For the AutomationDirect D0-05AA and AutomationDirect Direct Logic DL06
Page 1
The DL05 & DL06 Family of Products The DL05 micro PLC family includes eight different models. Each has eight inputs and six outputs in the base unit. The DL05 has one option module slot, which can be used to expand the I/O count, provide additional communications capability or add a real-time clock and battery back-up.
DL05
Communication ports
8 in/6 out
The larger DL06 micro PLC family has 20 inputs and 16 outputs in the base unit. The DL06 has four option module slots which can be used to add I/O or provide additional communications options.
Instruction sets The DL05 CPU offers PID capability, highspeed counting, and most of the same powerful instruction set as our popular D2-250-1 CPU, including the IBox instructions available in DirectSOFT version 5. All DL05 PLCs have two built-in RS-232 communications ports that can be used for programming, operator interface, networking, etc. The DL06 CPU offers PID capability, floating point number handling, and an instruction set very similar to our D2-260 CPU, including the IBox instructions available in DirectSOFT version 5. All DL06 PLCs have two built-in communications ports that can be used for programming, operator interface, networking, etc. One of the DL06 ports is a multi-function port capable of RS-232, RS-422, or RS-485 communications.
DL06 20 in/16 out Option modules
Optional LCD display
Power options The DL05 and DL06 families have AC and DC power options. They are also offered with a variety of I/O options. You can explore the Quick Selection Guide on the next page to choose the right PLC for your application.
High-speed inputs and outputs Units with DC inputs have selectable highspeed input features on three input points (DL05) or four input points (DL06). Units with DC outputs can use the first two outputs as a single bi-directional pulse output. An overview of the high-speed I/O features appear later in this section.
Communication ports
General Specifications Power Input Voltage Range Maximum Power Maximum Inrush Current Storage Temperature Ambient Operating Temperature Ambient Humidity Vibration Resistance Shock Resistance Noise Immunity Atmosphere
AC Powered
DC Powered
110/220VAC (+ 10%, -15%), 50-60Hz
12/24VDC
95-240VAC
12-24VDC
30VA (DL05) 40VA (DL06)
20W
13A, 1ms (240VAC)
10A < 1ms
-4ºF to 158ºF (-20ºC to 70ºC) 32°F to 131°F (0°C to 55°C) 5% - 95% relative humidity (non-condensing) MIL STD 810C, Method 514.2 MIL STD 810C, Method 516.2 NEMA (ICS3-304) No corrosive gases
Volume 13 e2-18
Programmable Controllers
1 - 80 0 - 633 - 0405
Page 2
Quick Selection Guide
Company Information Systems Overview Programmable Controllers
110/220 (+10%, -15%) VAC Power Options DL05
Field I/O
DL06
Software
D0-05AA 8 AC inputs 6 AC outputs, 0.5A/point
D0-06AA 20 AC inputs 16 AC outputs, 0.5A/point
D0-05AD 8 AC inputs 6 DC outputs (sinking), 1.0A/point Two outputs can be used as a single bi-directional 7kHz pulse output
D0-06AR 20 AC inputs 16 relay outputs, 2A/point
D0-05AR 8 AC inputs 6 relay outputs, 2A/point D0-05DA 8 DC inputs Three inputs are filtered, or configure as a single 5kHz high-speed counter, interrupt input, or pulse catch input 6 AC outputs, 0.5A/point
D0-06DD1 20 DC inputs Four inputs are filtered inputs, can also be configured as a single 7kHz high-speed counter, interrupt input, or pulse catch input 16 DC outputs (sinking), 1.0A/point* Two outputs can be used as a single bi-directional 10kHz pulse output
D0-06DA 20 DC inputs Four inputs are filtered inputs, can also be configured as a single 7kHz high-speed counter, interrupt input, or pulse catch input 16 AC outputs, 0.5A/point
D0-06DD2 20 DC inputs Four inputs are filtered inputs, can also be configured as a single 7kHz high-speed counter, interrupt input, or pulse catch input 16 DC outputs (sourcing), 1.0A/point Two outputs can be used as a single bi-directional 10kHz pulse output D0-06DR 20 DC inputs Four inputs are filtered inputs, can also be configured as a single 7kHz high-speed counter, interrupt input, or pulse catch input 16 relay outputs, 2A/point
D0-05DD 8 DC inputs Four inputs are filtered, or configure as a single 5kHz high-speed counter, interrupt input, or pulse catch input 6 DC outputs (sinking), 1.0A/point Two outputs can be used as a single bi-directional 7kHz pulse output
C-more & other HMI Drives Soft Starters Motors & Gearbox Steppers/ Servos Motor Controls Proximity Sensors Photo Sensors Limit Switches Encoders Current Sensors Pressure Sensors
D0-05DR 8 DC inputs Four inputs are filtered inputs, can also be configured as a single 5kHz high-speed counter, interrupt input, or pulse catch input 6 relay outputs, 2A/point
Temperature Sensors Pushbuttons/ Lights Process
12/24 VDC Power Options DL05
Relays/ Timers
DL06
Comm.
