and Schneider UI-8 Manual

The text of page 1, from the PDF itself

Mechanical DIN243Wiring RulesI/O Bus

These modules are intended for installation within the UL Listed enclosure model UL-ENCL for UL 294 and UL 1076.

I/O Modules connect in the following configurations:

Direct Connect

Direct Connect

Do not remotely ground any part of the input sensor wiring.

Max. Number of I/O Modules Number of modules is limited to 32 per CPU but may be reduced due to the capacity of the Power Supply**

Direct Connect

Power Supply PS 120/240 AC 50-U PS 120/240 AC 50 1 PS 120/240 AC 85-U PS 120/240 AC 85 PS –48 DC 50

Remote grounds connected to the return terminal could make the system operate incorrectly or damage the equipment.

Power Supply

The signal return is not true earth ground. It is an electronic reference point necessary to interpret the sensor properly.

15PANEL

For reliable operation, follow these wiring guidelines: · Never lay wires across the surface of a printed circuit board. · Wires should never be within 1 in. or 25 mm of any component on a printed circuit board.

Remote Cable

4 24 VDC RETURN 3 SHIELD

I/O2 COMM BI/O

Caution Do not externally ground any input signal. This may damage the unit. Signal return terminals are not connected to earth ground.

4 3 2 1

Technical Specifications

UI-8-10 / UI-8-10-10V

Digital Input/Output Module

Universal Input ModuleI/O xGND5V+24 VDC+24 V ReturnContact ClosureRET+5V

IN x Reference Resistor = OFF

DC VoltageV -INx Contact ClosureRETDIO-20LED IndicatorI/O xMax DC Voltage: GNDUI-8-10UI-8-10-10V *5V10VINxIN1 IN2 RETIN3 IN4 RETIN5 IN6 RETIN7 IN8 RET1471035689RET

Series-Parallel Circuits

10 KW111210 KW 10 KWContact Closure!INx10 KWContact Closure RET210 KWRET

  • Note: In the 10V mode the input impedance is reduced to 4.4K. This may affect the performance of the driving device.

GNDINx Contact Closure10 KW10KI/O xRETParallel Circuits +Digital logic InputINxI/O xGND

DM-20 to DIO-20 Power Connection

Normally Closed 10 KWContact ClosureContact Closure

24VDC @ .36 Amps TO DI0-20

Reference Resistor = ON

INx

Reference Resistor = ON

ThermistorSeries Circuits10 KWRETDIO-202Normally OpenIN xDM-201

8858 ft. (2700 m) bus topology 1640 ft. (500 m) free topology

IN x

10K

Cable Connector: ACC # 01-0010-840 (20 pcs.)

2000 ft. (610 m)Supervised Circuits5VContact ClosureConnectorsMax. Cable Lengths

COMM A&B Lines: Shielded, Twisted Pair RS-485 Impedance= 100-120 W FTT-10A Low Capacitance Power Lines: Remote hookups require Listed UL294 UL1076 power limited power supply. Calculate f for maximum voltage drop of 2 VDC

DM-20

  • -
  • Wattage does not include external devices ** 32 modules may require an auxiliary power source.

Local & Remote Cable Information

120 W EOL Resistor

Module Power Req. CPU (NetController) 10 W UI-8-10 & UI-8-10-10V 0.7 W DI-6 AC & DI-6 AC HV 0.7 W DI-8; Digital Input Module 0.8 W MI-6; MilliAmp Input Module 3.8 W DM-20 0.5 W * AO-4-8 & AO-4-8-O 3.8 W DO-4-R & DO-4-R-O 2.8 W DO-6-TR 1.1 W LO-2 & LO-2-O 0.4 W VT-1 1.5 W AC-1 2.6 W * AC-1A 2.0 W * AC-1 Plus 2.2 W * 1 The PS 120/240 AC 85-U model is only to be used for UL294 applications.

RS-485 Remote configuration (outside the Continuum enclosure) requires a 120 W resistor across pin 1 & 2 at the begining and at the end of the remote cable.

30-3001-716 Rev G.1Digital logic SignalRemote Connect

Remote Connection Line Termination

Some modules include an integral ground clip. All modules include a screw terminal connection for earth ground. It is important that this connection be made as close to the module as possible.

