Spec sheet · Andover Controls
Andover Controls LCX 810 Spec Sheet
Spec sheet4 pagesPDF 72 KB
All 4 pages are below, each with its text.
Covers · 1 model
The models it covers
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Four-page data sheet (DS-810-C, 1999) for the Andover Controls Infinity LCX 810 local control unit. It describes the controller's inputs, outputs, Infinet communications, programming and options, with a dimensional drawing and full specifications.
- Device
- Stand-alone programmable DDC controller for packaged HVAC units, heat pumps and fan coil units p. 1
- Inputs
- 8 universal: digital (on/off), counter (up to 4 Hz), temperature (-34 to 110°C), voltage (0 - 10VDC) p. 4
- Outputs
- 8 SPDT Form C relays, each with an HOA switch for manual override p. 4
- Power
- 24 VAC, 50/60 Hz, 18 VA p. 3
- Communications
- Infinet bus: twisted pair, half duplex RS-485, 300 to 19.2k baud, 4,000 ft. (1,220m) p. 1, 3
- Memory
- 128K EPROM, 32K RAM, 128 Byte EEPROM p. 4
- Battery
- Replaceable, non-rechargeable lithium; 7 years typical accumulated backup of RAM and real-time clock p. 3
- Operating environment
- -23 to 60°C, 10 to 95% RH (non-condensing); 0 to 38°C with display option p. 3
- Size
- 300.0H x 217.5W x 80.9D mm without enclosure; 482.6H x 381.0W x 120.6D mm with enclosure p. 3
- Weight
- 5.0 lbs. (2.3 kg) without enclosure; 19.0 lbs. (8.6 kg) with enclosure p. 3
- Display option
- 2 x 16 character LCD with keypad p. 2, 4
- Expansion modules
- EMX 140 (two pneumatic outputs), EMX 150 (two analog outputs), EMX 160 (eight digital inputs) p. 1
- Network size
- Up to 254 LCX 810s with the Infinity CX family of controllers p. 1
- Programming
- Plain English language, entered from an SX 8000 workstation, LSX 280 Lap-Top Service Tool or network controller p. 2
What this sheet walks you through
- Dimensions and terminal layout of the controller p. 2
- Programming the controller in Plain English p. 2
- Electrical, mechanical, battery and communications specifications p. 3
- Input, output and connection specifications p. 4
Good to know
- An Infilink amplification module is needed after every group of 32 units on the Infinet network. p. 3
- With the display option the operating range narrows to 0 to 38°C. p. 3
- Use copper conductors only. p. 2
- The sheet refers to the product installation guides for exact installation instructions and specifications. p. 4
Questions this sheet answers
What power supply does the Andover LCX 810 need?
24 VAC at 50/60 Hz; it draws 18 VA and is fused with a 2 amp pico fuse. p. 3
How long does the LCX 810 battery back up memory?
Its replaceable lithium battery gives 7 years typical accumulated power failure backup of RAM and the real-time clock. p. 3
Which I/O expansion modules fit the LCX 810?
Modules plug onto the bottom of the controller, including the EMX 140, EMX 150 and EMX 160. p. 1
What does the LCX 810 communicate with?
Over the Infinet field bus it talks to an Infinity CX or CMX network controller or the Lap-Top Service Tool. p. 3
The file
Size and text
Every page · 4
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 4
Open in the PDF
The text of page 1, from the PDF itself
Infinity LCX 810 Local Control Unit
The Infinity LCX 810 is a stand-alone, programmable, microprocessor-based controller that is used for Direct Digital Control and monitoring of packaged HVAC units, heat pumps, and fan coil units. The Infinet’s true peer-to-peer communications protocol provides the Infinity LCX 810 with the ability to instantly communicate with an Infinity network controller such as the CX 9200, as well as the entire network of Andover Infinet field controllers. Up to 254 LCX 810s can be networked with the Infinity CX
F E A T U R E S
- Stand-alone DDC for System Reliability
- Peer-to-Peer Communications Provide Transparent Data Transfer
family of controllers.
- Plain English ™ Language Simplifies Programming
The LCX 810 comes standard in a molded plastic enclosure suitable for panel mounting (shown). An optional metal enclosure is available for wall mounting. COMMUNICATIONS
Communication to the Infinity LCX 810 is handled via the Infinet bus, a twisted pair, half duplex RS-485 interface.
