Manual · Andover Controls
LCX 810 Installation Guide
Manual35 pagesPDF 360 KB
Installation guide for the Andover Controls LCX 810 controller on an Infinet network: site setup, wiring and power-up.
Covers · 1 model
The models it covers
Summary
What is in it
Andover Controls' installation guide for the LCX 810 controller on an Infinet network. It starts with site and system setup requirements (dimensions and weight, power, cable limits, lightning protection, building ground, environment, output equipment and input circuits), then gives step-by-step installation: mounting, connecting the battery and AC power, wiring the Infinet, inputs and outputs, expansion port modules, powering up, and connecting the Andover Controls service tool.
Its parts
- Setting Up the LCX 810 Controller and Infinet
- Site/System Setup Requirements
- Installing the LCX 810
- Powering Up the LCX 810
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Installation guide 30-3001-172, Version C (1997), for the Andover Controls LCX 810 controller on an Infinet network. It covers site preparation (power, cabling, grounding, environment), mounting, wiring the battery, power, Infinet, inputs and outputs, and what the lights show at power-up.
- Device
- Infinet network controller with eight inputs and eight Form C relay outputs p. 13, 14
- Power
- 24 VAC +/- 20%, 50/60 Hz, 18 VA, on its own unswitched circuit p. 11
- Outputs
- 8 Form C relays rated 5 A at 50 VAC; ON/OFF or PWM to 0.1 sec; override slide switch on each p. 13, 14
- Inputs
- 0 to 10.000 V range, 0.0025 V resolution, +/-0.005 V accuracy, pulses up to 5 Hz p. 14
- Input protection
- 120 VAC RMS or 120 VDC indefinitely on any single channel p. 14
- Input impedance
- 30.1KΩ referenced to 10.000 V, or 10 MΩ with the input reference resistor switch set to OUT p. 14, 23
- Battery
- 850 mA-hr 3.6 V primary lithium; runs the real-time clock and keeps RAM during AC outages p. 19
- Size and weight
- 11.75 x 8.9 x 2.75 in., 5 lbs p. 11
- Operating environment
- 32 to 120°F, 10 to 95% humidity non-condensing; inside a UL listed enclosure p. 13
- Infinet cable
- 24-gauge single twisted pair, tinned, shielded copper, such as Brand Rex # H 9002 or Anixter # 9J2401021 p. 11
- Bus length
- 4,000 ft at 19,200 baud for up to 32 Infinet controllers; longer with the InfiLink 200 p. 11
- Lightning arrester
- Two pair gas tube arrester, Andover Controls # 01-2100-299, where a bus cable enters or exits a building p. 12
- Current inputs
- 0 to 20 mA: 475Ω resistor across the input, reference resistor switch set to OUT p. 26
- CPU light
- Flashes every .2 sec after start; every .1 sec means a failed RAM or ROM test p. 29, 30
What this manual walks you through
- Site requirements: power, cable limits, lightning protection and grounding p. 10, 11, 12, 13
- Choosing wire gauge for thermistor runs p. 14, 15, 16
- Mounting the controller and connecting the battery p. 17, 19
- Wiring the AC power p. 21, 22
- Wiring the Infinet cable p. 22, 23
- Setting the input reference resistor switches and wiring thermistor, counter, voltage and current inputs p. 23, 25, 26, 27
- Wiring Form C outputs and setting the override switches p. 27, 28
- Powering up and reading the status lights p. 29, 30
- Connecting the Andover Controls Service Tool p. 31
Good to know
- All Infinity products must be grounded to true earth ground; a ground wire smaller than 14 AWG is not adequate. p. 12, 13
- The inputs are for two-wire devices and cannot power sensors or transducers that need an external supply. p. 14
- Never apply a voltage to a thermistor; one that has had voltage applied should be replaced. p. 25
- Install metal oxide varistors across the coil when switching inductive loads. p. 28
- Do not remotely ground any part of the sensor wiring; the signal return is not true earth ground. p. 23
Questions this manual answers
What does a fast-flashing CPU light on the LCX 810 mean?
If the CPU light flashes every .1 sec, the CPU has failed a RAM or ROM test; normally it flashes every .2 sec. p. 29, 30
What battery does the LCX 810 use?
An 850 mA-hr 3.6 V primary lithium battery, activated by removing a plastic tab; it keeps the clock and RAM during power loss. p. 19
How long can an Infinet bus run be?
Up to 4,000 ft at 19,200 baud with up to 32 controllers; the InfiLink 200 amplification module extends it. p. 11
How do I wire a current sensor to the LCX 810?
Set that input's reference resistor switch to OUT and wire a resistor across the input; 475Ω is recommended for 0 to 20 mA. p. 26
What power does the LCX 810 need?
24 VAC +/- 20% at 50/60 Hz, 18 VA, from its own independent, unswitched circuit. p. 11