D0-05DD-D 8 DC inputs Three inputs are filtered inputs, can also be configured as a single 5kHz high-speed counter, interrupt input, or pulse catch input 6 DC outputs (sinking), 1.0A/point Two outputs can be used as a single bi-directional 7kHz pulse output
D0-06DD1-D 20 DC inputs Four inputs are filtered inputs, can also be configured as a single 7kHz high-speed counter, interrupt input, or pulse catch input 16 DC outputs (sinking), 1.0A/point* Two outputs can be used as a single bi-directional 10kHz pulse output
D0-06DD2-D 20 DC inputs Four inputs are filtered inputs, can also be configured as a single 7kHz high-speed counter, interrupt input, or pulse catch input 16 DC outputs (sourcing), 1.0A/point Two outputs can be used as a single bi-directional 10kHz pulse output
D0-05DR-D 8 DC inputs Three inputs are filtered inputs, can also be configured as a single 5kHz high-speed counter, interrupt input, or pulse catch input 6 Relay outputs, 2A/point
D0-06DR-D 20 DC inputs Four inputs are filtered inputs, can also be configured as a single 7kHz high-speed counter, interrupt input, or pulse catch input 16 relay outputs, 2A/point
Note: High speed outputs cannot be used if highspeed inputs are in use, and high-speed inputs cannot be used if high-speed outputs are in use. Analog inputs and outputs can be accommodated with option modules, which are available for both the DL05 and DL06. * These outputs must be derated to 0.6A for EN61131-2 compliance.
Volume 13 w w w. a u to m at i o n d i re c t . c o m
Programmable Controllers e2-19
Terminal Blocks & Wiring Power Circuit Protection Enclosures Tools Pneumatics Appendix Product Index Part # Index
Page 3
Features at a Glance The DL05 and DL06 micro PLCs are complete self-contained systems. The CPU, power supply, and I/O are all included inside the same housing. Option modules are available to expand the capability of each PLC family for more demanding applications. The standard features of these PLCs are extraordinary and compare favorably with larger and more expensive PLCs. The specification tables to the right are meant for quick reference only. Detailed specifications and wiring information for each model of the DL05 and DL06 PLCs begin on page 2-33.
Program capacity Most boolean ladder instructions require a single word of program memory. Other instructions, such as timers, counters, etc., require two or more words. Data is stored in V-memory in 16-bit registers.
Performance The performance characteristics shown in the tables represent the amount of time required to read the inputs, solve the Relay Ladder Logic program and update the outputs.
Instructions A complete list of instructions is available at the end of this section.
Communications The DL05 and DL06 offer powerful communication features normally found only on more expensive PLCs.
Special features The DC input and DC output PLCs offer high-speed counting or pulse output. Option module slots allow for discrete I/O expansion, analog I/O, or additional communication options.
