For the Andover Controls i2-867

Page 46

Pre-Operation Checks 1.

Make sure the internal battery is present and the protective tab is removed.

2.

Make sure the 24VAC power is wired properly. Check to be sure that both wires have been connected.

3.

Make sure the controller has a true earth ground.

4.

Make sure you have used the proper cables and wires at correct lengths.

5.

Make sure the Infinet cables and shields has been properly wired.

Initial Power-Up 1.

Enable the AC power source (or close the power connection). The controller starts automatically. If the controller has been off, outputs remain off. If you have pressed the internal RESET button, outputs turn off.

2.

The CPU indicator flashes five times per second during normal operation.

3.

If the CPU indicator flashes two times per second, the CPU has failed an internal test. In this case, recheck your connections and contact your Andover Controls representative. Indicators are located on the Access Panel found behind the module door.

40

Andover Controls Corporation

Page 47

Troubleshooting CPU Indicator Is Not Blinking If the CPU indicator is not blinking then the unit is not operating. This could be due to the loss of primary AC power or other internal disfunction. Check that 24VAC is available and connected properly to the power terminals. This can be done using a multimeter reading the voltage across the 24VAC and GND terminals. If power appears to be OK, remove power and all other connections from the unit. The fuse within the unit may have failed. To access the fuse the controller housing itself must be disassembled. The housing consists of two pieces that are snapped together. Follow the illustrations below to open the housing and gain access to the fuse area of the printed circuit board:

Depress tabs found on both sides of the case

FUSE

Remove the plug-in power fuse component and check it for continuity with an Ohm meter. If the fuse is blown, replace it with a similar 2 Amp fuse (it resides in a socket). After replacement, take care re-mounting the cover. i2867 Installation & Programming Guide

41

Page 48

Unit Appears Functional But Is Not Responding To CX Controller If the CPU indicator is blinking normally chances are that the unit is operational. However, in that the i2867 is a programmable unit, it is possible that there is a programming problem. Monitoring Infinet Activity Infinet communications can be monitored simply by observing the status of the TD (transmit) and RD (receive) LED indicators viewable from the Access Panel. During Infinet communications, both of these LEDs should show activity.

One Input or Output Appears to Be Dysfunctional If the CPU indicator is operating and other inputs/outputs are operating properly there could be two reasons for the failure: •

The Input or Output has been damaged. In this case contact an Andover Controls representative for assistance.

•

If this is the first time using the controller, perhaps the program controlling the input/output is not correct. Re-check your program.

Internal Reset Button Should the controller appear to be non responsive and all other attempts to revive it fail, try pressing the Reset button. The button is located behind the Access Panel.

Restart Switch behind panel 42

Andover Controls Corporation

Page 49

To access the button, the module cover must be opened and the electronics access cover must be removed. The access cover is secured via two force fitting plastic tabs. To remove the access cover after the main cover is opened, gently pry the cover outward using your thumb and forefinger while lifting the cover. As shown below:

i2867 Installation & Programming Guide

43

Page 50

44

Andover Controls Corporation

Page 51

I2867 Installation & Programming Guide

Page 52

30-3001-796 i2867 Installation & Programming Guide Rev B