Page 17

17

AC-1A I/O Module Specifications

AC-1A Alarm Inputs

User LEDs/Switches

Up to 3 supervised inputs. Single or double

Status Indicator LEDs resistor supervision, series or parallel

Power

Power Indicator

Input Protection

Comm

TD Indicator

Transient voltage suppressor (TVS)

Override

Common Override Indicator on each input Status

Service/Wink

Outputs

Indicator

Door Outputs

Out1 - Out2

Two Output Status Indicators

2 Form C relays

Output Rating

+5 V Reader Power

5 V Reader Power Indicator

5 A @ 24 V AC/DC

Output Protection

Switches

Electrical

5,000 V isolation

Commission

Power Consumption

270 V metal oxide varistors

Reset

2.0 W at 10-28VDC plus reader

(MOVs) on each output power consumption

Overrides

Overload Protection

3-position manual override switch

0.5 A resettable fuse with transient on each output for manual control of relay.

voltage suppressor (TVS) and reverse

LED override status indicator polarity protection

Override Feedback Override detection and software

Inputs feedback provided for each output.

Card Readers

Reader LED Output

1

Open collector; up to 100 mA

Card Reader Type

Inputs/Output Connections

Supports Wiegand swipe and

Two-piece, 18-position removable proximity readers terminal block

Maximum Number of bits/Card 64

Card Reader Power 5 VDC, ± 3%, 50 mA, Current Limited

Distance, Card Reader to AC-1A 500 ft. max. using 18-ga. wire 200 ft. max. using 22-ga. wire

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 18

18

AC-1Plus I/O Module

The AC-1Plus, Andover Continuum’s full-feature access control module, provides full I/O for an access controlled door or portal in one compact module. The AC-1Plus supports multiple card formats, ADA (Alternate Door Access) doors, and multiple reader LED patterns. In addition, builtin reader supervision is provided - one LED will periodically check for voltage, absence of voltage, or shorts, and expose any of these conditions to the user for security purposes.The AC-1Plus can be located near an access controlled door for localized control and reduced wiring costs; or several AC-1Plus modules can be grouped together and DIN rail-mounted for centralized control. The AC-1Plus provides a Wiegand card input for Wiegand swipe and proximity type cards, reading up to 64 bits per card. The AC-1Plus also supports CardKey cards, reading up to 34 bits per card, and ABA card readers. Card reader power is 50 mA at 5V . The AC-1Plus has two 5 A, Form C relays, one for the door lock and an auxiliary output for local alarm annunciation, for example. Each output has an integral hand-off-auto switch and software feedback of the switch position. The AC-1Plus provides five supervised input channels, configurable as an exit request, door switch sensor, ADA exit request, bond sensor, or as a general purpose supervised input point.

Keypad Control The AC-1Plus supports Wiegand or ABA output keypads. To simplify installation and reduce wiring costs, a combination Wiegand (or ABA) output reader/keypad may be used. In this case, the keypad data comes into the module via the reader data lines. In addition, the AC-1Plus allows separate wiring of both a Wiegand (or ABA) output keypad and reader.

Access Control During normal operation of the AC-1Plus, access decisions are made in the Andover Continuum NetController CPU, which provides storage for up to 75,000 “local” personnel records. In addition, the NetController’s event buffer is softwareconfigurable to allow for the most optimized memory usage. If network communications are interrupted, the AC-1Plus will revert to a programmable degrade mode of operation, providing uninterrupted card access using site codes, card formats, and other degrade mode parameters stored in non-volatile EEPROM such as multiple card types (including custom format) and four site codes per each card type. ADA doors are also supported in degrade mode. A door can be configured to operate based on site code only, site code plus card, card only, card plus personal ID number (PIN), or keypad only. The door’s operating mode can even be changed based on time-of-day or other events for optimum flexibility through TAC’s easy-to-use Andover Plain English programming language. Each keypad can also permit entry of a duress alarm code that can initiate an alarm sequence at any AC-1Plus controller or at the Andover Continuum workstation. Time-based anti-passback and entry/egress antipassback are available to prevent tailgating. Entry/ egress anti-passback is system-wide and can be performed by readers located on different AC1Plus controllers across the network. Using Andover Plain English, the AC-1Plus can also be used for custom access control sequences such as two-man rule, optical turnstile control, and man trap configurations.