DL05 CPU Specifications System capacity
DL06 CPU Specifications System capacity
Total memory available (words). . . . . . . . . . . . . . . . . . . . 6K Ladder memory (words) . . . . . . . . . . . . . . . . . . . . . . . 2,048 V-memory (words) . . . . . . . . . . . . . . . . . . . . . . . . . . . 4,096 User V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . 3,968 Non-volatile user V-memory . . . . . . . . . . . . . . . . . . . 128 Battery backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes1 Total built-in I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 I/O expansion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes1
Total memory available (words) . . . . . . . . . . . . . . . . . 14.8K Ladder memory (words). . . . . . . . . . . . . . . . . . . . . . . . 7680 V-memory (words) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7616 User V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7488 Non-volatile user V-memory . . . . . . . . . . . . . . . . . . . 128 Built-in battery backup (D2-BAT-1) . . . . . . . . . . . . . . . . Yes Total I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 I/O expansion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes1
Performance
Contact execution (Boolean) . . . . . . . . . . . . . . . . . . . . 0.6µs Typical scan (1K Boolean)2 . . . . . . . . . . . . . . . . . . . 1-2ms.
Contact execution (Boolean) . . . . . . . . . . . . . . . . . . . . 0.7µs Typical scan (1K Boolean)2 . . . . . . . . . . . . . . . . . . 1.5-3ms.
Instructions and diagnostics RLL ladder style . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes RLLPLUS/flowchart style (Stages) . . . . . . . . . . . . . Yes/256 Run-time editing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Supports Overrides. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Scan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Variable/fixed Number of Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . 133 Types of Instructions: Control relays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 512 Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128 Counters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128 Immediate I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Subroutines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes For/next loops . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Timed interrupt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Integer math . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Floating-point math. . . . . . . . . . . . . . . . . . . . . . . . . . . No PID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Drum sequencers . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Bit of word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes ASCII print . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Real-time clock/calendar . . . . . . . . . . . . . . . . . . . . . . . . Yes1 Internal diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Password security. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes System and user error log . . . . . . . . . . . . . . . . . . . . . . . . No
Communications Built-in ports . . . . . . . . . . . . . . . . . . . . . . . . . Two RS-232C Protocols supported: K-sequence (proprietary protocol). . . . . . . . . . . . . . . Yes DirectNet master/slave . . . . . . . . . . . . . . . . . . . . . . . . Yes Modbus RTU master/slave. . . . . . . . . . . . . . . . . . . . . Yes ASCII out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Baud rate Port 1. . . . . . . . . . . . . . . . . . . . . . . . 9,600 baud (fixed) Port 2. . . . . . . . . . . . . . . . selectable 300-38,400 baud . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (default 9,600)
Specialty Features Filtered inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes3 Interrupt input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes3 High speed counter . . . . . . . . . . . . . . . . . . . . . . . Yes, 5kHz3 Pulse output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes, 7kHz3 Pulse catch input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes3 1- These features are available with use of certain option modules. Option module specifications are located later in this section. 2- Our 1K program includes contacts, coils, and scan overhead. If you compare our products to others, make sure you include their scan overhead. 3- Input features only available on units with DC inputs and output features only available on units with DC outputs.
Performance Instructions and diagnostics RLL ladder style . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes RLLPLUS/flowchart style (Stages) . . . . . . . . . . . . Yes/1024 Run-time editing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Supports Overrides. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Scan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Variable/fixed Number of Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . 229 Types of Instructions: Control relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1024 Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256 Counters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128 Immediate I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Subroutines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes For/next loops . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Table functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Timed interrupt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Integer math . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Trigonometric functions . . . . . . . . . . . . . . . . . . . . . . . Yes Floating-point math . . . . . . . . . . . . . . . . . . . . . . . . . . Yes PID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Drum sequencers . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Bit of word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Number type conversion . . . . . . . . . . . . . . . . . . . . . . Yes ASCII in, out, print . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes LCD instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Real-time clock/calendar . . . . . . . . . . . . . . . . . . . . . . . . Yes Internal diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Password security. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes System and user error log . . . . . . . . . . . . . . . . . . . . . . . . No
Communications Built-in ports:. . . . . . . . . . . . . . . . . . . . . . . . . One RS-232C . . . . . . . . . . One multi-function RS232C/RS422/RS485 NOTE: RS485 is for MODBUS RTU only. Protocols supported: K-sequence (proprietary protocol). . . . . . . . . . . . . . . Yes DirectNet master/slave . . . . . . . . . . . . . . . . . . . . . . . . Yes Modbus RTU master/slave. . . . . . . . . . . . . . . . . . . . . Yes ASCII in/out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes Baud rate Port 1. . . . . . . . . . . . . . . . . . . . . . . . 9,600 baud (fixed) Port 2. . . . . . . . . . . . . . . . selectable 300-38,400 baud . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (default 9,600)
Specialty Features
Filtered inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes3 Interrupt input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes3 High speed counter . . . . . . . . . . . . . . . . . . . . . . . Yes, 7kHz3 Pulse output. . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes, 10kHz3 Pulse catch input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes3 1- These features are available with use of certain option module. Option module specifications are located later in this section. 2- Our 1K program includes contacts, coils, and scan overhead. If you compare our products to others, make sure you include their scan overhead. 3- Input features only available on units with DC inputs and output features only available on units with DC outputs.