- Universal Inputs for Flexible Control Configurations
- Form C Outputs Provide On/Off or Pulse Width Modulation Switching
Communication is accomplished with a token passing protocol which provides full transparent data transfer between all Infinity controllers on the network.
- Expandable I/O Meets Additional Point Count Needs
INPUTS
The Infinity LCX 810 is capable of sensing eight inputs. Each input can accept a digital (on/off), counter (up to 4 Hz),
- Detachable Input/Output Connectors for Easy Installation
voltage (0-10VDC), or temperature signal.
- Full Function Manual Overrides OUTPUTS
Provide Status Feedback
The Infinity LCX 810 has eight Form C relay outputs rated at 5 amp 24VAC/DC, which provide on/off or pulse width modulation switching for control of fans, heating and cooling equipment, and economizers. Each output has a built-in switch for manual override.
- Optional Display/Keypad for Local Information Control
- Battery Backup For Seven Years
I/O EXPANSION
The LCX 810 contains an I/O expansion port for the addition of low-cost I/O modules directly onto the bottom of the controller. The family of modules includes the EMX 140 (two pneumatic outputs), the EMX 150 (two analog outputs), and the EMX 160 (eight digital inputs), etc.
Accumulated Power Failure of RAM Memory and Real-Time Clock
Page2of 4
Open in the PDF
The text of page 2, from the PDF itself
Infinity LCX 810 Local Control Unit
PROGRAMMING
Every LCX 810 can be configured to meet the exact distributed control requirements of your application using Andover Controls’ powerful Plain English™ programming language. Programs can be activated within individual LCX 810s or any network controller. Programs are entered into an LCX 810 using an SX 8000 workstation, the LSX 280 Lap-Top Service Tool, or network controller. The program is then stored in, and executed by, the LCX 810.
SOFTWARE CAPABILITIES
The dynamic memory of the LCX 810 can be allocated for any combination of Plain English control programs, scheduling, alarming and data logging. Andover's object-oriented language with intuitive keywords provides easy operation and programming. In addition, Plain English’s pre-defined and customized functions and powerful math capabilities reduce programming time for repetitive applications.
LOCAL DISPLAY WITH KEYPAD
An optional 2 x 16 character liquid crystal display provides for local viewing of point values and setpoint modifications in the LCX 810.
8.70" 220.0 mm 7.70" 195.5 mm
AC POWER CONNECTIONGND0.49" 12.5 mm++
USE COPPER CONDUCTORS ONLY F3 2 AMP
OPTIONAL DISPLAY WITH KEYPAD
F2 2 AMP 2 14 36 58
OUTPUT OVERRIDE SWITCHES
7 INPOWER INPUT TERMINALSOUT
INPUT REFERENCE RESISTOR
NC C+NO ON OFF AUTO3.6 V BATTERYON OFF AUTORET-1ON OFF AUTORET 3 4NC C NO NC C NO NC2C NOCPU ON OFF AUTORET 5 6TDRETON OFF AUTO7 8STATUSOVERRIDE+ -+24V EXTERNALINFINETSHLDR1RESETON OFF AUTO
C NC NO NC C NO NC C NO
ON OFF AUTOF1 1/8 AMP++ SERVICE PORT
4 HOLES 0.14' (3.5mm) DIA
NC NO CRD ON OFF AUTOINFINET TERMINALSOUTPUT LEDSINPUT TERMINALSNEU HOTINPUT TERMINALSPOWER INPUT TERMINALS0.48" 12.25 mmEXPANSION PORT
CASE DEPTH 3.23" (82mm)
LCX 810 Dimensional Drawing
10.95" 278.0 mm
11.94" 303.0 mm
Page3of 4
Open in the PDF
The text of page 3, from the PDF itself
SPECIFICATIONS
- ELECTRICAL Power
- 24 VAC, 50/60 Hz
- Power Consumption
- 18 VA
- Overload Protection
- Fused with 2 amp pico fuse. MOV protected.
- Real-Time Clock
- Battery-backed real-time clock.
