For the Andover Controls AC-1, Andover Controls DO-4, Andover Controls UI-8 and Schneider UI-8
Page 9
09
AO-4-8 I/O Module
The DI-8, Andover Continuum’s digital input module, is used for cost-effective sensing of multiple dry digital inputs in applications such as equipment status monitoring or alarm point monitoring. The DI-8 has eight digital inputs - each can be software configured to accept a digital (contact closure or 0–5 volt input) or counter signal. Counter frequency is 10 Hz on all eight inputs. In addition, high speed counting up to 10KHz max. is available (via a DIP switch) on Channel The AO-4-8, Andover Continuum’s analog output module, has four analog outputs with eight-bit resolution, which can be configured as either voltage (0–10 VDC) or current (0–20 mA) outputs. The AO-4-8 is the perfect choice for valves, dampers, variable speed drives, and similar equipment that demand high control accuracy. An AO-4-8-O model with full override capabilities is also available. Each output contains a threeposition manual override switch and override potentiometer. In addition, the AO-4-8-O provides software override feedback to the Andover Plain English programming language for each output.
Specifications Output Protection
User Leads/Switches
1/8 pico fuse per channel
Status Indicator LEDs
(40V TVS on each output - Power
Power Indicator
AO-4-8-O model only)
Comm
TD Indicator
Output Connections
Override
Common Override Indicator
Two-piece, 13-position removable
Status
Service/Wink Indicator terminal block
Switches
Output Types
Commission
Voltage or current
Reset
Voltage Range: 0–10 VDC
Models
Resolution: 0.05 V
AO-4-8
Accuracy: ±0.10V (1%FSR)
4 Analog outputs
Electrical
Output Current: +5 mA (sourcing)
AO-4-8-O
Power Consumption
-1 mA (sinking)
4 Analog outputs with overrides
3.8 W @ 24 VDC max.
Load Resistance: 2KW .(sourcing, min.)
Overload Protection
Current
0.5 A resettable fuse with transient
Range: 0–20 mA voltage suppressor (TVS) and reverse
Resolution: 0.1 mA polarity protection
Accuracy: ±0.2 mA Load Resistance: 650W (max.)
Outputs
Output Overrides
AO-4-8
3-position manual override switch and
4 Analog outputs; 8 bit resolution override potentiometer on each output,
AO-4-8-O with software feedback. LED override
4 Analog outputs with overrides;
status indicator. (AO-4-8-O only)
8 bit resolution
Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
Telephone: +1 978 975 9600
Fax: +1 978 975 9674 www.schneider-electric.com/buildings
Page 10
10
DO-6-TR I/O Module
The DO-6-TR, Andover Continuum’s triac output module, has six Form A triac-based outputs, rated at 0.5 A @ 24 VAC, for cost-effective on/off or pulsewidth modulation (PWM) control of lighting, heat, and fan units. The PWM feature permits the modulation of valves and dampers to 0.1 second resolution. Adjacent outputs can also be configured in pairs to provide up to three Form K, Tri-state outputs for bidirectional control of dampers and valves. Metal oxide varistors and optocouplers on the DO-6-TR provide 2500V isolation on each output, ensure noise-free operation, and, in most cases, eliminate the need to install MOVs in the field.
Specifications Outputs
User LEDs/Switches
Output Type
Status Indicator LEDs
6 Form A optically isolated triac outputs
Power
Power Indicator
(can be configured up to 3 Form K Tri-State
Comm
TD Indicator outputs)
Status
Service/Wink Indicator
Output Rating
Out1-Out6
Six Output Status
0.5 A @ 24 VAC
Indicators
(Cannot switch DC loads)
