Page 9

09

AO-4-8 I/O Module

The DI-8, Andover Continuum’s digital input module, is used for cost-effective sensing of multiple dry digital inputs in applications such as equipment status monitoring or alarm point monitoring. The DI-8 has eight digital inputs - each can be software configured to accept a digital (contact closure or 0–5 volt input) or counter signal. Counter frequency is 10 Hz on all eight inputs. In addition, high speed counting up to 10KHz max. is available (via a DIP switch) on Channel The AO-4-8, Andover Continuum’s analog output module, has four analog outputs with eight-bit resolution, which can be configured as either voltage (0–10 VDC) or current (0–20 mA) outputs. The AO-4-8 is the perfect choice for valves, dampers, variable speed drives, and similar equipment that demand high control accuracy. An AO-4-8-O model with full override capabilities is also available. Each output contains a threeposition manual override switch and override potentiometer. In addition, the AO-4-8-O provides software override feedback to the Andover Plain English programming language for each output.

Specifications Output Protection

User Leads/Switches

1/8 pico fuse per channel

Status Indicator LEDs

(40V TVS on each output - Power

Power Indicator

AO-4-8-O model only)

Comm

TD Indicator

Output Connections

Override

Common Override Indicator

Two-piece, 13-position removable

Status

Service/Wink Indicator terminal block

Switches

Output Types

Commission

Voltage or current

Reset

Voltage Range: 0–10 VDC

Models

Resolution: 0.05 V

AO-4-8

Accuracy: ±0.10V (1%FSR)

4 Analog outputs

Electrical

Output Current: +5 mA (sourcing)

AO-4-8-O

Power Consumption

-1 mA (sinking)

4 Analog outputs with overrides

3.8 W @ 24 VDC max.

Load Resistance: 2KW .(sourcing, min.)

Overload Protection

Current

0.5 A resettable fuse with transient

Range: 0–20 mA voltage suppressor (TVS) and reverse

Resolution: 0.1 mA polarity protection

Accuracy: ±0.2 mA Load Resistance: 650W (max.)

Outputs

Output Overrides

AO-4-8

3-position manual override switch and

4 Analog outputs; 8 bit resolution override potentiometer on each output,

AO-4-8-O with software feedback. LED override

4 Analog outputs with overrides;

status indicator. (AO-4-8-O only)

8 bit resolution

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 10

10

DO-6-TR I/O Module

The DO-6-TR, Andover Continuum’s triac output module, has six Form A triac-based outputs, rated at 0.5 A @ 24 VAC, for cost-effective on/off or pulsewidth modulation (PWM) control of lighting, heat, and fan units. The PWM feature permits the modulation of valves and dampers to 0.1 second resolution. Adjacent outputs can also be configured in pairs to provide up to three Form K, Tri-state outputs for bidirectional control of dampers and valves. Metal oxide varistors and optocouplers on the DO-6-TR provide 2500V isolation on each output, ensure noise-free operation, and, in most cases, eliminate the need to install MOVs in the field.

Specifications Outputs

User LEDs/Switches

Output Type

Status Indicator LEDs

6 Form A optically isolated triac outputs

Power

Power Indicator

(can be configured up to 3 Form K Tri-State

Comm

TD Indicator outputs)

Status

Service/Wink Indicator

Output Rating

Out1-Out6

Six Output Status

0.5 A @ 24 VAC

Indicators

(Cannot switch DC loads)