DM-20 to DIO-20 Data Connection

I/O1 COMM A5General Purpose I/OI/OLocal Cable5 +24 VDC

· Use shielded wire. · Terminate the shield of the wires at one end of the run only - preferably at the end where your I/O module is located. · Be careful when stripping wire not to drop small pieces of wire inside the cabinet. · Don’t run your wiring in the same conduit with AC power. · Don’t run your input wiring in the same conduit with your output wiring.

DIO-20 ConnectionsI/ODirect ConnectModule I/O Bus Pin-OutGrounding the ModulesI/O InstallationCPU

Power Avail. 35 W 50 W 70 W 85 W 50 W

RET

Caution: Earth ground ( ) must be connected to avoid module damage

Page 2 of Andover Controls AC-1, CPU-4M, CPU-8M, DO-4, UI-8 and Schneider UI-8 Manual

The text of page 2, from the PDF itself

DI-6 AC / DI-6-AC-HVMI-6DO-4-R / DO-4-R-OVT-1

AC Digital Input Module

MilliAmp Input ModuleRelay Output ModuleVoice Telecom ModulePolarity IndependentLOADSupplyAC SignalDC SignalIN x

24V Loop-Powered Sensor

IN xINxOUT xSignal

Voltage Range
LOAD

DI-6-ACDI-6-AC-HV

Max Current
20 mA

20-132 Vrms

90-250 Vrms

Voltage Supply to Sensor: 19 - 26V

Contact Rating
DI-8

AO-4-8 / AO-4-8-ODO-6-TRDigital Input ModuleAnalog Output ModuleTriac Output ModuleVoltage OutputDigital logic Signal

5A @ 240 VAC 5A @ 30 VDC

RJ-11 Telephone Line+ ONCurrent OutputEarth GroundOUT 1IN x OUTx IOUTx IIN x Contact Closure

OUTx V Device Load Resistance

RET

³ 2KW

Device Load Resistance £ 650W

OUT xLOADOUTx VCommonFORM AOUT 2GNDGNDON

Using Two Outputs to make FORM K

IN1 IN2 RETIN3 IN4 RETIN5 IN6 RETIN7 IN8 RET

Current Output
0 - 20 mA
Output Rating
24 VAC, 0.5 A (Cannot switch DC Loads)

14710

Voltage Output
0 - 10V
Minimum Load Current
30 mA

2356891112

LO-2 / LO-2-O Lighting Output Module

For more information on these Andover Continuum products, see the I/O Systems Reference, 30-3001-499, and the Power Supply Reference, 30-3001-702. For documentation specific to Underwriters Laboratories (UL) evaluation, see the Note below.

Override Switch Connections

Module External Power Connections 28 VAC Transformer

Momentary Switch

UL 916 Listed product for the United States and Canada, Open Energy Management Equipment.

PWR 24-30 VACOFFONREDGND

UL 294 (Access Control System Unit Subassemblies for the United States) and UL 1076 (Proprietary Burglar Alarm System Unit Subassemblies for the United States) and C22.2 No. 205-M1983 (Signal Equipment for Canada)

BLK

This ground connection must be the same as the ground for the Continuum Power Supply

28 VDC (half-wave rectified AC) to External Sensors

Output Rating
OVERRIDE

Indicator

Lamp Load – 20 Amp Tungsten Filament @125 VAC Resistive Load – 20 Amp Ballast @ 277 VAC (20 amp @347 VAC, Canada) Motor Load – 0.5 Hp @ 110-125 VAC 0.5 HP @ 220-277 VAC (0.5 Hp @ 347 VAC, Canada)

YELWHT28 VAC RECTRED (ON)

External Relay Assy. Connections

Note: Refer to the UL Listed Access Control/Proprietary Burglar Alarm System’s installation manual (the UL294 Access Control and UL 1076 Proprietary Burglar Alarm Systems Reference, 30-3001-504) for specific wiring, operation, and compatibility information.

REDBLK (OFF)BLK OVERRIDEOccupancy Sensor YELWHT (COM)BLU (POWER)WHT28 VAC RECT.

Note: Only these products mentioned in this document are evaluated by UL for UL 294 and UL 1076 applications: UI-8-10 UI -8-10-10V DI-8 (UL294 only) DO-4

© 2011 Schneider Electric All Rights Reserved. Schneider Electric § One High St. § North Andover MA USA 01845