Switches
Output Accuracy
Commission
0.1 sec. for Pulse Width Modulation
Reset
(PWM) control
Output Protection 2,500 V optical isolation
Electrical
Metal oxide varistor and snubber
Power Consumption on each output
1.1 W @ 24 VDC max.
Output Connections
Overload Protection
Two-piece, 13-position removable
0.5 A resettable fuse with transient terminal block voltage suppressor (TVS) and reverse polarity protection
Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
Telephone: +1 978 975 9600
Fax: +1 978 975 9674 www.schneider-electric.com/buildings
Page 11
11
DO-4-R I/O Module
The DO-4-R, Andover Continuum’s digital output module, has four Form C relay outputs, rated at 5 A @ 240 VAC. These versatile outputs make the DO-4-R an excellent choice for switching motor starters and other inductive loads up to 240 VAC, with either two position (on/off) or pulse-width modulation (PWM) control. The PWM feature permits the modulation of valves and dampers to 0.1 second resolution. Two adjacent Form C relay outputs can be combined in software to provide a Tri-state output, for bi-directional control of valves and dampers and other end devices. Metal oxide varistors and 5,000 V isolation on each output ensures reliable noise-free operation. A DO-4-R-O model with full override capability is also available. Each output has a local handoff-auto switch, which enables service personnel to override the output. The switch also provides override feedback of the output value for use in troubleshooting or test conditions. A local indicator light for each output displays relay status. Another LED provides override status.
Specifications Outputs
User LEDs/Switches
DO-4-R
Status Indicator LEDs
4 Form C relay outputs
Power
Power Indicator
DO-4-R-O
Comm
TD Indicator
4 Form C relay outputs with overrides
Override
Common Override
Output Rating
Indicator
5 A @ 240 VAC; 5 A @ 30 VDC
Status
Service/Wink Indicator
Output Resolution
Out1-Out4
Four Output Status
0.1 sec. For Pulse Width Modulation
Indicators
(PWM) control
Switches
Output Protection
Commission
270 V varistors across contacts.
Reset
5000 Vrms isolation @ 60 Hz between relay contacts and relay coil
Models
Power Consumption
Output Overrides
DO-4-R
2.8 W @ 10–-28 VDC max.
3-position manual override switch on
4 Form C relay outputs
Overload Protection each output, with software feedback.
DO-4-R-O
0.5 A resettable fuse with transient
LED override status indicator
4 Form C relay outputs with overrides voltage suppressor (TVS) and reverse
(DO-4-R-O only)
polarity protection
Override Feedback
Electrical
Override detection and feedback provided for each output
Output Connections Two-piece, 13-position removable terminal block
Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
Telephone: +1 978 975 9600
Fax: +1 978 975 9674 www.schneider-electric.com/buildings
Page 12
12
DM-20
I/O Module The DM-20, Andover Continuum’s Digital Input and Output module, provides high density, versatile I/O for many control applications. The DM-20 can control any combination of 20 inputs and outputs.
modulation (PWM) control of equipment and for switching inductive loads up to 240VAC. The DM-20 provides 24 VDC power to the DIO-20 via a threeposition cable assembly.
When coupled with the optional DIO-20 Expansion Board, the DM-20 allows you to mix and match up to 20* digital inputs and outputs using standard off-the-shelf digital I/O blocks to meet a wide range of applications, including ON-OFF or pulse-width
* Actual number of modules depends on the mix of inputs/outputs used. See Andover Continuum I /O System Reference Manual (Rev D or higher) for more information.
Specifications Inputs/Outputs
Output Resolution:
0.1 sec. For Pulse
20 total points; user-selectable
Width Modulation channel-by-channel as inputs or
(PWM) control Output Protection:
outputs w/o DIO-20
Transient voltage suppressor (TVS)
Input Type:
Digital 0–5 VDC and current limiting
Pulse Width:
125 ms ( min.)
resistor on each channel
(Digital pulse widths are
Input/Output based on Scan Time.)
Connections:
One female 25-pin
Current:
10µA
D-subminiature
Output Type:
Digital connector
Open-collector transistor with series 330 ohm 1/8 W
User LEDs/Switches
Electrical resistor; 15 mA (max.)
Status Indicator LEDs
Power Consumption
@ 5 V DC
Power Power Indicator
0.5 W @ 24VDC max.
w/DIO-20
Up to 9 W @ 24 VDC when the
Input Type:
Comm TD Indicator 24 VDC logic voltage
Status Service/Wink Indicator
DIO-20 is powered from the DM-20
(DIO-20). Input rating
Switches
External Power Connector depends on input
Commission module(s) selected
Reset
Three-position removable connector
Overload Protection
Pulse Width:
125 ms ( min.)
