Page 1 of Andover Continuum I/O Modules

Manual · Schneider

Andover Continuum I/O Modules

Manual23 pagesPDF 2.8 MB

Data sheet for the Schneider Electric Andover Continuum DIN rail I/O modules, including the UI-8-10, DO-4-R and AC-1 modules.

Download the PDF2.8 MB

Names · 4 models

The models it names

Filed with · 2 models

Also filed with these models on the old site

Summary

What is in it

Schneider Electric's data sheet for the Andover Continuum I/O modules of the Andover Continuum intelligent building system. It describes the shared features (DIN rail or panel mounting, slide-together power and communication connections, RS-485 or FTT-10A media, push-button commissioning), the common specifications and agency listings, and then each module in turn, such as the UI-8-10 universal input, DI, AO, DO-6-TR and DO-4-R output, AC-1Plus access control and VS-8-4 modules, with their own specifications.

From the manual

Key facts from this manual

Each line names its page in the PDF.

Schneider Electric data sheet set for the Andover Continuum I/O modules, used to pick modules for a Continuum controller. It gives the shared specifications (size, communications, mounting) and a spec page per module, including the UI-8-10 / UI-8-10-10V, DI-8, DI-6-AC, MI-6, AO-4-8, DO-6-TR, DO-4-R, DM-20 and the AC-1 access control family.

Read for this summary: pages 1 to 15 of 23.

Module family
Andover Continuum DIN-rail I/O modules; talk to the NetController CPU over Andover LON p. 2
RS-485 bus
39k baud; 2,000 ft. (610m); shielded twisted pair p. 4
FTT-10A bus
78k baud; up to 8858 ft. (2700m) bus topology, 1640 ft (500m) free topology p. 4
Size
3.8 in. W x 7.2 in. H (6.2 in. clips closed) x 2.5 in. D, except VS-8-4 p. 4
Weight
.75 lbs (0.34kg), except VS-8-4 p. 4
Operating environment
32 to 120°F (0 to 49°C), 10 to 95% RH non-condensing p. 4
Mounting
DIN rail or wall mount with attached clips; NEMA 1-style enclosure available p. 4
UI-8-10 inputs
8 universal inputs: voltage, thermistor, digital, counter or supervised; 0-5 V, 10-bit (UI-8-10-10V: 0-10 V) p. 5
UI-8-10 power
0.7 W @ 10-28VDC max. p. 5
UI-8-10 thermistor
10K ohm Type III thermistor, -30 to 230°F (-34 to 110°C) p. 5
UI-8-10 input protection
24 V AC/DC allowed on any single input p. 5
DO-4-R outputs
4 Form C relays, 5 A @ 240 VAC; 5 A @ 30 VDC; DO-4-R-O adds overrides p. 11
DO-4-R power
2.8 W @ 10-28 VDC max. p. 11
AC-1
Access control module: Wiegand/Prox cards, 5 V/12 V reader power, 24VDC power input only p. 13

What this manual walks you through

  • Choosing RS-485 or FTT-10A communication media p. 3
  • UI-8-10 and UI-8-10-10V universal input specifications p. 5
  • DI-8 digital input specifications p. 6
  • DI-6-AC and DI-6-AC-HV AC input specifications p. 7
  • MI-6 milliamp input specifications p. 8
  • AO-4-8 analog output specifications p. 9
  • DO-6-TR triac output specifications p. 10
  • DO-4-R and DO-4-R-O relay output specifications p. 11
  • DM-20 digital I/O with the DIO-20 expansion board p. 12
  • Choosing between the AC-1, AC-1A and AC-1Plus access modules p. 13

Good to know

  • RS-485 and FTT-10A modules cannot be mixed on the same I/O bus. p. 3
  • A remotely mounted RS-485 network needs termination at both ends. p. 4
  • Longer FTT-10A runs need a repeater. p. 4
  • The DI-8 takes 24 VAC/VDC continuous on only four channels. p. 6
  • The DO-6-TR triac outputs cannot switch DC loads. p. 10

Questions this manual answers

What inputs does the Andover UI-8-10 accept?

Eight universal inputs, each set in software as voltage, thermistor, digital or counter, with a 0-5 volt range and 10-bit conversion. p. 5

What is the difference between the UI-8-10 and the UI-8-10-10V?

The UI-8-10-10V has the same point types but a voltage divider DIP switch on each input, so each can be set for 0-10 volts. p. 5

What is the relay rating of the DO-4-R?

Its four Form C relays are rated 5 A @ 240 VAC and 5 A @ 30 VDC. p. 11

What does an AC-1 do if network communications are lost?

It falls back to a programmable degrade mode and keeps granting card access from site codes stored in its EEPROM. p. 14

How far can a card reader be from an AC-1?

500 ft. with 18-gauge wire, or 200 ft. with 22-gauge wire. p. 15

The whole text · 3 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 81-8
  2. Pages 9 to 169-16
  3. Pages 17 to 2317-23

The file

Revision and size

RevisionSDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
PublisherSchneider Electric
Pages23
PDF2.8 MB
TextText from the PDF itself.

The first pages · 3 of 23

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 23
Page 2
Page 2of 23
Page 3
Page 3of 23