Switches

Output Accuracy

Commission

0.1 sec. for Pulse Width Modulation

Reset

(PWM) control

Output Protection 2,500 V optical isolation

Electrical

Metal oxide varistor and snubber

Power Consumption on each output

1.1 W @ 24 VDC max.

Output Connections

Overload Protection

Two-piece, 13-position removable

0.5 A resettable fuse with transient terminal block voltage suppressor (TVS) and reverse polarity protection

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 11

11

DO-4-R I/O Module

The DO-4-R, Andover Continuum’s digital output module, has four Form C relay outputs, rated at 5 A @ 240 VAC. These versatile outputs make the DO-4-R an excellent choice for switching motor starters and other inductive loads up to 240 VAC, with either two position (on/off) or pulse-width modulation (PWM) control. The PWM feature permits the modulation of valves and dampers to 0.1 second resolution. Two adjacent Form C relay outputs can be combined in software to provide a Tri-state output, for bi-directional control of valves and dampers and other end devices. Metal oxide varistors and 5,000 V isolation on each output ensures reliable noise-free operation. A DO-4-R-O model with full override capability is also available. Each output has a local handoff-auto switch, which enables service personnel to override the output. The switch also provides override feedback of the output value for use in troubleshooting or test conditions. A local indicator light for each output displays relay status. Another LED provides override status.

Specifications Outputs

User LEDs/Switches

DO-4-R

Status Indicator LEDs

4 Form C relay outputs

Power

Power Indicator

DO-4-R-O

Comm

TD Indicator

4 Form C relay outputs with overrides

Override

Common Override

Output Rating

Indicator

5 A @ 240 VAC; 5 A @ 30 VDC

Status

Service/Wink Indicator

Output Resolution

Out1-Out4

Four Output Status

0.1 sec. For Pulse Width Modulation

Indicators

(PWM) control

Switches

Output Protection

Commission

270 V varistors across contacts.

Reset

5000 Vrms isolation @ 60 Hz between relay contacts and relay coil

Models

Power Consumption

Output Overrides

DO-4-R

2.8 W @ 10–-28 VDC max.

3-position manual override switch on

4 Form C relay outputs

Overload Protection each output, with software feedback.

DO-4-R-O

0.5 A resettable fuse with transient

LED override status indicator

4 Form C relay outputs with overrides voltage suppressor (TVS) and reverse

(DO-4-R-O only)

polarity protection

Override Feedback

Electrical

Override detection and feedback provided for each output

Output Connections Two-piece, 13-position removable terminal block

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 12

12

DM-20

I/O Module The DM-20, Andover Continuum’s Digital Input and Output module, provides high density, versatile I/O for many control applications. The DM-20 can control any combination of 20 inputs and outputs.

modulation (PWM) control of equipment and for switching inductive loads up to 240VAC. The DM-20 provides 24 VDC power to the DIO-20 via a threeposition cable assembly.

When coupled with the optional DIO-20 Expansion Board, the DM-20 allows you to mix and match up to 20* digital inputs and outputs using standard off-the-shelf digital I/O blocks to meet a wide range of applications, including ON-OFF or pulse-width

* Actual number of modules depends on the mix of inputs/outputs used. See Andover Continuum I /O System Reference Manual (Rev D or higher) for more information.

Specifications Inputs/Outputs

Output Resolution:

0.1 sec. For Pulse

20 total points; user-selectable

Width Modulation channel-by-channel as inputs or

(PWM) control Output Protection:

outputs w/o DIO-20

Transient voltage suppressor (TVS)

Input Type:

Digital 0–5 VDC and current limiting

Pulse Width:

125 ms ( min.)

resistor on each channel

(Digital pulse widths are

Input/Output based on Scan Time.)

Connections:

One female 25-pin

Current:

10µA

D-subminiature

Output Type:

Digital connector

Open-collector transistor with series 330 ohm 1/8 W

User LEDs/Switches

Electrical resistor; 15 mA (max.)

Status Indicator LEDs

Power Consumption

@ 5 V DC

Power Power Indicator

0.5 W @ 24VDC max.

w/DIO-20

Up to 9 W @ 24 VDC when the

Input Type:

Comm TD Indicator 24 VDC logic voltage

Status Service/Wink Indicator

DIO-20 is powered from the DM-20

(DIO-20). Input rating

Switches

External Power Connector depends on input

Commission module(s) selected

Reset

Three-position removable connector

Overload Protection

Pulse Width:

125 ms ( min.)

