The text of a manual · part 1 of 3
Andover Continuum I/O Modules, pages 1 to 8
Pages 1 to 8 of 23
The original document is the PDF (2.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Andover Controls AC-1, Andover Controls DO-4, Andover Controls UI-8 and Schneider UI-8
Page 1
Andover Continuum I/O Modules
The Andover Continuum intelligent building system allows you to mix and match various combinations of DIN rail-mounted modules, flexible I/O, CPU and power supply, and your choice of several user interface modules, in a single controller location to meet your building’s control and monitoring needs.
TM
Page 2
02
Andover Continuum I/O Modules Features
With the Andover Continuum system, as your network grows, simply add or replace I/O modules as needed. The Andover Continuum I/O modules feature a sleek, lightweight casing designed for natural convection cooling, and a 3-position front cover for easy access. Built-in quick-release fasteners at the back of each I/O module are provided for DIN rail mounting, no tools required. These fasteners also snap into a locked position for panel mounting. Input and output connectors are located at the bottom of each I/O module and are removable for easy field access and maintenance. All Andover Continuum modules are designed for mounting in an optional NEMA 1-style Andover Continuum enclosure.
Product AT A GLANCE • Flexible, Modular Design Fits Every Application • User-Configurable I/O Selection to Meet Specific Control Needs • DIN Rail Mounting Provides Easy Installation and System Expansion • NEMA 1-Style Enclosure Available • Three-Position Front Cover for Easy Access • Built-in Quick-Release Fasteners - No Tools Required! • Removable Input/Output Connectors for Easy Installation
The Andover Continuum I/O modules communicate with the Andover Continuum NetController CPU module using Andover LON communications. Like all Andover Continuum modules, the I/O modules slide together via built-in connectors on either side so network expansion is quick and easy. Both power transmission and communication signals feed through these connectors. For added convenience, in applications such as door control or lighting control, a single module or groups of I/O modules can be remotely located and connected using approved cable, and powered from a local power supply. Each I/O module features its own push-button for quick and easy network commissioning.
• Slide-Together Power/Communications Connections • Optional Remote Mounting • Push-Button Network Commissioning • Choice of RS-485 or FTT-10A Media
Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
Telephone: +1 978 975 9600
Fax: +1 978 975 9674 www.schneider-electric.com/buildings
Page 3
03
Andover Continuum I/O Modules Features (continued)
Communication Choices
Dimension Drawings
All Andover Continuum modules are available in either the standard RS-485 or the Free Topology (FTT-10A) media interface. RS-485 is perfect for local mounting applications and is a lower cost media choice. FTT-10A provides increased flexibility and reliability. FTT modules are connected using a twisted-pair cable and can be wired in a bus, star, distributed star, or even a ring topology for added resilience. Note: You cannot mix and match both media types on the same I/O bus.
Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
Telephone: +1 978 975 9600
Fax: +1 978 975 9674 www.schneider-electric.com/buildings
Page 4
04
Andover Continuum I/O Modules Specifications
N1831
I/O Modules Mechanical
Battery Backup
CPU
Operating Environment
Via Andover Continuum
3120E2 MCU with internal ROM,
32–120°F (0 to 49°C),
UPS power supply
EEPROM, and SRAM
10–95%RH (non-condensing)
Except VT-1 and AC-1Plus:
Size*
Communications
3150BFU1 with internal EEPROM
3.8˝ W (96.5mm) including connectors
Communications Interface:
and external FLASH and SRAM
7.2˝ H (182.88mm) with mounting
TAC-LON communications with clips extended
Andover Continuum CPU module
Agency Listings
6.2˝ H (157.48mm) with mounting
Choice of RS-485 or FTT-10A interface
UL/CUL 916, FCC CFR 47 Part 15, clips closed
Comm. Error Checking
ICES-003, EN55022,
2.5˝ D (96.5 x 170.2 x 63.5mm)
International Standard CRC 16
AS/NZS 3548, and VCCI Class A,
*With the exception of the VS-8-4 models –
RS-485
CE UL 864 - (UI-8-10-S, DI-8-S, MI-6-S,
9.0˝ W x7.2˝ H (6.2˝ H closed) x 2.5˝ D
Communications Speed: 39k baud
AO-4-8-S, DO-6-TR-S, DO-4-R-S,
(228.7 x 182.88mm (157.48 mm closed)
Bus Length: 2,000 ft. (610m)
DM-20-S, DO-4-R-O-S, UI-8-10-10V-S, x 63.5mm)
Bus Media: Shielded, twisted pair cable and AO-4-8-0-S only)
Weight*
120v termination required at both ends
UL 294 - (UI-8-10, DI-8, DO-4-R, DM-20,
.75 lbs (0.34kg)
of the ACC-LON network (when modules
AC-1, AC-1Plus, AC-1A, UI-8-10-10V,
*With the exception of the VS-8-4 models – are mounted remotely)
DO-4-R-O, VS-8-4, and VS-8-4-T only)
1.32lbs (0.60kg)
FTT-10A
UL-1076 - (UI-8-10, UI-8-10-10V, DO-4-R,
Enclosure Type
Communications Speed: 78k baud
DO-4-R-O, AC-1, AC-1a, and AC-1Plus only)
UL open class,
Bus Length: Up to 8858 ft. (2700m) – flammability rating of UL94-5V, IP 10 bus topology
Mounting
Up to 1640 ft (500m) – free topology
Mount on DIN rail or wall-mount
Repeater required for longer distances using attached clips.
Bus Media: Refer to FTT-10A
Andover Continuum NEMA 1-style documentation in Andover Continuum enclosure available
I/O System Reference Guide (P/N: 30-3001-4999--Rev D or higher)
Power/Communications Connections 5-position plug-in connectors on left and right sides allow Andover Continuum modules to be directly connected to each other or remotely connected via approved cable
Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
Telephone: +1 978 975 9600
Fax: +1 978 975 9674 www.schneider-electric.com/buildings
Page 5
05
UI-8-10 I/O Module
The UI-8-10, Andover Continuum’s universal input module, provides 8 universal inputs, software configurable as voltage, thermistor, digital, or counter point types. Each point can also be configured as a supervised input for security monitoring, providing separate indication of alarm and trouble conditions. This module is a perfect choice for any mix of temperature, pressure, flow, status points, and similar inputs in a control system, with a 0–5 volt input range and 10-bit A/D conversion. A UI-8-10-10V model is also available for 0–10 volt applications. It provides the identical point type selection, but is equipped with individual voltage divider DIP switches on each input, allowing each to be configured for a 0-10 volt range.
Specifications Input Impedance
Digital & Counter
UI-8-10 (0–5V): 5 MW w/pullup disabled;
Input Type: Contact Closure
10 KW w/pullup enabled
Frequency: 4 Hz (max.)
UI-8-10-10V (0–10V): 4.4 KW
Pulse Width: 125 ms ( min.)
Input Connections
(Digital pulse widths are based
Two-piece, 13-position removable on Scan Time.)
terminal block
Supervised
Voltage
Input Type: Single or Double Resistor
UI-8-10 (0–5V)
Supervision, Parallel or Series Circuit
Range:
0–5 V
Resolution:
5 mV
User LEDs/Switches
Accuracy:
±15 mV (±0.3% FSR)
Status Indicator LEDs
UI-8-10-10V (0–10V)
Power Power Indicator
Electrical
Range:
0–10 V
Comm TD Indicator
Power Consumption
Resolution:
10 mV
Status Service/Wink Indicator
0.7 W @ 10-28VDC max.
Accuracy:
±15 mV V (±0.4% FSR)
Push-Button Switches
Overload Protection
Thermistor
0.5 A resettable fuse with transient
UI-8-10 (0–5V)
Commission
Reset voltage suppressor (TVS) and reverse
Type:
10 KW, Type III Thermistor
Models polarity protection.
