Spec sheet · Andover Controls
Andover Controls AC-1 Spec Sheet
Spec sheet4 pagesPDF 57 KB
All 4 pages are below, each with its text.
Covers · 1 model
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Andover Controls spec sheet for the Continuum AC-1 access control I/O module, which runs one card-access door or portal from a Wiegand reader or keypad. It also covers the AC-1Plus, the full-feature version. It lists the electrical ratings, reader and alarm inputs, relay outputs, indicators and access control features.
- Device
- AC-1: Continuum access control I/O module for one door or portal, mounted near the door or on DIN rail p. 1
- Power
- 10-28 VDC, 2.0 W plus reader power p. 1
- Card reader
- AC-1: one Wiegand swipe or proximity reader, up to 64 bits per card p. 1
- Relay outputs
- Two Form C relays, 5 A at 24 V AC/DC, each with a 3-position manual override switch p. 2
- Alarm inputs
- AC-1: up to 3 supervised inputs, single or double resistor supervision, series or parallel p. 2
- Reader power
- 5 VDC ±3%, 50 mA, current limited p. 2
- Reader cable length
- 500 ft max with 18-ga. wire; 200 ft max with 22-ga. wire p. 2
- Overload protection
- 0.5 A resettable fuse with TVS and reverse polarity protection p. 1
- Output protection
- 5,000 V isolation; 270 V MOVs on each output p. 2
- Reader LED output
- AC-1: open collector, up to 100 mA p. 2
- Connections
- AC-1: two-piece, 18-position removable terminal block p. 2
- Controller
- Access decisions made in the Continuum NetController CPU, up to 75,000 local personnel records p. 1
- AC-1Plus readers
- AC-1Plus: Wiegand, Proximity, CardKey and ABA readers; 64 bits for Wiegand and Proximity, 34 for CardKey p. 4
- AC-1Plus inputs
- AC-1Plus: 5 supervised inputs; removable terminal blocks, two 8-position and one 6-position p. 4
What this sheet walks you through
- Choosing a door operating mode (site code, card, card plus PIN, or keypad) p. 1
- Keeping doors working in degrade mode when the network is down p. 1
- Setting up anti-passback to prevent tailgating p. 1
- Wiring a Wiegand keypad together with or apart from the reader p. 1
- AC-1Plus card formats, ADA doors and reader LED patterns p. 3
Good to know
- Supervised alarm inputs can watch door contacts, request-to-exit devices or a cabinet tamper switch. p. 1
Questions this sheet answers
What voltage does the Andover AC-1 need?
10 to 28 VDC; it draws 2.0 W plus the card reader's power. p. 1
What card readers work with the AC-1?
Wiegand swipe and proximity readers, reading up to 64 bits per card. p. 1
How far can the card reader be from the AC-1?
Up to 500 ft with 18-ga. wire, or 200 ft with 22-ga. wire. p. 2
What are the AC-1 relay ratings?
It has two Form C relays rated 5 A at 24 V AC/DC. p. 2
What does the AC-1Plus add over the AC-1?
CardKey and ABA card reader support, multiple card formats, ADA doors and five supervised input channels. p. 3
The file
Size and text
Every page · 4
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 4
Open in the PDF
The text of page 1, from the PDF itself
AC-1
I/O MODULE
The AC-1, Continuum’s access control module, provides full I/O for an access controlled door or portal in one compact module. The AC-1 can be located near an access controlled door for localized control and reduced wiring costs; or several AC-1 modules can be grouped together and DIN rail-mounted for centralized control. The AC-1 provides a Wiegand card input for Wiegand swipe and proximity type cards, reading up to 64 bits per card. Reader power is 50 mA at 5V. The module itself can be powered by a voltage source that can range from 10-28 VDC. The AC-1 has two 5 A, Form C relays - one for the door lock and a second for local alarm annunciation. Each output has an integral hand-off-auto switch for manual operation, and software feedback of the switch position. Up to three supervised alarm inputs can be used for door status contacts, request-to-exit devices, a cabinet tamper switch, or any other two-state or three-state (on/off/trouble) alarm device.