0.5 A resettable fuse with transient voltage

(Digital pulse widths are suppressor (TVS) and reverse polarity based on Scan Time.)

protection for both DM-20 power and

Current:

N/A

DIO-20 power

Output Type:

5 VDC logic voltage.

LED Power Supply

Output range depends on

Customer-provided external 5 V power output module selected supply when using the DM-20 to drive LEDs

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 13

13

AC-1 Family Family of Access Control Modules

TAC® offers three access control modules to meet the demands of different access requirements: AC-1: Use the AC-1 when powering modules from a Andover Continuum power supply. (AC-1 has a 24VDC power input only. ) The AC-1 supports Wiegand/Prox cards and 5 V/12 V reader power (switch-selectable).

AC-1A: Use the AC-1A if you are powering modules from a local 12VDC power supply. The AC-1A offers an extended 10-28VDC power input. (Power supply can also power any 12 V prox readers you may be using.) The AC-1A supports Wiegand/Prox cards, and 5 V reader power only.

AC-1PLUS: The enhanced version. Use the AC-1Plus when using mag stripe or Cardkey readers, ADA sequences that require extra inputs, special door unlock/door ajar times for disabled persons, and jobs that require reader tamper detection. The AC-1Plus offers an extended 10-28VDC power input (power supply can also power 12 V prox readers), and supports 5 V reader power only.

Page 14

14

AC-1

I/O Module The AC-1provides full I/O for an access controlled door or portal in one compact module. The AC-1 can be located near an access controlled door for localized control and reduced wiring costs; or several AC-1 modules can be grouped together and DIN rail-mounted for centralized control. The AC-1 provides a Wiegand card input for Wiegand swipe and proximity type cards, reading up to 64 bits per card. Reader power is switchselectable between 5V and 12V to meet most card reader power requirements. The AC-1 has two 5 A, Form C relays - one for the door lock and a second for local alarm annunciation. Each output has an integral handoff-auto switch for manual operation, and software feedback of the switch position. Up to three supervised alarm inputs can be used for door status contacts, request-to-exit devices, a cabinet tamper switch, or any other two-state or three-state (on/off/trouble) alarm device.

Keypad Control The AC-1 supports Wiegand output keypads. To simplify installation and reduce wiring costs, the keypad data comes into the module via the reader data lines.

Access Control During normal operation of the AC-1, access decisions are made in the Andover Continuum NetController CPU , which provides storage for up to 75,000 “local” personnel records. In addition, the NetController’s event buffer is software-configurable to allow for the most optimized memory usage. If network communications are interrupted, the AC-1 will revert to a programmable degrade mode of operation, providing uninterrupted card access using site codes and other degrade mode parameters stored in non-volatile EEPROM in each AC-1 module. A door can be configured to operate based on site code only, site code plus card, card plus personal ID number (PIN), or keypad only. The door’s operating mode can even be changed based on time-of-day or other events for optimum flexibility through TAC’s easy-to-use Andover Plain English programming language. Each keypad can also permit entry of a duress alarm code that can initiate an alarm sequence at any AC-1 controller or at the Andover Continuum workstation. Time-based anti-passback and entry/egress antipassback are available to prevent tailgating. Entry/ egress anti-passback is system-wide and can be performed by readers located on different AC-1 controllers across the network. Using Andover Plain English, the AC-1 can also be used for custom access control sequences such as two-man rule, optical turnstile control, and man trap configurations.

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 15

15

AC-1 Specifications

AC-1 Distance, Card Reader to AC-1

User LEDs/Switches

500 ft. max. using 18-ga. wire

Status Indicator LEDs

200 ft. max. using 22-ga. wire

Power

Power Indicator

Alarm Inputs

Comm

TD Indicator

Up to 3 supervised inputs. Single or double

Override

Common Override Indicator resistor supervision, series or parallel

Input Protection

Status

Service/Wink Indicator

Transient voltage suppressor (TVS)

Out1 - Out2

Two Output Status Indicators on each input +5 V Reader Power

Outputs

5 V Reader Power Indicator

Door Outputs

+12 V Reader Power 12 V Reader Power Indicator

2 Form C relays

Electrical

Output Rating

Switches

Power Consumption

5 A @ 24 V AC/DC

Commission

2.6 W plus reader power consumption

Output Protection

Reset at 24VDC max.

