Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of Andover Controls i2-867 Spec Sheet

Spec sheet · Andover Controls

Andover Controls i2-867 Spec Sheet

Spec sheet4 pagesPDF 226 KB

All 4 pages are below, each with its text.

Download the PDF226 KB

Covers · 1 model

The models it covers

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

This is the Andover Controls data sheet for the Infinet II (i2) 867 Terminal Controller, a compact DDC controller for package units, heat pumps, unit ventilators and other terminal units. It describes the inputs and outputs, Flash memory, Smart Sensor interface, Infinet RS-485 communications and specifications.

Device
Compact DDC terminal controller for package units, heat pumps, unit ventilators and other terminal units p. 1
Inputs
Four universal inputs (voltage, digital on/off, counter up to 4Hz, temperature) plus a fifth input for the Smart Sensor or a standard room temperature sensor p. 1
Universal input range
Temperature -30°F to 230°F (-34°C to 110°C); current input (0 - 20 mA) with an external 250 ohm resistor p. 3
Outputs
Five Form A Triac outputs (any two consecutive can form a Form K tri-state output, 2 max) and two 0-10V analog outputs p. 2
Network
Infinet RS-485 field bus to a network controller, 1200 to 19.2K baud; up to 254 Infinet devices per network controller p. 1, 3
Bus length and media
4,000 ft. (1,220m) standard; twisted, shielded pair, low capacitance cable; CRC 16 error checking p. 3
Compatibility
Infinet and Infinet II controllers; Continuum CyberStation and Infinity SX 8000 front-ends p. 1
Memory
Flash memory holds the operating system and application programs; operating system upgrades by software download p. 1
Battery
Replaceable, non-rechargeable lithium battery; about 5 years typical accumulated backup of RAM p. 3
Programming
Plain English language, entered from Continuum CyberStation, Infinity SX 8000 Workstation or a local user terminal p. 2
Smart Sensor
Built-in connection; the sensor has a 2-character LED display and 6-button programmable keypad (an LCD version is also offered) p. 2
Status LEDs
CPU, TD and RD; RESET switch and an input pull-up resistor switch per input p. 3
Option
i2867-S: UL864 Smoke Control System Equipment, UUKL p. 3

What this sheet walks you through

  • Programming the controller in Plain English and copying programs between units p. 2
  • Configuring two Triac outputs as a Form K output for dampers and valves p. 2
  • Dimensional, power and communications, inputs, and outputs/Smart Sensor drawings p. 2

Good to know

  • The Triac outputs are rated for AC loads only; DC loads are not permitted. p. 2, 3
  • An i2 Infilink module extends the bus and is required after every group of 32 units on the network. p. 3
  • The data sheet lists agency listings UL/CUL 916, FCC CFR 47 Part 15, ICES-003, EN55022, AS/NZS 3548, VCCI Class A and CE. p. 3

Questions this sheet answers

How many inputs and outputs does the Andover i2867 have?

Four universal inputs plus a Smart Sensor input, five Form A Triac outputs and two 0-10V analog outputs. p. 1, 2

What happens to the i2867 program after a power loss?

The operating system and programs are kept in Flash memory and restored when power returns; an on-board battery protects point and log data. p. 1

Can the i2867 Triac outputs switch DC loads?

No. The outputs are rated for AC loads only. p. 2

Is the i2867 compatible with Continuum?

Yes. It works with both the Continuum CyberStation and Infinity SX 8000 front-ends over the Infinet RS-485 field bus. p. 1

The file

Size and text

Pages4
PDF226 KB
TextText from the PDF itself.

Every page · 4

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Andover Controls i2-867 Spec Sheet

The text of page 1, from the PDF itself

INFINET

II

867 Terminal Controller

  • Compact Terminal Controller Provides Low-cost DDC Control of Package Units, Heat Pumps, Unit Ventilators
  • Compatible with Both Continuum and Infinity Systems
  • Universal Inputs with Form A, Form K, and Analog Outputs for Flexible Control Options
  • Non-Volatile Flash Memory Provides Utmost Reliability, Stores Both Application Program and Operating System
  • Flash Memory Allows Easy On-Line Software Updates
  • Modular, Sleek Design Simplifies Installation in Small Areas
  • View and Modify Information with Optional Andover Smart Sensor Display
  • Local On-Board Service Port