Volume 13 e2-20
Programmable Controllers
1 - 80 0 - 633 - 0405
Page 4
Features at a Glance
Company Information Systems Overview Programmable Controllers
DirectSOFT software The DL05 and DL06 PLCs use the same familiar DirectSOFT programming software that our larger PLCs use. A FREE version of DirectSOFT gives you all the great features of the full version, but with a 100-word PLC program download limitation. For programs larger than 100 words, the full package is required. The FREE PC-DS100 software may be sufficient to program the DL05 and DL06. If you are programming with a full package version prior to v5.0, you will need v2.4 or later for the DL05 PLCs and v4.0 or later for the DL06. We always recommend the latest version for the most robust features. See the Software section in this catalog for a complete description of DirectSOFT including features, part numbers of programming packages and upgrades.
Mounting tab
Input status indicators
Mode switch
Communication ports
Output status indicators
Field I/O Software C-more & other HMI Drives
Mode status indicators
Soft Starters
Communication status indicators
Motors & Gearbox
Removable terminal block
Steppers/ Servos Motor Controls Proximity Sensors Photo Sensors
External power inputs
Discrete input terminals
Discrete output terminals
Option module slot Limit Switches
Hardware features diagrams
Encoders Current Sensors
External power inputs
Discrete output terminals
Removable terminal block
Option module slots Pressure Sensors Temperature Sensors Pushbuttons/ Lights
Mode status indicators
Output status indicators
Input status indicators
Communication status indicators
Process Relays/ Timers Comm. Terminal Blocks & Wiring Power Circuit Protection
Mode switch
Enclosures Tools Pneumatics
Discrete input terminals
Removable terminal block
Communication ports
Mounting tab
Appendix Product Index Part # Index
Volume 13 w w w. a u to m at i o n d i re c t . c o m
Programmable Controllers e2-21
Page 5
Product Dimensions and Installation It is important to understand the installation requirements for your DL05 or DL06 system. Your knowledge of these requirements will help ensure that your system operates within its environmental and electrical limits. Note: there is a minimum clearance requirement of 2" (51mm) between the panel door (or any devices mounted in the panel door) and the nearest DL05 component.
Plan for safety This catalog should never be used as a replacement for the user manual. You can purchase, download free, or view online the user manuals for these products. The D0-USER-M is the publication for the DL05 PLCs, and the D0-06USER-M is the publication for the DL06 PLCs. The D0-OPTIONS-M is the user manual for the option modules. These user manuals contain important safety information that must be followed. The system installation should comply with all appropriate electrical codes and standards.
Temperature probe 2" 50mm min
Power source 2" 50mm min 2" 50mm min
Panel ground terminal
Bus b ar
Panel
Ground braid copper lugs
Star washers
Star washers
Earth ground
Panel or single point ground
See the Enclosure section to find an enclosure that fits your application
Temperature probe
1.5" 38mm min
Environmental Specifications for DL05 and DL06
Power source
1.5" 38mm min
Panel ground terminal
Bus b ar Earth ground
Note: There is a minimum clearance requirement of 1.5" (38mm) between the panel door (or any devices mounted in the panel door) and the nearest DL06 component.
