Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 1 of 3

Andover Continuum I/O Modules, pages 1 to 8

Pages 1 to 8 of 23

The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Andover Controls AC-1, Andover Controls DO-4, Andover Controls UI-8 and Schneider UI-8

Page 1

Andover Continuum I/O Modules

The Andover Continuum intelligent building system allows you to mix and match various combinations of DIN rail-mounted modules, flexible I/O, CPU and power supply, and your choice of several user interface modules, in a single controller location to meet your building’s control and monitoring needs.

TM

Page 2

02

Andover Continuum I/O Modules Features

With the Andover Continuum system, as your network grows, simply add or replace I/O modules as needed. The Andover Continuum I/O modules feature a sleek, lightweight casing designed for natural convection cooling, and a 3-position front cover for easy access. Built-in quick-release fasteners at the back of each I/O module are provided for DIN rail mounting, no tools required. These fasteners also snap into a locked position for panel mounting. Input and output connectors are located at the bottom of each I/O module and are removable for easy field access and maintenance. All Andover Continuum modules are designed for mounting in an optional NEMA 1-style Andover Continuum enclosure.

Product AT A GLANCE • Flexible, Modular Design Fits Every Application • User-Configurable I/O Selection to Meet Specific Control Needs • DIN Rail Mounting Provides Easy Installation and System Expansion • NEMA 1-Style Enclosure Available • Three-Position Front Cover for Easy Access • Built-in Quick-Release Fasteners - No Tools Required! • Removable Input/Output Connectors for Easy Installation

The Andover Continuum I/O modules communicate with the Andover Continuum NetController CPU module using Andover LON communications. Like all Andover Continuum modules, the I/O modules slide together via built-in connectors on either side so network expansion is quick and easy. Both power transmission and communication signals feed through these connectors. For added convenience, in applications such as door control or lighting control, a single module or groups of I/O modules can be remotely located and connected using approved cable, and powered from a local power supply. Each I/O module features its own push-button for quick and easy network commissioning.

• Slide-Together Power/Communications Connections • Optional Remote Mounting • Push-Button Network Commissioning • Choice of RS-485 or FTT-10A Media

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 3

03

Andover Continuum I/O Modules Features (continued)

Communication Choices

Dimension Drawings

All Andover Continuum modules are available in either the standard RS-485 or the Free Topology (FTT-10A) media interface. RS-485 is perfect for local mounting applications and is a lower cost media choice. FTT-10A provides increased flexibility and reliability. FTT modules are connected using a twisted-pair cable and can be wired in a bus, star, distributed star, or even a ring topology for added resilience. Note: You cannot mix and match both media types on the same I/O bus.

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 4

04

Andover Continuum I/O Modules Specifications

N1831

I/O Modules Mechanical

Battery Backup

CPU

Operating Environment

Via Andover Continuum

3120E2 MCU with internal ROM,

32–120°F (0 to 49°C),

UPS power supply

EEPROM, and SRAM

10–95%RH (non-condensing)

Except VT-1 and AC-1Plus:

Size*

Communications

3150BFU1 with internal EEPROM

3.8˝ W (96.5mm) including connectors

Communications Interface:

and external FLASH and SRAM

7.2˝ H (182.88mm) with mounting

TAC-LON communications with clips extended

Andover Continuum CPU module

Agency Listings

6.2˝ H (157.48mm) with mounting

Choice of RS-485 or FTT-10A interface

UL/CUL 916, FCC CFR 47 Part 15, clips closed

Comm. Error Checking

ICES-003, EN55022,

2.5˝ D (96.5 x 170.2 x 63.5mm)

International Standard CRC 16

AS/NZS 3548, and VCCI Class A,

*With the exception of the VS-8-4 models –

RS-485

CE UL 864 - (UI-8-10-S, DI-8-S, MI-6-S,

9.0˝ W x7.2˝ H (6.2˝ H closed) x 2.5˝ D

Communications Speed: 39k baud

AO-4-8-S, DO-6-TR-S, DO-4-R-S,

(228.7 x 182.88mm (157.48 mm closed)

Bus Length: 2,000 ft. (610m)

DM-20-S, DO-4-R-O-S, UI-8-10-10V-S, x 63.5mm)

Bus Media: Shielded, twisted pair cable and AO-4-8-0-S only)

Weight*

120v termination required at both ends

UL 294 - (UI-8-10, DI-8, DO-4-R, DM-20,

.75 lbs (0.34kg)

of the ACC-LON network (when modules

AC-1, AC-1Plus, AC-1A, UI-8-10-10V,

*With the exception of the VS-8-4 models – are mounted remotely)

DO-4-R-O, VS-8-4, and VS-8-4-T only)

1.32lbs (0.60kg)

FTT-10A

UL-1076 - (UI-8-10, UI-8-10-10V, DO-4-R,

Enclosure Type

Communications Speed: 78k baud

DO-4-R-O, AC-1, AC-1a, and AC-1Plus only)

UL open class,

Bus Length: Up to 8858 ft. (2700m) – flammability rating of UL94-5V, IP 10 bus topology

Mounting

Up to 1640 ft (500m) – free topology

Mount on DIN rail or wall-mount

Repeater required for longer distances using attached clips.

