Page 17

Installing the LCX 810 Unpacking Be careful when unpacking the unit to not damage the packaging material - you must reuse it if you ship the product back for repair.

Parts Required To install a single controller you start with the following parts: • • • •

LCX 810 Controller AC Power Cable Infinet Cable (twisted pair) InfiLink 200s as Hubs, Repeaters, or Cable Switching Boxes

Mounting Caution You must encase the LCX 810 in a UL listed cabinet to keep its Open Class rating. 1. Before you begin, look at the front of the LCX 810 cover. Figure 1 shows the front of the LCX 810. 2. The front cover of the LCX 810 has two Phillips head quarter turn fasteners aligned down the center, one above the middle and one at the bottom. Remove those fasteners, holding the cabinet firm so it does not fall. 3. Remove the cover and place it to one side.

LCX 810 Installation Guide

Technical Manuals Online! - http://www.tech-man.com

13

Page 18

Figure 1. The Front Cover of the LCX 810

1

2

3

SHIFT LOCK

4

5

6

BACK SPACE

7

8

9

CANCEL

ON

OFF

– ON

0

+/–

1/4 Turn Fastener

ENTER

1

LCX 810 2 CPU

3 TD

4 RD

5 OVERRIDE

6 EXTERNAL +24V

7

8

1/4 Turn Fastener

14

Technical Manuals Online! - http://www.tech-man.com

LCX 810 Installation Guide

Page 19

Warning Never drill holes in the LCX 810 cover or boards. A metal shaving could easily short circuit the electronics. 4. Screw the LCX 810 to the wall using standard No. 8 screws in the pre-cut holes in the four corners of the base plate. Figure 2 shows the location of the corner screw holes and measurements to all other openings in the cabinet. It also shows the locations of the override slide switches and other parts of the controller. You may want to refer to this figure for assistance during the installation process.

Connecting the Battery When you have the controller mounted, find the 1--2 AA battery. Remove the plastic tab below the clip on the battery to activate the battery. The battery is an 850 mA-hr 3.6 V primary lithium battery that runs the real-time clock and maintains RAM when AC power goes out.

LCX 810 Installation Guide

Technical Manuals Online! - http://www.tech-man.com

15

Page 20

Figure 2. Locations of Openings in Cabinet and Parts Inside Controller 8.56 .43 .43

7.70 x 1.05 GND x

AC INPUT USE COPPER CONDUCTORS ONLY

NEU HOT

7.56

6.14

10.02

OUTPUTS xxxxxxxxxxx IN xxxxxxxxxxx OUT RET 1 2 RET 3 4 RET 5 6 RET 7 8

10.95

11.81

INPUT REFERENCE RESISTOR

+

3

– 4

INPUTS

INFINET

SERVICE PORT

NC C NO NC C NO NC C NO NC C NO

9.04

CPU

TD

5

RD

6

OVERRIDE

7

STATUS LIGHTS

+ – SHLD

2

3.6V

INPUTS x

1

+24V EXTERNAL EXPANSION PORT

16

Technical Manuals Online! - http://www.tech-man.com

8

NC C NO NC C NO NC C NO NC C NO x

LCX 810 Installation Guide

Page 21

Connecting the AC Power Warning Be sure the AC power cable is not connected to an electrical power source while you are wiring the controller, or you could receive an electrical shock that is life-threatening.

Note If the installation requires the secondary of the 24 V transformer to be grounded, always connect the "neutral" to ground and only ground it at the transformer. The AC power connection is in the upper left corner of the controller. You must wire the AC cable to the three screws on the far left.

Caution Be sure to connect all three wires, HOT, NEUTRAL, and GROUND. Otherwise, the controller could malfunction. The three screws are labeled HOT NEU GND. The three wires at the end of your AC cord are black, white, and green. 1. Place the green wire under the metal plate behind the top screw, labeled GND. 2. Tighten the screw with a flathead screw driver. Figure 3 shows the position of the plate, where to place the wire, and how the screw fits on the plate. You can see how the screw holds the plate in place once you tighten it. 3. Place the white wire under the metal plate behind the middle screw, labeled NEU.

LCX 810 Installation Guide

Technical Manuals Online! - http://www.tech-man.com

17

Page 22

Figure 3. Metal Plate and Screw for Power Supply Wire Metal Plate

Insert Wire Here 4. Tighten the screw with a flathead screw driver. 5. Place the black wire under the metal plate behind the bottom screw, labeled HOT. 6. Tighten the screw with a flathead screw driver.

Wiring the Infinet to the LCX 810 Note You must use shielded cables for Infinet to ensure compliance with the Class A FCC limits and to ensure reliable communications. Figure 4 illustrates how to wire the Infinet cable to the removable block terminal connector in the lower left corner of the LCX 810.

Figure 4. Infinet Cable Wiring Infinet Connection WHITE

+

BLACK WHITE

– BLACK

SHLD

1. Trim back the shield over the wires. 2. Take the first wire for the incoming Infinet and the first wire for the outgoing Infinet and slip both in the hole beneath the screw labeled with a plus sign (top).

18

Technical Manuals Online! - http://www.tech-man.com

LCX 810 Installation Guide

Page 23

3. Tighten the screw down on them until the screw holds the wires in place. 4. Slip the second (usually black) wire from each Infinet cable under the screw labeled with a minus sign (middle) and tighten the screw down on them. 5. Slip the shields from the incoming and outgoing Infinet cables under the screw labeled SHLD (bottom) and tighten the screw down on them.

Wiring the Infinet to the Infinity CX 9000 You connect the last piece of Infinet cabling to the Infinity CX 9000. See the Andover Controls Infinity CX 9000 Hardware Installation Guide for instructions.

Setting the Input Reference Resistor Switches The inputs are on the lower left side of the LCX 810. Above the inputs is a DIP switch, with small switches for each input. Look closely at the switch and notice that each small switch is numbered. Each small switch corresponds to the input with the same number. If an input is either a thermistor or a digital input, switch its input reference resistor switch to IN. If you require that the input be high impedance (10 MΩ), set its input reference resistor switch to OUT.

Wiring the Inputs Caution Do not remotely ground any part of the sensor wiring. Remote grounds connected to the LCX 810 return terminal could make the controller operate incorrectly or damage the equipment. The signal return is not true earth ground. It is an electronic reference point necessary to interpret the sensor properly. Do not externally ground sensor or switch terminals that return to the LCX 810.

LCX 810 Installation Guide

Technical Manuals Online! - http://www.tech-man.com

19

Page 24

Caution Although inputs usually function properly with unshielded sensor wire, you may need shielded wire if you run the wire as follows: • In the same conduit with other noise-generating conductors such as 60 Hz AC power. • In long runs close to large power-consuming or power-generating equipment that can produce 60 Hz noise. We recommend you run input wiring in a conduit separate from AC power or output wiring and avoid long wiring runs.

Caution Follow the rules below when wiring inputs and outputs: • Never lay wires across the surface of the printed circuit board. You should bring input wires in from the left and output wires in from the right. • Bundle excess wires toward the back of the cabinet to avoid any contact with circuit boards. • Wires should never be within 1 in. of any component on the printed circuit board. • Keep cabinet free of foreign materials (extra power supplies, relays, and so on). • Be careful when stripping wire not to drop small pieces of wire inside the cabinet. If you violate any of these rules, the controller could malfunction.

20

Technical Manuals Online! - http://www.tech-man.com

LCX 810 Installation Guide

Page 25

Caution Never apply a voltage to a thermistor. Doing so alters the thermistor’s accuracy and reliability. You should replace a thermistor that has had voltage applied to it. Never bring a soldering iron to within 3 inches of the thermistor’s sensing tip. The inputs are on the lower left side of the LCX 810. Notice that the inputs are labeled RET, 1, 2, RET, 3, 4, and so on. The first return terminal goes to the first two inputs, the second to the next two inputs, and so on. Figure 5 shows a thermistor attached to an input point. One lead connects to the numbered input terminal, the other to a return terminal.

Figure 5. Schematic of Input Wiring for Thermistor 1 (input point 1)

RET (return)

Follow these steps: 1. Slip the first wire for the first sensor under the input point screw for input 1 and tighten the screw down on it. 2. Slip the first wire for the second sensor under the input point screw for input 2 and tighten the screw down on it. 3. Slip the ground wires from both the first and second sensors under the RETURN screw above input point 1 and tighten the screw down on them. 4. Repeat the steps 1 through 3 for each pair of inputs.

LCX 810 Installation Guide

Technical Manuals Online! - http://www.tech-man.com

21

Page 26

Figure 6 shows a counter wired to an input point.

Figure 6. Schematic of Wiring for Counter or Digital Input 1 (input point 1)

RET (return)

Figure 7 shows a voltage sensor wired to an input point.

Figure 7. Schematic of Wiring for Voltage Input 1 (input point 1) + V –

RET (return)

Figure 8 shows a current sensor wired to an input point. You must set the reference resistor switch to OUT for a current input. Then wire a resistor across the input.

Figure 8. Wiring Diagram for Current Input 1 (input point 1)

RL= 475Ω with wattage rating ≥ 1--4 Watt RET (return)

The exact number of Ohms resistance required varies based on the range of current - while we recommend 475Ω for a 0 to 20 mA input, you can also calculate the appropriate resistance with the following formula: VIN V R m a x = ---------------------I m a x mA × 1000

22

Technical Manuals Online! - http://www.tech-man.com

LCX 810 Installation Guide

Page 27

To account for the input current rising slightly above the maximum (such as slightly over 20 mA), you should choose a value slightly below the maximum resistance you calculate. For example, you calculate the resistance for 0 to 20 mA: 10 R m ax = ----20 × 1000 = 500Ω

You then select the next standard resistor, 475Ω, with a 0.1% or 1% tolerance. (The accuracy of the input is directly proportional to the tolerance of the resistor. So the lower the tolerance, the greater the ac1 curacy.) The wattage rating should be greater than or equal to --4 watt. Be sure you check the Andover Controls Infinity CX Programmer’s Guide for details on how to convert the voltage from a current input to other units.

Wiring the Outputs Wiring Form C Outputs The outputs are along the upper right side of the LCX 810. All the outputs are Form C and are labeled NC, C, NO from top to bottom. You wire the outputs as follows: 1. Slip the appropriate wire under the NC screw and tighten the screw down on it. 2. Slip the appropriate wire under the C screw and tighten the screw down on it. 3. Slip the appropriate wire under the NO screw and tighten the screw down on it.

LCX 810 Installation Guide

Technical Manuals Online! - http://www.tech-man.com

23

Page 28

Figure 9 shows the schematic for wiring a Form C output.

Figure 9. Schematic of Form C Output Wiring NC C NO

4. When switching inductive loads (relays, contactors, motors, or valves), be sure to install metal oxide varistors across the coil of the device being switched.

Setting the Override Switches The eight three-position override slide switches let you either manually control each output or set it to A or AUTO so the controller can control it.

Connecting Modules to the Expansion Port The expansion port at the bottom center of the controller board allows you to connect modules to expand the capabilities of the controller. Contact your Andover Controls representative for more information on expansion modules.

24

Technical Manuals Online! - http://www.tech-man.com

LCX 810 Installation Guide