1.5" 38mm min
Storage Temperature
-4º F-158ºF (-20ºC to 70ºC)
Ambient Operating Temperature
32ºF-131ºF (0º to 55ºC)
Ambient Humidity
5 to 95% relative humidity (non-condensing)
Vibration Resistance
MIL STD 810C Method 514.2
Shock Resistance
MIL STD 810C Method 516.2
Noise Immunity Atmosphere
NEMA (ICS3-304) No corrosive gases
Volume 13 e2-22
Programmable Controllers
1 - 80 0 - 633 - 0405
Page 6
Product Dimensions and Installation
Company Information Systems Overview Programmable Controllers
Unit dimensions and mounting orientation
Field I/O
DL05 and DL06 PLCs must be mounted properly to ensure ample airflow for cooling purposes. It is important to follow the unit orientation requirements and to verify that the PLC’s dimensions are compatible with your application. Notice particularly the grounding requirements and the recommended cabinet clearances.
Software C-more & other HMI Drives Soft Starters Motors & Gearbox
Mounting orientation
Steppers/ Servos Motor Controls Proximity Sensors Photo Sensors Limit Switches Encoders Current Sensors Pressure Sensors
Mounting orientation
Temperature Sensors Pushbuttons/ Lights Process Relays/ Timers Comm. Terminal Blocks & Wiring Power Circuit Protection Enclosures Tools Pneumatics Appendix Product Index Part # Index
Volume 13 w w w. a u to m at i o n d i re c t . c o m
Programmable Controllers e2-23
Page 7
Choosing the I/O Type The DL05 and DL06 product families offer a number of different I/O configurations. Choose the configuration that is right for your application. Also, keep in mind that both the DL05 and the DL06 PLCs offer the ability to add I/O with the use of option modules.
Fixed discrete I/O All DL05 micro PLCs have eight built-in inputs and six built-in outputs on the base unit. The DL06 micro PLCs have 20 builtin inputs and 16 built-in outputs on the base unit. We offer the most common I/O types for your convenience, including AC inputs and outputs, DC sinking and sourcing inputs and outputs, and relay outputs. Refer to the tables to the right to see the I/O combinations available and their voltage ranges.
DL05 Base Unit I/O Table Inputs Part Number I/O type/ Sink or Voltage commons source ranges
Outputs
Price
I/O type/ Sink or Voltage/current commons source ratings N/A
6-27VDC, 2A 6-240VAC, 2A
<--->
N/A
6-27VDC, 2A 6-240VAC, 2A
<--->
Sink
6-27VDC, 0.5A (Y0-Y1) 6-27VDC, 1.0A (Y2-Y5)
<--->
DC/1
Sink
6-27VDC, 0.5A (Y0-Y1) 6-27VDC, 1.0A (Y2-Y5)
<--->
90-120VAC AC/2
N/A
17-240VAC 47-63Hz 0.5A
<--->
AC/2
N/A
17-240VAC 47-63Hz 0.5A
<--->
Sink or 12-24VDC Source
Relay/2
N/A
6-27VDC, 2A 6-240VAC, 2A
<--->
Sink or 12-24VDC Source
DC/1
Sink
6-27VDC, 0.5A (Y0-Y1) 6-27VDC, 1.0A (Y2-Y5)
<--->
D0-05AR
AC/2
N/A
D0-05DR
DC/2
Sink or 12-24VDC Source
D0-05AD
AC/2
N/A
D0-05DD
DC/2
Sink or 12-24VDC Source
D0-05AA
AC/2
N/A
D0-05DA
DC/2
Sink or 12-24VDC Source
D0-05DR-D DC/2 D0-05DD-D DC/2
90-120VAC Relay/2 Relay/2
90-120VAC DC/1
Option module slots The DL05 has one option module slot and the DL06 has four option module slots. Check out the discrete and analog I/O you can add by purchasing inexpensive option modules. Specialty modules are also available and are discussed later in this section.
Automatically assigned addresses The DL05 uses automatic addressing, so for the vast majority of applications, there is no setup required. We use octal addressing for our products, which means there are no 8s or 9s. The DL05’s eight input points use addresses X0-X7, and the six output points use addresses Y0-Y5. Similarly, the DL06 uses addresses X0-X23 and Y0-Y17.