Bus Media: Refer to FTT-10A

Andover Continuum NEMA 1-style documentation in Andover Continuum enclosure available

I/O System Reference Guide (P/N: 30-3001-4999--Rev D or higher)

Power/Communications Connections 5-position plug-in connectors on left and right sides allow Andover Continuum modules to be directly connected to each other or remotely connected via approved cable

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 5

05

UI-8-10 I/O Module

The UI-8-10, Andover Continuum’s universal input module, provides 8 universal inputs, software configurable as voltage, thermistor, digital, or counter point types. Each point can also be configured as a supervised input for security monitoring, providing separate indication of alarm and trouble conditions. This module is a perfect choice for any mix of temperature, pressure, flow, status points, and similar inputs in a control system, with a 0–5 volt input range and 10-bit A/D conversion. A UI-8-10-10V model is also available for 0–10 volt applications. It provides the identical point type selection, but is equipped with individual voltage divider DIP switches on each input, allowing each to be configured for a 0-10 volt range.

Specifications Input Impedance

Digital & Counter

UI-8-10 (0–5V): 5 MW w/pullup disabled;

Input Type: Contact Closure

10 KW w/pullup enabled

Frequency: 4 Hz (max.)

UI-8-10-10V (0–10V): 4.4 KW

Pulse Width: 125 ms ( min.)

Input Connections

(Digital pulse widths are based

Two-piece, 13-position removable on Scan Time.)

terminal block

Supervised

Voltage

Input Type: Single or Double Resistor

UI-8-10 (0–5V)

Supervision, Parallel or Series Circuit

Range:

0–5 V

Resolution:

5 mV

User LEDs/Switches

Accuracy:

±15 mV (±0.3% FSR)

Status Indicator LEDs

UI-8-10-10V (0–10V)

Power Power Indicator

Electrical

Range:

0–10 V

Comm TD Indicator

Power Consumption

Resolution:

10 mV

Status Service/Wink Indicator

0.7 W @ 10-28VDC max.

Accuracy:

±15 mV V (±0.4% FSR)

Push-Button Switches

Overload Protection

Thermistor

0.5 A resettable fuse with transient

UI-8-10 (0–5V)

Commission

Reset voltage suppressor (TVS) and reverse

Type:

10 KW, Type III Thermistor

Models polarity protection.

Range:

-30 to 230°F

UI-8-10

(-34 to 110°C)

8 Universal inputs; 0-5 Volt input range

40 to 100°F range

UI-8-10-10V

(4 to 38°C)

8 Universal inputs; 0-10 Volt input range

Inputs

Resolution:

Number of Inputs 8 Universal inputs; 10 bit resolution

Accuracy:

40 to 100°F range (4 to 38°C)

Input Types Voltage, Thermistor, Digital, Counter, and

UI-8-10-10V (0–10V)

Supervised

Type:

10 KW, Type III Thermistor

Input Protection

Range:

-30 to 230°F (-34 to 110°C)

24 V AC/DC allowed to any single input (40V TVS on each input – UI-8-10-10V

Resolution: Accuracy:

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

0.20°F typical (0.11°C typical)

model only)

±1.0°F (±0.55°C)

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 6

06

DI-8

I/O Module The DI-8, Andover Continuum’s digital input module, is used for cost-effective sensing of multiple dry digital inputs in applications such as equipment status monitoring or alarm point monitoring. The DI-8 has eight digital inputs - each can be software configured to accept a digital (contact closure or 0–5 volt input) or counter signal. Counter frequency is 10 Hz on all eight inputs. In addition, high speed counting up to 10KHz max. is available (via a DIP switch) on Channels 1 and 2 for high-speed metering and industrial applications. 40 V bipolar transorbs on all eight inputs protect against high voltage short duration transient events. The DI-8 is designed to accept dry contact inputs or 0-5 volts, but can withstand up to 24 VAC/VDC continuous voltage on four channels.

Specifications

Counter: Inputs

Input Type: Contact closure

Number of Inputs:

or 0–5 VDC input

8 Digital inputs

Channels 1 and 2 in HI-speed mode

Input Types

(selectable via dip switch):

Digital or Counter, software selectable

Frequency: 10kHz (max.)

Input Protection

Pulse Width: 50 µS (min.)

24 V AC/DC applied to 4 channels max.

Current:

0.5 mA

(40V TVS on each input)

Channels 3 through 8; and Channel

Input Impedance

1 and 2 in LO-speed mode:

10KW pull-up resistor referenced to +5

Frequency: 10 Hz (max.)

VDC

Pulse Width: 50 mS (min.)