MECHANICAL Operating Environment:
-10 to 140½F (-23 to 60°C), 10 to 95% RH (non-condensing) 32 to 104°F (0 to 38°C) with display option
- Size
- 11 13/16"H x 8 9/16"W x 3 3/16"D (300.0H x 217.5W x 80.9D)mm (without enclosure) 19"H x 15"W x 4 3/4"D (482.6H x 381.0W x 120.6D)mm (with enclosure)
- Weight
- 5.0 lbs. (2.3 kg) (without enclosure) 19.0 lbs. (8.6 kg) (with enclosure)
- Enclosure Type
- UL open class, IP 10 Optional NEMA 1-style enclosure, UL flame retardancy #94-5V, IP 20
- BATTERY Battery Backup
- Replaceable, non-rechargeable, lithium battery. Provides 7 years typical accumulated power failure backup of RAM memory and real-time clock.
COMMUNICATIONS Communications Interface:
Through Infinet field bus to Infinity CX or CMX Network Controller or Lap-Top Service Tool.
- Communications Speed
- 300 to 19.2k baud
- Bus Length
- 4,000 ft. (1,220m) standard for Infinet, Infilink amplification module allows extension to longer distances and is required after every group of 32 units on the network.
- Bus Media
- Infinet: twisted, shielded pair, approved, low capacitance cable
Page4of 4
Open in the PDF
The text of page 4, from the PDF itself
S P E C I F I C A T I O N S (Cont'd)
- Comm. Error Checking
- International Standard CRC 16
- INPUTS/OUTPUTS Inputs
- 8 Universal inputs: digital (on/off), counter (up to 4 Hz at 50% duty cycle), temperature (-30 to +230½F) ( -34 to 110°C), voltage (0 - 10VDC)
- Input Voltage Range
- 0 - 10 volts DC
- Input Impedance
- 10 meg ohms minimum with pull-up disabled
- Input Protection
- 24 VAC or 24 VDC indefinitely on any single channel, ± 1500 volt transients
- Input Resolution
- 2.5 mV
- Input Accuracy
- ±5 mV (± 0.46°F over range of -10 to +150½F) (± 0.26°C over range of -23 to +65°C)
- Outputs
- 8 single-pole double throw (SPDT) Form C relays
- Output Ratings
- 5A, 24 VAC, ± 1500 volt transients
- Output Resolution
- 0.1 sec. for pulse width modulation
- Overrides
- Each output is equipped with an HOA switch for manual control of the output.
- Expansion Bus
- Interfaces to optional I/O expansion modules Andover Controls Corporation World Headquarters 300 Brickstone Square Andover, Massachusetts 01810 USA Tel:978 470 0555 • Fax:978 470 0946 http://www.andovercontrols.com
- CONNECTIONS Power
- Three-position barrier strip
- Outputs
- Removable two-piece terminal strip
- Inputs
- Removable two-piece terminal strip
- Infinet Bus
- Removable two-piece terminal strip
Andover Controls Ltd. Smisby Road Ashby-de-la-Zouch Leicestershire LE65 2UG England Tel: 01530 417733 • Fax: 01530 415436 Andover Controls GmbH Am Seerhein 8 D-78467 Konstanz, Germany Tel:07531 99370 • Fax:07531 993710 Andover Controls S.A. Immeuble Dolomites 2 58 Rue Roger Salengro 94126 Fontenay Sous Bois Cedex, France Tel:331 53 99 16 16 • Fax:331 53 99 16 15
- GENERAL Memory Size
- 128K EPROM, 32K RAM, 128 Byte EEPROM
AGENCY LISTINGS
UL/CUL 916, FCC, CE
Andover Controls Asia Unit 1201-02 , Phase I, Cheuk Nang Centre 9 Hillwood Road, Tsim Sha Tsui Kowloon, Hong Kong Tel:852 2739 5497 • Fax:852 2739 7350 Andover Controls Mexico Insurgentes Sur 1722-501 Col. Florida Mexico D.F. 01030, Mexico Tel:525 661 56 72 • Fax:525 661 54 15 Copyright 1999, Andover Controls
OPTIONS
Corporation. Data subject to change without notice. Consult Andover Product
2 x 16 Character Liquid Crystal Local Display
Installation Guides for exact installation instructions and specifications.
NEMA 1-Style Enclosure (for Wall Mounting)
U.S. Patent # 4591967 #DS-810-C