Range:
-30 to 230°F
UI-8-10
(-34 to 110°C)
8 Universal inputs; 0-5 Volt input range
40 to 100°F range
UI-8-10-10V
(4 to 38°C)
8 Universal inputs; 0-10 Volt input range
Inputs
Resolution:
Number of Inputs 8 Universal inputs; 10 bit resolution
Accuracy:
40 to 100°F range (4 to 38°C)
Input Types Voltage, Thermistor, Digital, Counter, and
UI-8-10-10V (0–10V)
Supervised
Type:
10 KW, Type III Thermistor
Input Protection
Range:
-30 to 230°F (-34 to 110°C)
24 V AC/DC allowed to any single input (40V TVS on each input – UI-8-10-10V
Resolution: Accuracy:
Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
0.20°F typical (0.11°C typical)
model only)
±1.0°F (±0.55°C)
Telephone: +1 978 975 9600
Fax: +1 978 975 9674 www.schneider-electric.com/buildings
Page 6
06
DI-8
I/O Module The DI-8, Andover Continuum’s digital input module, is used for cost-effective sensing of multiple dry digital inputs in applications such as equipment status monitoring or alarm point monitoring. The DI-8 has eight digital inputs - each can be software configured to accept a digital (contact closure or 0–5 volt input) or counter signal. Counter frequency is 10 Hz on all eight inputs. In addition, high speed counting up to 10KHz max. is available (via a DIP switch) on Channels 1 and 2 for high-speed metering and industrial applications. 40 V bipolar transorbs on all eight inputs protect against high voltage short duration transient events. The DI-8 is designed to accept dry contact inputs or 0-5 volts, but can withstand up to 24 VAC/VDC continuous voltage on four channels.
Specifications
Counter: Inputs
Input Type: Contact closure
Number of Inputs:
or 0–5 VDC input
8 Digital inputs
Channels 1 and 2 in HI-speed mode
Input Types
(selectable via dip switch):
Digital or Counter, software selectable
Frequency: 10kHz (max.)
Input Protection
Pulse Width: 50 µS (min.)
24 V AC/DC applied to 4 channels max.
Current:
0.5 mA
(40V TVS on each input)
Channels 3 through 8; and Channel
Input Impedance
1 and 2 in LO-speed mode:
10KW pull-up resistor referenced to +5
Frequency: 10 Hz (max.)
VDC
Pulse Width: 50 mS (min.)
Inputs Connections
Currrent:
0.5 mA
Two-piece, 13-position removable
Electrical terminal block
User leads/Switches
Power Consumption
Digital
Status Indicator LEDs
0.8 W @ 10–28 VDC max.
Input Type: Contact closure or 0–5V input
Power
Power Indicator
Overload Protection
Pulse Width: 50 ms ( min.)
Comm
TD Indicator
0.5 A resettable fuse with transient
Current: 0.5mA (max.)
Status
Service/Wink Indicator voltage suppressor (TVS) and reverse Input Status 1–8 polarity protection
Input Status Indicator (Closed circuit=ON)
Switches Commission Reset
Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
Telephone: +1 978 975 9600
Fax: +1 978 975 9674 www.schneider-electric.com/buildings
Page 7
07
DI-6-AC I/O Module
The DI-6-AC, Andover Continuum’s digital AC input module, has six digital (“wet”) AC inputs for costeffective ON-OFF status indication of fan motor starters, solenoid valves, control relays, or external power supplies, and similar applications that require a quick and easy way to detect voltage. The DI-6AC monitors the absence or presence of AC or DC voltage levels directly, with no interposing relays needed. The DI-6-AC can monitor voltages from 24–120V. A DI-6-AC-HV model is also available for sensing higher voltages - 120–240V. Both models can also accept DC voltages. All inputs are optically coupled with 2500V isolation on each input for noise-free operation.