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 19

19

AC-1Plus I/O Module Specifications

AC-1Plus

Distance, Card Reader to AC-1Plus

User LEDs/Switches

500 ft. max. using 18-ga. wire

Status Indicator LEDs

200 ft. max. using 22-ga. wire

Power

Power Indicator

Alarm Inputs

Comm

TD Indicator

5 supervised inputs. Single or double

Override

Common Override Indicator resistor supervision, series or parallel

Input Protection

Status

Service/Wink Indicator

Transient voltage suppressor (TVS) on each input

Out1 - Out2

Two Output Status Indicators

Outputs

+5 V Reader Power

Door Outputs Electrical Power Consumption 2.2 W at 10-28VDC plus reader power consumption

Overload Protection 0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection

Inputs Card Readers 1

Card Reader Type Supports Wiegand, Proximity, CardKey, and ABA readers

Maximum Number of bits/Card 64 for Wiegand and Proximity; 34 for CardKey

Card Reader Power 5 VDC, ± 3%, 50 mA, Current Limited

Indicator

2 Form C relays

Switches:

Output Rating

Commission

5 A @ 24 V AC/DC

Reset

Output Protection 5,000 V isolation 270 V metal oxide varistors (MOVs) on each output

Overrides 3-position manual override switch on each output. LED override status indicator

Override Feedback Override detection and software feedback provided for each output

Reader LED Outputs 2 open collector; up to 100 mA. Choice of 3 LED patterns

Inputs/Output Connections Removable terminal blocks: (2) 8-position; (1) 6-position

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

5 V Reader Power

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 20

20

LO-2

I/O Module The LO-2, Andover Continuum’s lighting control module, can control 2 high voltage lighting circuits, using externally mounted GE RR7 or RR9 lighting relays, rated for 20 A @ 277 VAC (347 VAC option for Canada). These relays are connected to the LO-2 via two three foot, 5-conductor wires provided. The RR9 relay provides status feedback of the relay position, using a built-in pilot contact. The RR7 relay provides control of the circuit with no feedback. An on-board status LED for each output is provided when RR9 relays are used, as well as pilot light voltage for wall switches that have status indication. External 28 VAC is required to power the GE relays. This same transformer can power the LO-2 when the module is located remotely. An LO-2-O model, with on-board momentary override toggle switches, is also available.

External Override Capabilities Two Class II low voltage manual override inputs, one for each relay output, are provided for override capabilities. These inputs directly control the lighting relays, independent of any schedule or program. Wall switches, occupancy sensors, or a combination of both may be wired to these inputs.

Lighting Control The LO-2 can be coupled with Andover Continuum’s programmable input modules to provide flexible lighting control strategies such as: • Outdoor Lighting Control with a Photocell • Daylight Control • After-Hours Lighting Usage with Card Swipe Readers • Adjustable Override Time with Flick Warning • Cleaning Crew Override • Data Logging and Reporting • Run time Analysis, including Accumulated On-Time and Percentage On-Time • Tenant Billing Reports • Custom Control Strategies These programs can be easily modified to fit the exact needs of your project.

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 21

21

LO-2 I/O Module Specifications

LO-2 Inputs/Outputs

Lighting Relay Connections

Inputs

5-position male connector accepts standard

2 Class II Low Voltage override inputs,

GE female plug-in connector.

providing direct control of lighting relays

(Two 3-foot, 5-conductor wires with female

Input Protection connectors provided. Wires color-coded to

Transient voltage suppressors (TVS)

match GE relays.)

with reverse polarity protection

User LEDs/Switches

Electrical Power Consumption 0.4 W @ 24 VDC max. Consumes no DC power when external AC power is present

External AC Power 28 VAC powers both module and lighting relays; can also power the LO-2 module

Outputs

Status Indicator LEDS

Output Type

Power

Power Indicator

2 pulsed lighting control outputs

Comm

TD Indicator compatible with externally mounted

Status

Service/Wink Indicator

GE RR7 or RR9 relays

Out1-Out2

Two Output Status

Output Rating (Lighting Relay) Lamp Load –

Resistive Load – 20 A ballast @ 277 VAC Motor Load – and associated devices)

Overload Protection DC: 0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection. AC: 0.5 A resettable fuse with MOV