KEYPAD CONTROL
The AC-1 supports Wiegand output keypads. To simplify installation and reduce wiring costs, a combination Wiegand output reader/keypad may be used. In this case, the keypad data comes into the module via the reader data lines. In addition, the AC-1 allows separate wiring of both a Wiegand output keypad and reader.
ACCESS CONTROL
During normal operation of the AC-1, access decisions are made in the Continuum NetController CPU , which provides storage for up to 75,000 “local” personnel records. In addition, the NetController’s event buffer is software-configurable to allow for the most optimized memory usage. If network communications are interrupted, the AC-1 will revert to a programmable degrade mode of operation, providing uninterrupted card access using site codes and other degrade mode parameters stored in non-volatile EEPROM in each AC-1 module. A door can be configured to operate based on site code only, site code plus card, card plus personal ID number (PIN), or keypad only. The door’s operating mode can even be changed based on time-of-day or other events for optimum flexibility through Andover Controls’ easy-to-use Plain English® programming language. Each keypad can also permit entry of a duress alarm code that can initiate an alarm sequence at any AC-1 controller or at the Continuum workstation. Time-based anti-passback and entry/egress anti-passback are available to prevent tailgating. Entry/egress anti-passback is system-wide and can be performed by readers located on different AC-1 controllers across the network. Using Plain English, the AC-1 can also be used for custom access control sequences such as two-man rule, optical turnstile control, and man trap configurations. SPECIFICATIONS ELECTRICAL
- Power Consumption
- 2.0 W at 10-28VDC plus reader power consumption.
- Overload Protection
- 0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection
INPUTS/OUTPUTSInputs12
- Card Readers
- 1
- Card Reader Type
- Supports Wiegand swipe and proximity readers
- Maximum Number of bits/Card
- 64
Page2of 4
Open in the PDF
The text of page 2, from the PDF itself
AC-1 I/O MODULE CONTINUED
- Card Reader Power
- 5 VDC, ± 3%, 50 mA, Current Limited
- Distance, Card Reader to AC-1
- 500 ft. max. using 18-ga. wire 200 ft. max. using 22-ga. wire
- Alarm Inputs
- Up to 3 supervised inputs. Single or double resistor supervision, series or parallel.
- Input Protection
- Transient voltage suppressor (TVS) on each input
- Outputs Door Outputs
- 2 Form C relays
- Output Rating
- 5 A @ 24 V AC/DC
- Output Protection
- 5,000 V isolation 270 V metal oxide varistors (MOVs) on each output
- Overrides
- 3-position manual override switch on each output for manual control of relay. LED override status indicator.
- Override Feedback
- Override detection and software feedback provided for each output.
- Reader LED Output
- Open collector; up to 100 mA.
- Inputs/Output Connections
- Two-piece, 18-position removable terminal block
USER LEDS/SWITCHES
Status Indicator LEDS Power Comm Override Status Out1 - Out2 +5 V Reader Power Switches Commission Reset
13
Power Indicator TD Indicator Common Override Indicator Service/Wink Indicator Two Output Status Indicators 5 V Reader Power Indicator
Page3of 4
Open in the PDF
The text of page 3, from the PDF itself
AC-1Plus I/O MODULE
The AC-1Plus, Continuum’s full-feature access control module, provides full I/O for an access controlled door or portal in one compact module. The AC-1Plus supports multiple card formats, ADA (Alternate Door Access) doors, and multiple reader LED patterns. In addition, built-in reader supervision is provided - one LED will periodically check for voltage, absence of voltage, or shorts, and expose any of these conditions to the user for security purposes.The AC-1Plus can be located near an access controlled door for localized control and reduced wiring costs; or several AC-1Plus modules can be grouped together and DIN railmounted for centralized control. The AC-1Plus provides a Wiegand card input for Wiegand swipe and proximity type cards, reading up to 64 bits per card. The AC1Plus also supports CardKey cards, reading up to 34 bits per card, and ABA card readers. Card reader power is 50 mA at 5V . The AC-1Plus has two 5 A, Form C relays - one for the door lock and an auxiliary output for local alarm annunciation, for example. Each output has an integral hand-off-auto switch and software feedback of the switch position. The AC-1Plus provides five supervised input channels, configurable as an exit request, door switch sensor, ADA exit request, bond sensor, or as a general purpose supervised input point.