Review the I/O specs and wiring diagrams The Base Unit I/O tables give a brief description of the I/O combinations offered for the DL05 and DL06 PLCs. The I/O specifications are discussed in more detail later in this section.
Sinking/sourcing If you are using a DC field device, you should consider whether that device requires a sinking or sourcing PLC I/O configuration. For more information on sinking and sourcing concepts, please refer to the Appendix of this catalog. Sink/source inputs, All built-in DC inputs on the DL05 and DL06 micro PLCs can be wired in a sinking or sourcing configuration. However, all inputs on a single common must use the same configuration. In some cases, the DC inputs on option modules are fixed as sinking or sourcing. Refer to the table on the next page. Sinking outputs, All built-in DC outputs on the DL05 are sinking. The DL06 family offers two PLCs with sinking DC outputs, and two with sourcing outputs.
High-speed inputs and pulse outputs DL05s and DL06s with DC inputs offer highspeed input features, and DC output units offer pulse output features. The first three DC inputs on the DL05 PLCs are set up by default as filtered inputs with a 10 ms filter. Likewise, the first four DC inputs on the DL06 PLCs are set to the same default value. By entering a setup code in a special V-memory location, you can choose other features. In some modes of operation, you have a choice as to how you use each point. For example, if you use X0 as an up counter, you can use X2 as a reset input for the counter or as a filtered discrete input. If these features interest you, take a look at the detailed high-speed I/O descriptions found later in this section.
Sourcing outputs, The DL06 PLC family includes the D0-06DD2(-D) with sourcing outputs. If a sourcing output is required, you might also consider using the D0-xxTD2 option module with sourcing outputs, which can also be installed in a DL05 or DL06 PLC.
Volume 13 e2-24
Programmable Controllers
1 - 80 0 - 633 - 0405
Page 8
Choosing the I/O Type
Company Information Systems Overview
Inputs Outputs Part Number I/O Type/ Sink or Voltage I/O Type/ Sink or Voltage/Current Commons source Ranges Commons Source Ratings D0-06AA
AC/5
N/A
90-120VAC AC/4
D0-06AR
AC/5
N/A
90-120VAC Relay/4
D0-06DA
DC/5
12-24VDC
AC/4
D0-06DD1
DC/5
12-24VDC
DC/4
D0-06DD2
DC/5
12-24VDC
DC/4
D0-06DR
DC/5
Sink or source Sink or source Sink or source Sink or source Sink or source Sink or source Sink or source
12-24VDC
Relay/4
12-24VDC
DC/4
12-24VDC
DC/4
12-24VDC
Relay/4
D0-06DD1-D DC/5 D0-06DD2-D DC/5 D0-06DR-D DC/5
Price
17-240VAC, 0.5A <---> 50/60 Hz 6-27VDC, 2A N/A <---> 6-240VAC, 2A 17-240VAC, 0.5A N/A <---> 50/60Hz 6-27VDC, 0.5A (Y0-Y1) Sink <---> 6-27VDC, 1.0A (Y2-Y17)* 12-24VDC, 0.5A (Y0-Y1) Source <---> 12-24VDC, 1.0A (Y2-Y17) 6-27VDC, 2A N/A <---> 6-240VAC, 2A 6-27VDC, 0.5A (Y0-Y1) Sink <---> 6-27VDC, 1.0A (Y2-Y17)* 12-24VDC, 0.5A (Y0-Y1) Source <---> 12-24VDC, 1.0A (Y2-Y17) 6-27VDC, 2A N/A <---> 6-240VAC, 2A N/A
* These outputs must be derated to 0.6A for EN61131-2 compliance.
Discrete I/O Option Moduless Inputs Outputs Part Number I/O Type/ Sink or Voltage I/O Type/ Sink or Number/ Number/ Commons source Ranges Commons Source D0-07CDR
DC/4/1
D0-08CDD1
DC/4/2
Sink or source Sink or source
D0-08TR
N/A
N/A
D0-10ND3
DC/10/2
Price
N/A
<--->
DC/4/2
Sink
6-27VDC, 0.3A
<--->
Relay/8/2
N/A
6-27VDC, 1A 6-240VAC, 1A
<--->
N/A
<--->
Relay/3/1
12-24VDC N/A
By using option modules, you can add analog inputs or outputs to your DL05 or DL06 PLC. The table below shows the input and output types at a glance. Detailed specifications are provided later in this section.