0.5 A resettable fuse with transient voltage
(Digital pulse widths are suppressor (TVS) and reverse polarity based on Scan Time.)
protection for both DM-20 power and
Current:
N/A
DIO-20 power
Output Type:
5 VDC logic voltage.
LED Power Supply
Output range depends on
Customer-provided external 5 V power output module selected supply when using the DM-20 to drive LEDs
Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
Telephone: +1 978 975 9600
Fax: +1 978 975 9674 www.schneider-electric.com/buildings
Page 13
13
AC-1 Family Family of Access Control Modules
TAC® offers three access control modules to meet the demands of different access requirements: AC-1: Use the AC-1 when powering modules from a Andover Continuum power supply. (AC-1 has a 24VDC power input only. ) The AC-1 supports Wiegand/Prox cards and 5 V/12 V reader power (switch-selectable).
AC-1A: Use the AC-1A if you are powering modules from a local 12VDC power supply. The AC-1A offers an extended 10-28VDC power input. (Power supply can also power any 12 V prox readers you may be using.) The AC-1A supports Wiegand/Prox cards, and 5 V reader power only.
AC-1PLUS: The enhanced version. Use the AC-1Plus when using mag stripe or Cardkey readers, ADA sequences that require extra inputs, special door unlock/door ajar times for disabled persons, and jobs that require reader tamper detection. The AC-1Plus offers an extended 10-28VDC power input (power supply can also power 12 V prox readers), and supports 5 V reader power only.
Page 14
14
AC-1
I/O Module The AC-1provides full I/O for an access controlled door or portal in one compact module. The AC-1 can be located near an access controlled door for localized control and reduced wiring costs; or several AC-1 modules can be grouped together and DIN rail-mounted for centralized control. The AC-1 provides a Wiegand card input for Wiegand swipe and proximity type cards, reading up to 64 bits per card. Reader power is switchselectable between 5V and 12V to meet most card reader power requirements. The AC-1 has two 5 A, Form C relays - one for the door lock and a second for local alarm annunciation. Each output has an integral handoff-auto switch for manual operation, and software feedback of the switch position. Up to three supervised alarm inputs can be used for door status contacts, request-to-exit devices, a cabinet tamper switch, or any other two-state or three-state (on/off/trouble) alarm device.
Keypad Control The AC-1 supports Wiegand output keypads. To simplify installation and reduce wiring costs, the keypad data comes into the module via the reader data lines.
Access Control During normal operation of the AC-1, access decisions are made in the Andover Continuum NetController CPU , which provides storage for up to 75,000 “local” personnel records. In addition, the NetController’s event buffer is software-configurable to allow for the most optimized memory usage. If network communications are interrupted, the AC-1 will revert to a programmable degrade mode of operation, providing uninterrupted card access using site codes and other degrade mode parameters stored in non-volatile EEPROM in each AC-1 module. A door can be configured to operate based on site code only, site code plus card, card plus personal ID number (PIN), or keypad only. The door’s operating mode can even be changed based on time-of-day or other events for optimum flexibility through TAC’s easy-to-use Andover Plain English programming language. Each keypad can also permit entry of a duress alarm code that can initiate an alarm sequence at any AC-1 controller or at the Andover Continuum workstation. Time-based anti-passback and entry/egress antipassback are available to prevent tailgating. Entry/ egress anti-passback is system-wide and can be performed by readers located on different AC-1 controllers across the network. Using Andover Plain English, the AC-1 can also be used for custom access control sequences such as two-man rule, optical turnstile control, and man trap configurations.
Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
Telephone: +1 978 975 9600
Fax: +1 978 975 9674 www.schneider-electric.com/buildings
Page 15
15
AC-1 Specifications
AC-1 Distance, Card Reader to AC-1
User LEDs/Switches
500 ft. max. using 18-ga. wire
Status Indicator LEDs
200 ft. max. using 22-ga. wire
Power
Power Indicator
Alarm Inputs
Comm
TD Indicator
Up to 3 supervised inputs. Single or double
Override
Common Override Indicator resistor supervision, series or parallel
Input Protection
Status
Service/Wink Indicator
Transient voltage suppressor (TVS)
Out1 - Out2
Two Output Status Indicators on each input +5 V Reader Power
Outputs
5 V Reader Power Indicator
Door Outputs
+12 V Reader Power 12 V Reader Power Indicator
2 Form C relays
Electrical
Output Rating
Switches
Power Consumption
5 A @ 24 V AC/DC
Commission
2.6 W plus reader power consumption
Output Protection
Reset at 24VDC max.