KEYPAD CONTROL
The AC-1Plus supports Wiegand output keypads. To simplify installation and reduce wiring costs, a combination Wiegand output reader/keypad may be used. In this case, the keypad data comes into the module via the reader data lines. In addition, the AC1Plus allows separate wiring of both a Wiegand output keypad and reader.
ACCESS CONTROL
During normal operation of the AC-1Plus, access decisions are made in the Continuum NetController CPU, which provides storage for up to 75,000 “local” personnel records. In addition, the NetController’s event buffer is software-configurable to allow for the most optimized memory usage. If network communications are interrupted, the AC-1Plus will revert to a programmable degrade mode of operation, providing uninterrupted card access using site codes, card formats, and other degrade mode parameters stored in non-volatile EEPROM such as multiple card types (including custom format) and four site codes per each card type. ADA doors are also supported in degrade mode. A door can be configured to operate based on site code only, site code plus card, card only, card plus personal ID number (PIN), or keypad only. The door’s operating mode can even be changed based on time-of-day or other events for optimum flexibility through Andover Controls’ easy-to-use Plain English® programming language. Each keypad can also permit entry of a duress alarm code that can initiate an alarm sequence at any AC-1Plus controller or at the Continuum workstation. Time-based anti-passback and entry/egress anti-passback are available to prevent tailgating. Entry/egress anti-passback is system-wide and can be performed by readers located on different AC-1Plus controllers across the network. Using Plain English, the AC-1Plus can also be used for custom access control sequences such as two-man rule, optical turnstile control, and man trap configurations.
14
Page4of 4
Open in the PDF
The text of page 4, from the PDF itself
A C - 1P L U S I/O MODULE CONTINUED
SPECIFICATIONSELECTRICAL
- Power Consumption
- 2.0 W at 10-28VDC plus reader power consumption.
- Overload Protection
- 0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection
INPUTS/OUTPUTS
- Inputs Card Readers
- 1
- Card Reader Type
- Supports Wiegand, Proximity, CardKey, and ABA readers
- Maximum Number of bits/Card
- 64 for Wiegand and Proximity; 34 for CardKey
- Card Reader Power
- 5 VDC, ± 3%, 50 mA, Current Limited
Distance, Card Reader to AC-1Plus:
500 ft. max. using 18-ga. wire 200 ft. max. using 22-ga. wire
- Alarm Inputs
- 5 supervised inputs. Single or double resistor supervision, series or parallel.
- Input Protection
- Transient voltage suppressor (TVS) on each input
- Outputs Door Outputs
- 2 Form C relays
- Output Rating
- 5 A @ 24 V AC/DC
- Output Protection
- 5,000 V isolation 270 V metal oxide varistors (MOVs) on each output
- Overrides
- 3-position manual override switch on each output. LED override status indicator.
- Override Feedback
- Override detection and software feedback provided for each output.
- Reader LED Outputs
- 2 open collector; up to 100 mA. Choice of 3 LED patterns
- Inputs/Output Connections
- Removable terminal blocks: (2) 8-position; (1) 6-position
USER LEDS/SWITCHES
Status Indicator LEDS Power Comm Override Status Out1 - Out2 +5 V Reader Power Switches Commission Reset
15
Power Indicator TD Indicator Common Override Indicator Service/Wink Indicator Two Output Status Indicators 5 V Reader Power Indicator