Inputs Part Number
Outputs Price
No. Input Type No.
Output Type
F0-04AD-1
4
0-20mA or 0 4-20mA
N/A
<--->
Steppers/ Servos
F0-04AD-2
4
0-5VDC or 0 0-10VDC
N/A
<--->
Motor Controls
F0-08ADH-1
8
0-20mA
0
N/A
<--->
F0-08ADH-2
8
0-5VDC or 0 0-10VDC
N/A
<--->
F0-04DAH-1
0
N/A
4
4-20mA <--->
F0-08DAH-1
0
N/A
8
4-20mA <--->
F0-04DAH-2
0
N/A
4
0-10VDC <--->
F0-08DAH-2
0
Limit Switches
Current Sensors
N/A
8
0-10VDC <--->
F0-4AD2DA-1 4
0-20mA or 2 4-20mA
F0-2AD2DA-2 2
0-5VDC or 2 0-10VDC 0-5VDC or 2 0-10VDC
0-20mA or <---> 4-20mA 0-5VDC or <---> 0-10VDC 0-5VDC or <---> 0-10VDC
DC/10/2
D0-10TD1
N/A
N/A
N/A
DC/10/2
Sink
6-27VDC, 0.3A
<--->
D0-10TD2
N/A
N/A
N/A
DC/10/2
Source
12-24VDC, 0.3A
<--->
D0-16ND3
DC/16/4
Sink or source
20-28VDC
N/A
N/A
N/A
<--->
D0-16TD1
N/A
N/A
N/A
DC/16/2
Sink
6-27VDC, 0.1A
<--->
D0-16TD2
N/A
N/A
N/A
DC/16/2
Source
12-24VDC, 0.1A
<--->
Power budgeting
<---> <--->
No power budgeting is necessary for the DL05. The built-in power supply is sufficient for powering the base unit, any of the option modules, the handheld programmer, and even a DV1000 operator interface.
12-24VDC
N/A
N/A
N/A
<--->
F0-04RTD
4
RTD
0
N/A
<--->
F0-04THM*
4
Thermocouple / Voltage
0
N/A
<--->
N/A
N/A
N/A
Relay/4/4
N/A
F0-08NA-1
AC/8/2
N/A
80-132VAC 90-150VDC
N/A
N/A
N/A
F0-08SIM
8-pt. Input simulator
<--->
Communications and Specialty Option Modules Part Number H0-ECOM H0-ECOM100 D0-DEVNETS H0-CTRIO H0-PSCM D0-DCM F0-CP128
Description Ethernet Communications Module 10 Mbit Ethernet Communications Module 10/100 Mbit DeviceNET Slave Module High Speed Counter I/O Module Profibus Slave Communications Module Serial Communications Module ASCII CoProcessor Module
Price <---> <---> <---> <---> <---> <---> <--->
Temperature Sensors Pushbuttons/ Lights Process
Comm.
* See module specifications page for thermocouple types and voltage input ranges supported
Power budgeting is necessary for the DL06. With four option module slots and an optional LCD display, it is necessary to verify that sufficient power is available for all optional devices. Power budgeting is described in detail on page 2-29 and in the DL06 User Manual. Programmable Controllers
Pressure Sensors
Relays/ Timers
Volume 13 w w w. a u to m at i o n d i re c t . c o m
Proximity Sensors Photo Sensors
F0-4AD2DA-2 4
F0-04TRS
Soft Starters Motors & Gearbox
12-24VDC
5-30VDC, 3A 5-125VAC, 3A
C-more & other HMI Drives
D0-10ND3F
N/A
Software
Analog I/O Option Modules
Sink or source Sink or source
N/A
Field I/O
Encoders
Voltage/Current Ratings 6-27VDC, 1A 6-240VAC, 1A
12-24VDC
Programmable Controllers
Analog I/O
DL06 Base Unit I/O Table e2-25
Terminal Blocks & Wiring Power Circuit Protection Enclosures Tools Pneumatics Appendix Product Index Part # Index