The Infinet II (i2) 867 is a compact terminal controller that provides lowcost DDC control of package units, heat pumps, unit ventilators, and other terminal unit applications. Its versatile mix of I/O, Universal inputs, Triac outputs, plus an interface to Andover Controls’ Smart Sensor room temperature sensor with programmable keypad, allows for flexible control solutions. The i2867 also features two analog outputs to control reheat valves, dampers, lighting ballasts, etc. And because the i2867 is enclosed in a sleek, modular casing, it can be mounted in a small area, perfect for retrofit applications. Similar to all i2 controllers, the i2867 features Flash memory, increased user memory, and a fast (32-bit) processor for faster scan times, with plenty of additional memory available for data logging of your critical data. The i2867 communicates with the entire Andover Controls Infinet™ RS-485 field bus; i.e., both Infinet and Infinet II controllers, and is compatible with both the Continuum CyberStation and Infinity SX 8000 front-ends. Up to 254 Infinet devices can be networked to any Andover network controller.

INCREASED RELIABILITY WITH FLASH MEMORY The i2867’s non-volatile Flash memory stores your operating system and application programs, so that in the event of a power loss, your application will be restored when power is returned. In additon, the Flash memory allows for easy upgrades of your operating system via software downloads, eliminating the need to swap out proms. The i2867 includes an on-board battery to safeguard your runtime data, protecting all point data and log data from being lost if power is removed. INPUTS The input configuration on the i2867 consists of four full range Universal inputs that accept voltage (0-5VDC), digital (on/off), counter signals (up to 4Hz), or temperature signals. The i2867 also offers a fifth input to support the Andover Smart Sensor, or any standard room temperature sensor.

WE'RE BUILDING SMART

Page 2 of Andover Controls i2-867 Spec Sheet

The text of page 2, from the PDF itself

OUTPUTS The i2867 contains five Form A Triac-based outputs. Each Triac is ground referenced. These outputs can be used separately for on/off or pulsed control of lighting, heat, and fan units or be configured into Form K Tri-state outputs (2-max) for bi-directional control of dampers and valves, with a free Triac output remaining. (Note: Any two consecutive Triac outputs can be configured as a Form K output.) Outputs are rated for AC loads only. The i2867 also offers two (0-10V) analog outputs. SOFTWARE CAPABILITIES The dynamic memory of the i2867 can be allocated for any combination of programs, scheduling, alarming, and data logging using the powerful Andover Controls Plain English® programming language. Our object-oriented Plain English language with intuitive keywords provides an easy method to tailor the controller to meet your exact requirements. Programs are entered into the i2867 using the Continuum CyberStation, Infinity SX 8000 Workstation, or local user terminal. Programs are then stored in, and executed by, the i2867. Programming multiple i2867s is inherently easy with Plain English. A complete copy of one i2867’s programs can be loaded directly into other i2867s without changing any point names or programs. In addition, channel assignments for the i2867 are similar to other Infinet devices such as the i2865 for easy program conversion. SMART SENSOR INTERFACE The i2867 provides a built-in connection for Andover’s Smart Sensor. The Smart Sensor provides a 2-character LED display and a 6-button programmable keypad that enables operators and occupants to change setpoints, balance VAV boxes, monitor occupancy status, and turn equipment on and off. An enhanced version of the Smart Sensor is also available with a 4-digit custom LCD that provides the following icons: PM, %, °, Setpoint, Cool, Heat, CFM, Fan, OA, and SP.

123 Dimensional Drawing1

Power and Communications Drawing

2Inputs Drawing3

Outputs/Smart Sensor Drawing

Page 3 of Andover Controls i2-867 Spec Sheet

The text of page 3, from the PDF itself

S P E C I F I C AT I O N S 867 Terminal Controller

INPUTS/OUTPUTS (CONTINUED)

ELECTRICAL Power: Power Consumption: Overload Protection: Software Real-Time Clock:

24 VAC, +10% -15%, 50/60 Hz 4 VA Fused with 2 amp fuse. MOV protected. Synchronized through Infinet by network controller

Outputs:

Output Rating: For SPST:

MECHANICAL Operating Environment: Size: Weight: Enclosure Type: Mounting:

32°–120°F (0–49°C), 10–95% RH (noncondensing) 6.20"H x 3.50”W x 2.50"D (157H x 89W x 64) mm 0.64 lbs. (0.29 kg) UL Open class, IP 10. Flammability rating of UL94-5V Din-rail or panel mount

BATTERY Battery Backup:

For 0-10V:

Output Accuracy: For SPST: For 0-10V:

Power/Communications: Inputs: Outputs/Smart Sensor:

Communications Interface: Through Infinet RS-485 field bus to network controller Communications Speed: 1200 to 19.2K baud Bus Length: 4,000 ft. (1,220m) standard for Infinet, i2 Infilink module allows extension to longer distances and is required after every group of 32 units on the network. Bus Media: Infinet: twisted, shielded pair, low capacitance cable Comm. Error Checking: International Standard CRC 16 Continuum CyberStation and Infinity SX Compatibility: 8000 systems

Service Port
INPUTS/OUTPUTS

GENERAL

Input Voltage Range: Input Impedance: Input Protection:

Input Resolution: Input Accuracy:

Maximum 0.5A, 24VAC, ±2000V transients (Tested according to EN61000-4-4) Minimum: 20 mA AC Each Triac is ground referenced, DC loads not permitted. 5 mA maximum, 2K ohm minimum impedance, ±1000V transients (Tested according to EN61000-4-4) 0.1 sec. for pulse width modulation 50 mV resolution/100mV accuracy

CONNECTIONS Replaceable, non-rechargeable, lithium battery. Provides 5 years typical accumulated power failure backup of RAM memory.

COMMUNICATIONS

Inputs
5 single pole single throw (SPST) Form A Triacs (any two consecutive outputs can be configured as one Tri-state Form K) 2 analog outputs (0-10V)

4 Universal inputs: Voltage (0-5.115 VDC); Temperature -30°F to 230°F (-34°C to 110°C), Digital (on/off), Counter (up to 4Hz at 50% duty cycle, 125 ms min. pulse width). Current input (0 - 20 mA) using external 250 ohm resistor 1 Smart Sensor Temperature Input (32°F to 105°F) (0°C to 41°C) 0-5.115 volts DC 10K ohm to 5.120V or 5M ohm with pullup resistor disabled 24 VAC or 24 VDC temporarily on any single channel, ±1000V transients (Tested according to EN61000-4-4) 5.0 mV ±15mV (±0.56°C from -23°C to +66°C or ±1°F from -10°F to +150°F)

5-position removeable screw terminal connector 5-position removeable screw terminal connector 16-position removeable screw terminal connector 4-position shrouded connector

USER LEDS/SWITCHES Status Indicator LEDS: CPU TD RD

CPU Active Transmit Data Receive Data

Switches: RESET Input Pull-up Resistor Switch (per input)

Memory: Processor
128K SRAM, 1MB FLASH Motorola 32-bit Coldfire

AGENCY LISTINGS UL/CUL 916, FCC CFR 47 Part 15, ICES-003, EN55022, AS/NZS 3548, and VCCI Class A, CE

OPTIONS UL864, Smoke Control System Equipment, UUKL (i2867-S)

Page 4 of Andover Controls i2-867 Spec Sheet

The text of page 4, from the PDF itself

Andover Controls Corp. World Headquarters 300 Brickstone Square Andover, Massachusetts 01810 USA Tel: +1 978 470 0555 Fax: +1 978 470 0946 Andover Controls Europe Smisby Road Ashby-de-la-Zouch Leicestershire LE65 2UG England Tel: +44 1530 417733 Fax: +44 1530 415436 Andover Controls Germany Am Seerhein 8 D-78467 Konstanz Germany Tel: +49 7531 99370 Fax: +49 7531 993710 Andover Controls France Immeuble Dolomites 2 58 Rue Roger Salengro 94126 Fontenay Sous Bois, France Tel: +33 1 53 99 16 16 Fax: +33 1 53 99 16 15 Andover Controls Poland Radzikowskiego 56 31-315 Krakow Poland Tel: +48 126385500 Fax: +48 126385501 Andover Controls Asia Unit 1201-02, Phase 1, Cheuk Nang Centre 9 Hillwood Road, Tsim Sha Tsui East Kowloon, Hong Kong Tel: +852 2739 5497 Fax: +852 2739 7350 Andover Controls Mexico Insurgentes Sur 1722-501 Col. Florida Mexico D.F. 01030, Mexico Tel: +5255 5661 5672 Fax: +5255 5661 5415

WE'RE BUILDING SMART

A Balfour Beatty Company

www.andovercontrols.com ©2004 Andover Controls Corporation • All brand names, trademarks and registered trademarks are the property of their respective holders. DS-I-I2867-D

More documents · 1

For the same models