For the Andover Controls LCX 810
Page 9
Setting Up the LCX 810 Controller and Infinet This manual covers the following: • Site/System Setup Requirements • Installing the LCX 810 • Powering Up the LCX 810
Warranty Registration Your warranty is effective for 18 months starting on the date the system is shipped.
Warning All wiring and installations must comply with local, state, and national electrical codes.
LCX 810 Installation Guide
Technical Manuals Online! - http://www.tech-man.com
5
Page 10
Site/System Setup Requirements Before you proceed to install the system, you should map out where you plan to install each controller, terminal/workstation, and modem. When planning the sites, be aware of any electrical interference that may occur. You also need to be aware of cabinet dimensions, power requirements, cable limitations, and environmental requirements.
Note This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions in this manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Note This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Avis Le présent appareil numérique n’émet pas de bruits radioélectriques dépassant les limites applicables aux appareils numériques de la class A prescrites dans le Règlement sur le brouillage radioélectrique édicté par le ministère des Communications du Canada.
6
Technical Manuals Online! - http://www.tech-man.com
LCX 810 Installation Guide
Page 11
Controller Dimensions and Weight Each LCX 810 is 11.75 × 8.9 × 2.75 in. and weighs 5 lbs.
Power Requirements Caution The LCX 810 should receive power from its own independent, unswitched circuit. The LCX 810 operates on a power supply of 24 VAC +/– 20% 50/60 Hz. The LCX 810 consumes 18 VA of power.
Cable Limitations The maximum cable length for all buses is 4,000 ft at 19,200 baud (up to 32 Infinet controllers). You can extend buses beyond 4,000 ft or put more than 32 Infinet controllers on less than 4,000 ft by using the InfiLink 200 amplification module.
Note You must use shielded cables for Infinet to ensure compliance with the Class A FCC limits and to provide reliable communications. Cables that form Infinet are 24-gauge, single-twisted-pair, tinned, shielded copper wire. Use the following cables1 or their equivalents: • Brand Rex # H 9002 (single-pair) • Anixter # 9J2401021 (single-pair plenum cable) The cable should have a nominal impedance of 100 Ohms and a nominal velocity of propagation of 78%.
1. You can also use any cables you may already have in place for ACNET or LBU.
LCX 810 Installation Guide
Technical Manuals Online! - http://www.tech-man.com
7
Page 12
Capacitance of Infinet cable should be nominal, below 12.5 pF/ft between conductors and below 22 pF/ft between the conductor connected to ground and the next conductor.
Lightning Protection Lightning arresters are required at each point where a bus cable enters or exits a building. Use the following arrester: Two pair gas tube arrester, Andover Controls # 01-2100-299
Building Ground Requirements Warning Be sure that all Infinity products from Andover Controls Corporation are grounded to true earth ground. This kind of ground protects the equipment from transients and other power surges in the area. We cannot guarantee that the controller system will operate as documented unless you properly ground all controllers.
Warning Be sure to have your grounds inspected before you begin the installation process to be sure your municipality follows the National Electrical Code. Many municipalities do not and often have substandard electrical grounds. An example of a substandard ground is a galvanized steel cold water pipe. As the pipe corrodes, it does not act as a true ground. The corrosion acts as an insulator, raising the potential of the pipe with respect to the ground. When lightning strikes in the area of the installation, it drastically changes the potential of the earth. Since properly grounded Andover Controls units respond to changes in potential more rapidly than poorly grounded electrical systems, a poorly grounded building tries to reach
8
Technical Manuals Online! - http://www.tech-man.com
LCX 810 Installation Guide
Page 13
ground through the Andover Controls system. The surge of current can destroy electronic components on the controller board. Surges of much lower potential than lightning also impact the reliability of Andover Controls equipment.
Inspecting the Ground You can check your ground as follows: 1. Check your ground by first inspecting the building power distribution panel for earth ground termination. If the ground termination is any of the following, it is not adequate and must be corrected: • Does not exist. • Is connected to a corroded or galvanized pipe. • Is connected using a small gauge wire (less than 14 AWG). 2. Be sure your Andover Controls cabinet is connected to the ground with a copper conductor that terminates at the distribution panel.
Environmental Requirements The LCX 810 operates in rooms with temperatures ranging from 32 to 120°F and with humidity between 10 and 95%, non-condensing. The controller must be in an Underwriter Laboratories listed enclosure.
Output Equipment Requirements The eight outputs on the LCX 810 are Form C and provide direct digital control for digital devices. In addition to standard ON/OFF, digital outputs have pulse width modulation (PWM). PWM allows you to modulate valves and dampers to 0.1 sec resolution.
LCX 810 Installation Guide
Technical Manuals Online! - http://www.tech-man.com
9
Page 14
All outputs are programmable. Eight override slide switches let you either manually control each output or set it to A or AUTO so the controller can control it. The Form C relay of each output is rated for 5 A at 50 VAC.
Input Circuit Specifications Caution Andover Controls inputs are designed to be used with two-wire devices and do not provide sufficient power to operate sensors or transducers requiring an external power supply. The following specifications apply to the eight LCX 810 inputs: • Voltage Range - 0 to 10.000 V • Resolution - 0.0025 V • Accuracy - +/–0.005 V • Maximum Pulse Frequency - 5 Hz at a duty cycle of 50% with a minimum pulse width of 100 ms • Input Impedance - 30.1KΩ referenced to 10.000 V or 10 MΩ referenced to ground with the input reference resistor switch set to OUT • Filtering - Corner Frequency at 16 Hz –20 db/decade • Over-Voltage Protection - 120 VAC RMS or 120 VDC indefinitely on any single channel; +/–1500 V transient for 50 µs on all channels • Calibration - Permanent (factory)
Special Factors for Thermistors To keep thermistor errors minimal, lay out your site so you can limit the length of wire runs to the maximum for the gauge wire you select.
10
Technical Manuals Online! - http://www.tech-man.com
LCX 810 Installation Guide
Page 15
Table 1 shows the maximum runs for wires of various gauges to keep errors within .5°F, .25°F, and .10°F when sensing temperatures up to 70°F.
Table 1. Wire Gauges and Corresponding Maximum Runs for Sensing Temperatures Up to 70 °F Gauge
1/ ° F Error 2
1/ ° F Error 4
1/ ° F Error 10
#14
26,700 ft
13,300 ft
5300 ft
#16
16,800 ft
8400 ft
3300 ft
#18
10,500 ft
5200 ft
2100 ft
#20
6600 ft
3300 ft
1300 ft
#22
4100 ft
2000 ft
800 ft
Table 2 shows the maximum runs for wires of various gauge to keep errors minimal when sensing temperatures up to 100°F.
Table 2. Wire Gauges and Corresponding Maximum Runs for Sensing Temperatures Up to 100 °F Gauge
1/ ° F Error 2
1/ ° F Error 4
1/ ° F Error 10
#14
12,700 ft
6300 ft
2500 ft
#16
7900 ft
3900 ft
1500 ft
#18
5000 ft
2500 ft
1000 ft
#20
3100 ft
1500 ft
600 ft
#22
1900 ft
900 ft
300 ft
Table 3 shows the maximum runs for wires of various gauges to keep errors minimal when sensing temperatures up to 150°F.
LCX 810 Installation Guide
Technical Manuals Online! - http://www.tech-man.com
11
Page 16
Table 3. Wire Gauges and Corresponding Maximum Runs for Sensing Temperatures Up to 150 °F 1/ ° F Error 2
1/ ° F Error 4
#14
4100 ft
2000 ft
800 ft
#16
2600 ft
1300 ft
500 ft
#18
1600 ft
800 ft
300 ft
#20
1000 ft
500 ft
200 ft
#22
650 ft
300 ft
130 ft
Gauge
1/ ° F Error 10
Laying Out the Site Setup You may want to draw a map of where you plan to put each controller and store it in a notebook. Find the tag attached to each controller that gives the number of the controller. Before you remove any tags, be sure the tag has all of the following information on it: • Location of the controller. • Serial number. • Model name and number. • Communications port the Infinet connects to on the Infinity CX 9000. Then collect the tags. You will need to know where your controllers are located when you later assign a name to each controller and each input and output.
12
Technical Manuals Online! - http://www.tech-man.com
LCX 810 Installation Guide