Specifications Input Connections
DC Input Voltage Range: 90–250 V
Two-piece, 13-position removable
DC Input Current:
terminal block
DC Voltage “ON” Threshold: 90 V
DI-6-AC
(Above this voltage is considered “ON”)
AC Inputs
DC Voltage “OFF” Threshold: 45 V
AC Input Range: 20–132 Vrms
(Below this voltage is considered “OFF”)
2 mA (max.)
AC Input Current: 5 mA (max.) AC Voltage “ON” Threshold: 16 Vrms
User leads/Switches
(Above this voltage is considered “ON”)
Status Indicator LEDs
AC Voltage “OFF” Threshold: 8 Vrms
Power
(Below this voltage is considered “OFF”)
Comm TD Indicator
Input Resistance (±5%): 30KW
Status
Power Indicator Service/Wink
Maximum Turn ON Time: 20 ms
Indicator
Electrical
Maximum Turn OFF Time: 60 ms
Input Status 1–:6
Input Status Indicator
Power Consumption
DC Input Voltage Range: 20–132 V
(Above voltage
0.7 W @ 24 VDC (max).; when provided by
DC Input Current:
5 mA (max.)
threshold = ON)
Andover Continuum power supply module
DC Voltage “ON” Threshold: 20 V
Switches
Overload Protection
(Above this voltage is considered “ON”)
Commission
0.5 A re-settable fuse with transient
DC Voltage “OFF” Threshold: 12 V
Reset voltage suppressor (TVS) and reverse
(Below this voltage is considered “OFF”)
polarity protection
DI-6-AC-HV
Models
AC Inputs:
DI-6-AC
Inputs
AC Input Range:
90–250 Vrms
6 Digital AC Inputs, 24–120 V input signal
Number of Inputs
AC Input Current:
2 mA (max.)
DI-6-AC-HV
6 Digital AC or DC voltage inputs
AC Voltage “ON” Threshold: 75 Vrms
Input Protection
(Above this voltage is considered “ON”)
2500 V isolation on each input.
AC Voltage “OFF” Threshold: 30 Vrms
Each input has a 270 V metal
(Below this voltage is considered “OFF”)
oxide varistor (MOV.)
Input Resistance (±5%): 200KW
6 Digital AC Inputs, 120–240 V input signal
Maximum Turn ON Time: 20 ms Maximum Turn OFF Time: 60 ms
Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
Telephone: +1 978 975 9600
Fax: +1 978 975 9674 www.schneider-electric.com/buildings
Page 8
08
MI-6
I/O Module The MI-6, Andover Continuum’s milliamp input module, allows for a direct connection of a 2-wire 0–20mA or 4–20mA sensor to any of the module’s six inputs. The need for an external resistor and an external power supply is eliminated. The MI-6 module is a perfect match for temperature transmitters, humidity and pressure transducers, gas monitors, and other industry-standard sensors with either a 0–20mA or 4–20mA output. The six inputs on the MI-6 module have a 0-20mA range and 10 bit A/D conversion.
Specifications Inputs
User Leads/Switches
Number of Inputs
Status Indicator LEDs
6 Milliamp inputs
Power Power Indicator
Input Range
Comm TD Indicator
0–20 mA
Status Service/Wink Indicator
Resolution
Switches
20 µA
Commission
Accuracy
Reset
±80 µA (max.)
Drift ±50ppm/DegC (max.)
Input Resistance 249W, 0.1%
Electrical Power Consumption 3.8 W @ 24 VDC max. (Including up to 20mA sensor power for each input)
Overload Protection 0.5 A resettable fuse with transient voltage suppressor (TVS) and reverse polarity protection
Maximum Input Current ±30 mA
Voltage Supply to Sensors 19–26 VDC
Input Protection Each input: A transient voltage suppressor (TVS) and a resettable fuse. Sensor voltage output: TVS and resettable fuse
Input Connections Two-piece, 13-position removable terminal block
Schneider Electric One High Street, North Andover, MA 01845 USA SDS-C-IOMODULES-US.BU.N.EN.6.2006.0.00.CC
Telephone: +1 978 975 9600
Fax: +1 978 975 9674 www.schneider-electric.com/buildings