Inputs Connections

Currrent:

0.5 mA

Two-piece, 13-position removable

Electrical terminal block

User leads/Switches

Power Consumption

Digital

Status Indicator LEDs

0.8 W @ 10–28 VDC max.

Input Type: Contact closure or 0–5V input

Power

Power Indicator

Overload Protection

Pulse Width: 50 ms ( min.)

Comm

TD Indicator

0.5 A resettable fuse with transient

Current: 0.5mA (max.)

Status

Service/Wink Indicator voltage suppressor (TVS) and reverse Input Status 1–8 polarity protection

Input Status Indicator (Closed circuit=ON)

Switches Commission Reset

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 7

07

DI-6-AC I/O Module

The DI-6-AC, Andover Continuum’s digital AC input module, has six digital (“wet”) AC inputs for costeffective ON-OFF status indication of fan motor starters, solenoid valves, control relays, or external power supplies, and similar applications that require a quick and easy way to detect voltage. The DI-6AC monitors the absence or presence of AC or DC voltage levels directly, with no interposing relays needed. The DI-6-AC can monitor voltages from 24–120V. A DI-6-AC-HV model is also available for sensing higher voltages - 120–240V. Both models can also accept DC voltages. All inputs are optically coupled with 2500V isolation on each input for noise-free operation.

Specifications Input Connections

DC Input Voltage Range: 90–250 V

Two-piece, 13-position removable

DC Input Current:

terminal block

DC Voltage “ON” Threshold: 90 V

DI-6-AC

(Above this voltage is considered “ON”)

AC Inputs

DC Voltage “OFF” Threshold: 45 V

AC Input Range: 20–132 Vrms

(Below this voltage is considered “OFF”)

2 mA (max.)

AC Input Current: 5 mA (max.) AC Voltage “ON” Threshold: 16 Vrms

User leads/Switches

(Above this voltage is considered “ON”)

Status Indicator LEDs

AC Voltage “OFF” Threshold: 8 Vrms

Power

(Below this voltage is considered “OFF”)

Comm TD Indicator

Input Resistance (±5%): 30KW

Status

Power Indicator Service/Wink

Maximum Turn ON Time: 20 ms

Indicator

Electrical

Maximum Turn OFF Time: 60 ms

Input Status 1–:6

Input Status Indicator

Power Consumption

DC Input Voltage Range: 20–132 V

(Above voltage

0.7 W @ 24 VDC (max).; when provided by

DC Input Current:

5 mA (max.)

threshold = ON)

Andover Continuum power supply module

DC Voltage “ON” Threshold: 20 V

Switches

Overload Protection

(Above this voltage is considered “ON”)

Commission

0.5 A re-settable fuse with transient

DC Voltage “OFF” Threshold: 12 V

Reset voltage suppressor (TVS) and reverse

(Below this voltage is considered “OFF”)

polarity protection

DI-6-AC-HV

Models

AC Inputs:

DI-6-AC

Inputs

AC Input Range:

90–250 Vrms

6 Digital AC Inputs, 24–120 V input signal

Number of Inputs

AC Input Current:

2 mA (max.)

DI-6-AC-HV

6 Digital AC or DC voltage inputs

AC Voltage “ON” Threshold: 75 Vrms

Input Protection

(Above this voltage is considered “ON”)

2500 V isolation on each input.

AC Voltage “OFF” Threshold: 30 Vrms

Each input has a 270 V metal

(Below this voltage is considered “OFF”)

oxide varistor (MOV.)

Input Resistance (±5%): 200KW

6 Digital AC Inputs, 120–240 V input signal

Maximum Turn ON Time: 20 ms Maximum Turn OFF Time: 60 ms

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600

Fax: +1 978 975 9674 www.schneider-electric.com/buildings

Page 8

08

MI-6

I/O Module The MI-6, Andover Continuum’s milliamp input module, allows for a direct connection of a 2-wire 0–20mA or 4–20mA sensor to any of the module’s six inputs. The need for an external resistor and an external power supply is eliminated. The MI-6 module is a perfect match for temperature transmitters, humidity and pressure transducers, gas monitors, and other industry-standard sensors with either a 0–20mA or 4–20mA output. The six inputs on the MI-6 module have a 0-20mA range and 10 bit A/D conversion.

Specifications Inputs

User Leads/Switches

Number of Inputs

Status Indicator LEDs

6 Milliamp inputs

Power Power Indicator

Input Range

Comm TD Indicator

0–20 mA

Status Service/Wink Indicator

Resolution

Switches

20 µA

Commission

Accuracy

Reset

±80 µA (max.)

Drift ±50ppm/DegC (max.)

Input Resistance 249W, 0.1%

Electrical Power Consumption 3.8 W @ 24 VDC max. (Including up to 20mA sensor power for each input)

Overload Protection 0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection

Maximum Input Current ±30 mA

Voltage Supply to Sensors 19–26 VDC

Input Protection Each input: A transient voltage suppressor (TVS) and a resettable fuse. Sensor voltage output: TVS and resettable fuse

Input Connections Two-piece, 13-position removable terminal block

Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC

Telephone: +1 978 975 9600