Switches

(@347 VAC, Canada)

Commission

0.5 HP @ 110-125 VAC

Reset

0.5 HP @ 220-277 VAC

External Transformer up to 5 LO-2 modules (10 GE relays

External 24-30 VAC Indicator

@125 VAC when mounted remotely 40 VA transformer provides power for

Indicators (RR-9 only) 24 VAC

20 A Tungsten Filament

(0.5 HP @ 347 VAC,

Models

Canada)

LO-2

Pilot Contact Rating (RR9 only)

2 pulsed lighting control outputs

1 A @ 24 VAC, isolated

LO-2-O

Output Feedback

2 pulsed lighting control outputs

RR9 relays have LED status indication with overrides and software feedback for relay status

Output Protection Transient voltage suppressors (TVS) on outputs. GE relays provide isolation

Overrides Momentary override toggle switches (LO-2-O model only)

AC Power/External Override Input Connections Two-piece, 12-position removable terminal block

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 22

22

VS-8-4 I/O Module

The VS-8-4, Andover Continuum’s video switch module, integrates low-cost, high quality video security directly into your Andover Continuum system. The VS-8-4 switches eight video signal inputs and four high-speed, buffered outputs. Any one of the eight input lines can be connected to any of the four outputs. Each output has a voltage gain of two and is capable of driving 75W backterminated lines. Up to eight surveillance cameras and four video monitors or VCRs can be connected to a single VS-8-4 module. The VS-8-4 can be ordered with optional date/time and caption display. Captions are selectable, allowing different displays based on events or alarms. Both models can be ordered to support either the PAL or NTSC standard.

Specifications All Channel Crosstalk

Models

>-55dB@10MHz

VS-8-4

All Channel Off Isolution

8 Video inputs; 4 Video outputs,

>-55dB@10MHz

NTSC or PAL video inputs

Outputs

VS-8-4-TN

4 Video outputs

8 Video inputs; 4 Video outputs with

Output Impedence date/time- and text-stamping for

75W

NTSC video inputs

Signal

VS-8-4-TP

1 V peak-peak when terminated into 75W

8 Video inputs; 4 Video outputs with

Electrical

Input/Output Connections date/time- and text-stamping for

Power Consumption

75W BNC connectors

PAL video inputs

2 W @ 10-28VDC max.

Input/Output Protection

Overload Protection

ESD protection provided

0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse

User LEDs/Switches polarity protection

Status Indicator LEDs Power

Power Indicator

Inputs/Outputs

Comm

TD Indicator

Inputs

Status

Service/Wink Indicator

8 Video inputs

Input Impedence

Input Status 1-8

Input Status Indicator (4 LEDs per input)

75W

Bandwidth (-3dB)

Switches

>75MHz (Rload=150W)

Commission

Single Channel Crosstalk

Reset

>-60dB@10MHz

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 23

23

VT-1

I/O Module The Andover Continuum VT-1 Interactive Voice Response (IVR) module provides users with easy-touse remote data entry capabilities for their Andover Continuum system using the familiar touch-tone keypad on any North American standard or cellular telephone. The VT-1 also allows spoken messages to be pre-recorded to inform the user of current system conditions and/or to prompt the user for additional input. The VT-1 can be used, for example, to change building setpoints or schedules; arm or disarm alarms; unlock doors; request status or determine operating conditions of equipment; and to report alarm or event conditions or history. The VT-1 provides 10 built-in prompt messages and 50 pre-recorded vocabulary words, which can be used individually or combined to form phrases and sentences. In addition, up to 50 custom messages (up to 3.5 minutes total) can be prerecorded, played, and erased in the VT-1’s Message Management Mode - all over the telephone!

Specifications Electrical

User LEDs/Switches

Power Consumption

Status LEDs

1.5 W @ 24 VDC max.

Power

Overload Protection

Communications

0.5 A resettable fuse with transient

Service/Wink indicator voltage suppressor (TVS) and reverse

Record mode polarity protection

Play mode Erase mode

Inputs/Outputs

Ring

Phone Line Connections

Off-hook

1 RJ-11 connector with SIDAC

Switches and resettable telecom fuses

Commission Reset

All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand changes. Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings June 2006 pdw

© 2006-2009 Schneider Electric. All rights reserved.

Note: VT-1 approved for use in North American phone systems only.