5,000 V isolation
Overload Protection
270 V metal oxide varistors (MOVs)
0.5 A resettable fuse with transient on each output voltage suppressor (TVS) and reverse
Overrides polarity protection
3-position manual override switch on each output for manual control of relay.
Inputs
LED override status indicator
Card Readers
Override Feedback
1
Override detection and software
Card Reader Type feedback provided for each output
Supports Wiegand swipe and
Reader LED Output proximity readers
Open collector; up to 50 mA
Maximum Number of bits/Card
Inputs/Output Connections
64
Two-piece, 16-position removable
Card Reader Power terminal block
5 VDC or 12 VDC (switch selectable) Switch Setting:
+5 V
Output Voltage:
+5.20 V ±0.05 V
Output Current:
120 mA (max.)
Switch Setting:
+12 V
Output Voltage:
+12.0 V ±5%
Output Current:
180 mA (max.)
Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
Telephone: +1 978 975 9600
Fax: +1 978 975 9674 www.schneider-electric.com/buildings
Page 16
16
AC-1A
I/O Module The AC-1Plus, Andover Continuum’s full-feature access control module, provides full I/O for an access controlled door or portal in one compact module. The AC-1Plus supports multiple card formats, ADA (Alternate Door Access) doors, and multiple reader LED patterns. In addition, builtin reader supervision is provided - one LED will periodically check for voltage, absence of voltage, or shorts, and expose any of these conditions to the user for security purposes. The AC-1Plus can be located near an access controlled door for localized control and reduced wiring costs; or several AC-1Plus modules can be grouped together and DIN rail-mounted for centralized control. The AC-1Plus provides a Wiegand card input for Wiegand swipe and proximity type cards, reading up to 64 bits per card. The AC-1Plus also supports CardKey cards, reading up to 34 bits per card, and ABA card readers. Card reader power is 50 mA at 5V . The AC-1Plus has two 5 A, Form C relays, one for the door lock and an auxiliary output for local alarm annunciation, for example. Each output has an integral hand-off-auto switch and software feedback of the switch position. The AC-1Plus provides five supervised input channels, configurable as an exit request, door switch sensor, ADA exit request, bond sensor, or as a general purpose supervised input point.
Keypad Control The AC-1Plus supports Wiegand or ABA output keypads. To simplify installation and reduce wiring costs, a combination Wiegand (or ABA) output reader/keypad may be used. In this case, the keypad data comes into the module via the reader data lines. In addition, the AC-1Plus allows separate wiring of both a Wiegand (or ABA) output keypad and reader.
Access Control During normal operation of the AC-1A, access decisions are made in the Andover Continuum NetController CPU , which provides storage for up to 75,000 “local” personnel records. In addition, the NetController’s event buffer is software-configurable to allow for the most optimized memory usage. If network communications are interrupted, the AC-1A will revert to a programmable degrade mode of operation, providing uninterrupted card access using site codes and other degrade mode parameters stored in non-volatile EEPROM in each AC-1A module. A door can be configured to operate based on site code only, site code plus card, card plus personal ID number (PIN), or keypad only. The door’s operating mode can even be changed based on time-of-day or other events for optimum flexibility through TAC’s easy-to-use Andover Plain EnglishTM programming language. Each keypad can also permit entry of a duress alarm code that can initiate an alarm sequence at any AC-1A controller or at the Andover Continuum workstation. Time-based anti-passback and entry/egress anti-passback are available to prevent tailgating. Entry/egress anti-passback is system-wide and can be performed by readers located on different AC-1A controllers across the network. Using Andover Plain English, the AC-1A can also be used for custom access control sequences such as two-man rule, optical turnstile control, and man trap configurations.
Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC