Page 29

Powering Up the LCX 810 Before you power up the controller, be sure the following are correct: 1. Be sure the battery is connected. 2. Be sure the AC power is wired properly. Check to be sure all three wires have been connected. 3. Be sure the controller has a true earth ground. 4. Be sure you have used the proper cables and wires and correct lengths. 5. Be sure you have properly labeled the tag with the name of the controller before removing it. 6. Be sure the Infinet has been properly wired. Double check that the ground wire is under the negative screw. 7. Be sure that Infinet cable shields are properly connected. If you have completed all previous sections in this manual, you are now ready to power up the controller. Turn on the AC power source (or close the power connection) and the controller starts automatically. The following occurs (also occurs when you press RESET): 1. If the controller has been off, relays remain off. If you have pressed RESET, relays de-energize. 2. If you are pressing RESET, the OVERRIDE light turns on while you are pressing the button. 3. The CPU light begins flashing and flashes every .2 sec. 4. The TD light immediately starts flashing after you let go of the button to show data is being transmitted. 5. The RD light begins flashing only if data is being received from other controllers on the network. This may not happen immediately. LCX 810 Installation Guide

Technical Manuals Online! - http://www.tech-man.com

25

Page 30

6. If any of the eight outputs is not set to AUTO, the overrides are enabled and the OVERRIDE light remains steadily on. 7. If the CPU light flashes every .1 sec, it means the CPU has failed a RAM or ROM test. See the Andover Controls Infinet Controller Troubleshooting Guide. 8. The EXTERNAL +24V light turns on and remains steadily on. When the EXTERNAL +24V light goes out, it means no power is being supplied to the expansion port. You may have to replace the fuse. See the Andover Controls Infinet Controller Troubleshooting Guide. 9. The eight status lights on the front of the controller each correspond to the output with the same number. They remain off until their corresponding outputs are turned ON by the controller programs. If no programs are running, the lights remain off. Pulsed outputs flash on for the duration of the pulse and then go off.

Reset Button The RESET button is the red square button just left of the horizontal center of the board at the bottom. You press it to initiate a warm start. The same events occur for a warm start as for a cold start.

Adjusting the LCD View Angle The LCD VIEW ANGLE adjustment screw is at the top in the center of the board. You turn the screw to adjust the angle of the LCD on the front cabinet. The contrast changes at different viewing angles. Adjust it to your needs.

Completing the Installation To complete the installation of your LCX 810 replace the cabinet cover, using the two Phillips head quarter turn fasteners.

26

Technical Manuals Online! - http://www.tech-man.com

LCX 810 Installation Guide

Page 31

Connecting the Andover Controls Service Tool The SERVICE PORT on the far left side of the bottom of the controller is to connect the Andover Controls Service Tool to a LCX 810. The service tool will access all LCX 810s and other Infinet controllers on the same network. For information on availability of the Andover Controls Service Tool, contact your Andover Controls representative.

LCX 810 Installation Guide

Technical Manuals Online! - http://www.tech-man.com

27

Page 32

LCX 810 Installation Guide

Technical Manuals Online! - http://www.tech-man.com

28