5,000 V isolation

Overload Protection

270 V metal oxide varistors (MOVs)

0.5 A resettable fuse with transient on each output voltage suppressor (TVS) and reverse

Overrides polarity protection

3-position manual override switch on each output for manual control of relay.

Inputs

LED override status indicator

Card Readers

Override Feedback

1

Override detection and software

Card Reader Type feedback provided for each output

Supports Wiegand swipe and

Reader LED Output proximity readers

Open collector; up to 50 mA

Maximum Number of bits/Card

Inputs/Output Connections

64

Two-piece, 16-position removable

Card Reader Power terminal block

5 VDC or 12 VDC (switch selectable) Switch Setting:

+5 V

Output Voltage:

+5.20 V ±0.05 V

Output Current:

120 mA (max.)

Switch Setting:

+12 V

Output Voltage:

+12.0 V ±5%

Output Current:

180 mA (max.)

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 16

16

AC-1A

I/O Module The AC-1Plus, Andover Continuum’s full-feature access control module, provides full I/O for an access controlled door or portal in one compact module. The AC-1Plus supports multiple card formats, ADA (Alternate Door Access) doors, and multiple reader LED patterns. In addition, builtin reader supervision is provided - one LED will periodically check for voltage, absence of voltage, or shorts, and expose any of these conditions to the user for security purposes. The AC-1Plus can be located near an access controlled door for localized control and reduced wiring costs; or several AC-1Plus modules can be grouped together and DIN rail-mounted for centralized control. The AC-1Plus provides a Wiegand card input for Wiegand swipe and proximity type cards, reading up to 64 bits per card. The AC-1Plus also supports CardKey cards, reading up to 34 bits per card, and ABA card readers. Card reader power is 50 mA at 5V . The AC-1Plus has two 5 A, Form C relays, one for the door lock and an auxiliary output for local alarm annunciation, for example. Each output has an integral hand-off-auto switch and software feedback of the switch position. The AC-1Plus provides five supervised input channels, configurable as an exit request, door switch sensor, ADA exit request, bond sensor, or as a general purpose supervised input point.

Keypad Control The AC-1Plus supports Wiegand or ABA output keypads. To simplify installation and reduce wiring costs, a combination Wiegand (or ABA) output reader/keypad may be used. In this case, the keypad data comes into the module via the reader data lines. In addition, the AC-1Plus allows separate wiring of both a Wiegand (or ABA) output keypad and reader.

Access Control During normal operation of the AC-1A, access decisions are made in the Andover Continuum NetController CPU , which provides storage for up to 75,000 “local” personnel records. In addition, the NetController’s event buffer is software-configurable to allow for the most optimized memory usage. If network communications are interrupted, the AC-1A will revert to a programmable degrade mode of operation, providing uninterrupted card access using site codes and other degrade mode parameters stored in non-volatile EEPROM in each AC-1A module. A door can be configured to operate based on site code only, site code plus card, card plus personal ID number (PIN), or keypad only. The door’s operating mode can even be changed based on time-of-day or other events for optimum flexibility through TAC’s easy-to-use Andover Plain EnglishTM programming language. Each keypad can also permit entry of a duress alarm code that can initiate an alarm sequence at any AC-1A controller or at the Andover Continuum workstation. Time-based anti-passback and entry/egress anti-passback are available to prevent tailgating. Entry/egress anti-passback is system-wide and can be performed by readers located on different AC-1A controllers across the network. Using Andover Plain English, the AC-1A can also be used for custom access control sequences such as two-man rule, optical turnstile control, and man trap configurations.

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings