Page 9
Networking the DL05 and DL06 All DL05 and DL06 PLCs have built-in networking capability. The DL05 family offers two 6-pin, RS-232 ports. You can use these ports for programming, networking, or connecting an operator interface device. The RS-232 ports support point-to-point communications using the optional D0-CBL cable. If you need to create a multi-drop network or require longer distances between devices, you can use the FA-ISOCON at each DL05 to convert the RS-232 signal to RS422 or RS-485.
Optional Ethernet communication modules Need to connect to a high speed HMI or computer system? We offer 10Base-T and 100Base-T Ethernet communications modules. You can use the H0-ECOM and H0-ECOM100 Ethernet communication modules with our Ethernet hub/switch (E-SW05U) or with most off-the-shelf Ethernet hubs or switches. The ECOM option modules plug into any DL05 or DL06 PLC. The H0-ECOM100 supports the industry standard Modbus TCP protocol.
Point-to-point
The DL06 family of PLCs offers even greater communications flexibility. Port 1 is a fixed baud rate port identical to port 1 on the DL05 PLCs, but port 2 is a multifunction port that can be used as RS-232, RS-422, or RS-485 (Modbus/ASCII only) without using external converters. This allows you to create multi-drop networks with minimal installation headaches.
12’ crossover cable = D0-CBL maximum distance 50ft (15m)
Protocols supported Each port is capable of communicating using K-sequence, DirectNET and Modbus RTU protocols. Port 1 can only be a slave for each of the protocols. Port 2 can serve as a K-sequence slave or a network master or slave for either DirectNET or Modbus RTU protocols.
Master Slave
Multi-drop
Serial Bus Protocols We also offer option modules that allow you to connect a DL05 or DL06 PLC to a variety of network as a slave device. Our D0-DEVNETS (DeviceNet) and H0-PSCM (PROFIBUS) option modules plug into any DL05 or DL06 PLC. The D0-DCM Data Communications module supports DirectNET and Modbus RTU protocols.
ZL-CMA15 FA-ISOCON
ZIPLink communication adatper modules The ZIPLink communications adapter modules offer fast and convenient screw terminal connection for the bottom port of the DL06 CPU. The adapter modules are RS232/422 DIP switch selectable and are offered with or without indicating LEDs and surge protection. See the Wiring Solutions section in this catalog for more information.
ZL-CMA15L Maximum distance of 3,300 ft. (1000m)
Volume 13 e2-26
Programmable Controllers
1 - 80 0 - 633 - 0405
Page 10
Ports, Status Indicators, and Modes
Company Information Systems Overview
Port 1
Port 2
Port 1 is a 6-pin, fixed configuration port and has the same pin assignments on the DL05 and the DL06. Please refer to the table and diagrams on this page. This port can be used to connect to an HPP, DirectSOFT, an operator interface, or other external device. Features include: • 9600 baud • 8 data bits • Odd parity • 1 start bit, 1 stop bit • Station address of 1 • Asynchronous, half-duplex, DTE
Port 2 is a configurable port on both the DL05 and the DL06 PLCs. The DL05 PLC uses a 6-pin modular connector and offers RS-232 communications only. The DL06 PLC uses a 15-pin HD-sub connector and offers RS-232, RS-422, or RS-485 communications. Please refer to the table and diagrams on this page for more information. This port can be used to connect to an HPP, DirectSOFT, an operator interface, or other external device. Features of port 2 include: • 300, 600, 1200, 2400, 4800, 9600 (default), 19,200, 38,400 baud • 8 data bits • Odd (default), even, or no parity • 1 start bit, 1 stop bit • Station address: 1 (default) 1-90 DirectNET, K sequence 1-247 Modbus RTU • Asynchronous, half-duplex, DTE
Protocols supported (as slave): • K sequence, DirectNET, Modbus RTU
DL05 & DL06 Port 1 Pin Descriptions 1 2 3 4 5 6
0V
Power (-) connection (GND)
5V
Power (+) connection
RXD
Receive data (RS-232C)
TXD
Transmit data (RS-232C)
5V
Power (+) connection
0V
Power (-) connection (GND)
Protocols supported: • K sequence (slave), DirectNET (master/slave), Modbus (master/slave)
DL05 Port 2 Pin Descriptions 1 2 3 4 5 6
DL05
0V
Power (-) connection (GND)
5V
Power (+) connection
RXD
Receive data (RS-232C)
TXD
Transmit data (RS-232C)
RTS
Ready to send
0V
Power (-) connection (GND)
DL06 Port 2 Pin Descriptions 6-pin Female Modular Connector
DL06
6-pin Female Modular Connector
1 5V 2 TXD 3 RXD 4 RTS 5 CTS 6 RXD7 0V 8 0V 9 TXD+ 10 TXD11 RTS+ 12 RTS13 RXD+ 14 CTS+ 15 CTS-
Power (+) connection Transmit data (RS-232C) Receive data (RS-232C)
DL05 and DL06 status indicators Status Indicators Indicator Status Meaning PWR
RUN
CPU
C-more & other HMI
OFF
Power failure
Drives
ON
CPU is in Run Mode
OFF
CPU is in Stop or Program Mode
ON
CPU self diagnostics error
OFF
CPU self diagnostics good
ON
Data is being transmitted by the CPU-Port 1
Steppers/ Servos
OFF
No data is being transmitted by the CPU-Port 1
Motor Controls
ON
Data is being received by the CPU-Port 1
OFF
No data is being received by the CPU-Port 1
ON
Data is being transmitted by the CPU-Port 2
OFF
No data is being transmitted by the CPU-Port 2
Limit Switches
ON
Data is being received by the CPU-Port 2
Encoders
OFF
No data is being received by the CPU-Port 2
Current Sensors
TX2
RX2
DL05 and DL06 mode switches CPU Action
Soft Starters Motors & Gearbox
Proximity Sensors Photo Sensors
Pressure Sensors Temperature Sensors Pushbuttons/ Lights
CPU is forced into the RUN mode if no
Process ming/monitoring device. RUN PROGRAM and the TEST modes
Relays/ Timers
RUN (Run errors are encountered. No program Program) changes are allowed by the programTERM are available. Mode and program (Terminal) changes are allowed by the programming/monitoring device. CPU is forced into the STOP mode. No changes are allowed by the programming/monitoring device.
Comm. Terminal Blocks & Wiring
Ready to send (RS232C) Clear to send (RS232C) Receive data (-) (RS-422/485)
Use the optional low profile 15-pin adapter to make option module wiring easier.
Power (-) connection (GND) Power (-) connection (GND)
D0-06ADPTR
Power Circuit Protection Enclosures
Transmit data (+) (RS-422/485 Tools
Transmit data (-) (RS-422/485) Ready to send (+) (RS-422/485)
Pneumatics
Ready to send (-) (RS-422/485)
Appendix
Receive data (+) (RS-422/485) Product Index
Clear to send (+) (RS-422/485) Clear to send (-) (RS-422/485)
15-pin Female D-sub Connector
Part # Index
Volume 13 w w w. a u to m at i o n d i re c t . c o m
Software
Power good
RX1
STOP
Field I/O
ON
TX1
Mode Switch Position
Programmable Controllers
Programmable Controllers e2-27
Page 11
ASCII and Modbus Instructions ASCII instructions for DL06 The DL06 PLC supports several easy to use instructions, which allow ASCII strings to be read into or written from the communication ports when using either the CPU port 2, or the D0-DCM Data Communications Module port 2. Raw ASCII: CPU/DCM Port 2 can be used for either reading or writing raw ASCII strings, but not for both. Embedded ASCII: With these instructions, you can use the DL06 PLC to locate ASCII strings embedded within a supported protocol via CPU/DCM Port.
Receiving ASCII strings 1. ASCII IN (AIN) - This instruction configures CPU/DCM Port 2 for raw ASCII input strings, with parameters such as fixed and variable length ASCII strings, termination characters, byte swapping options, and instruction control bits. Use barcode scanners, weigh scales, etc., to write raw ASCII input strings into CPU/DCM Port 2 based on the AIN instruction’s parameters.
Writing ASCII strings
More ASCII instructions
1. Print from V-memory (PRINTV) - Use this instruction to write raw ASCII strings out of CPU/DCM port 2 to a d i s p l a y panel, serial printer, etc. The instruction features the starting Vm e m o r y address, string length, byte swapping options, etc. When the instruction’s permissive bit is enabled, the string is written to CPU/DCM Port 2.
ASCII Find (AFIND) - Finds where a specific portion of the ASCII string is located in continuous V-memory addresses.
2. Print to V-memory (VPRINT) - Use this instruction to create pre-coded ASCII strings in the PLC (e.g. alarm messages). When the instruction’s permissive bit is enabled, the message is loaded into a pre-defined V-memory address location. Then the PRINTV instruction may be used to write the pre-coded ASCII string out of CPU/DCM Port 2. American, European, and Asian Time/Dates tamps are supported. 3. Print Message (PRINT) - This existing instruction can be used to create precoded ASCII strings in the PLC. When the instruction’s permissive bit is enabled, the string is written to CPU/DCM Port 2. The VPRINT/PRINTV instruction combination is more powerful and flexible than the PRINT instruction.
2. Write embedded ASCII strings directly to V-memory from an external HMI (or similar master device). The ASCII string is transmitted through CPU/DCM Port 2 using any supported communications protocol. This method uses the familiar RX/WX instructions previously available.
4. If the DL06 PLC is a network master, the Network Write (WX) can be used to write embedded ASCII data to an HMI or slave device directly from V-memory. This is done via a supported communications protocol using CPU/DCM Port 2.
ASCII Extract (AEX) - Extracts a specific portion (usually some data value) from the ASCII find location or other known ASCII data location. Compare V-memory (CMPV) - This instruction is used to compare two blocks of Vmemory addresses and is usually used to detect a change in an ASCII string. Compared data types must be of the same format (e.g. BCD, ASCII, etc.). Swap Bytes (SWAPB) - Swaps V-memory bytes on ASCII data that was written directly to V-memory from an external HMI or similar master device via a communications protocol. The AIN and AEX instructions have a built-in byte swap feature. The F0-CP128 option module is also available for more extensive ASCII communications.
Modbus RTU instructions for DL06 The DL06 CPU/DCM port 2 supports Modbus Read/Write instructions that simplify setup. The MRX and MWX instructions allow you to use native Modbus addressing, eliminating the need for octal to decimal conversions. Function Codes 05 and 06 and the ability to read Slave Exception Codes have been added. These flexible instructions allow the user to select the following parameters within one instruction window: • 584/984 or 484 Modbus data type • Slave node (0-247) • Function code • Starting master/slave memory address • Number of bits • Exception code starting address
3. If the DL06 is used as a network master, the Network Read instruction (RX) can be used to read embedded ASCII data from a network slave device. Again, the ASCII string would be transmitted through CPU/DCM Port 2, using any supported communications protocol. Volume 13 e2-28
Programmable Controllers
1 - 80 0 - 633 - 0405
Page 12
Power Budgeting for the DL06
Company Information Systems Overview
The DL06 has four option module slots. To determine whether the combination of modules you select will have sufficient power, you will need to perform a power budget calculation.
Power supplied Power is supplied from two sources: the internal base unit power supply and, if required, an external supply (customer furnished). The D0-06xx (AC powered) PLCs supply a limited amount of 24 VDC power. The 24 VDC output can be used to power external devices. For power budgeting, start by considering the power supplied by the base unit. All DL06 PLCs supply the same amount of 5 VDC power. Only the AC units offer 24 VDC auxiliary power. Be aware of the trade-off between 5 VDC power and 24 VDC power. The amount of 5 VDC power available depends on the amount of 24 VDC power being used, and the amount of 24 VDC power available depends on the amount of 5 VDC power consumed. Determine the amount of internally supplied power from the table to the right.
Power required by base unit Because of the different I/O configurations available in the DL06 family, the power consumed by the base unit itself varies from model to model. Subtract the amount of power required by the base unit from the amount of power supplied by the base unit. Be sure to subtract 5 VDC and 24 VDC amounts.
Power required by option modules Next, subtract the amount of power required by the option modules you are planning to use. Again, remember to subtract both 5 VDC and 24 VDC. If your power budget analysis shows surplus power available, you should have a workable configuration.
DL05/06 Power Consumed by Option Modules
DL06 Power Supplied by Base Units Part Number 5 VDC (mA) D0-06xx D0-06xx-D
24 VDC (mA)
1500mA
300mA
2000mA
200mA
1500mA none
DL06 Base Unit Power Required Part Number 5 VDC (mA) D0-06AA D0-06AR D0-06DA D0-06DD1 D0-06DD2 D0-06DR D0-06DD1-D D0-06DD2-D D0-06DR-D
24 VDC (mA)
800mA none
900mA none
800mA none
600mA
280mA*
600mA none
950mA none
600mA none
600mA none
950mA none
* Only if auxiliary 24VDC power is connected to V+ terminal.
DL06 Power Consumed by Other Devices Part Number D0-06LCD D2-HPP DV-1000 C-more Micro-Graphic
5 VDC (mA)
24 VDC (mA)
50mA none
200mA none
150mA none
210mA none
Power Budgeting Example 5VDC power 24VDC power (mA) (mA)
Power Source A D0-06DD1 (select row A or B) B
1500mA
300mA
2000mA
200mA
Part Number 5 VDC (mA) 24 VDC (mA) 130mA none D0-07CDR 100mA none D0-08CDD1 280mA none D0-08TR 35mA none D0-10ND3 35mA none D0-10ND3F 150mA none D0-10TD1 150mA none D0-10TD2 35mA none D0-16ND3 200mA none D0-16TD1 200mA none D0-16TD2 250mA none F0-04TRS 5mA none F0-08NA-1 50mA none F0-04AD-1 75mA none F0-04AD-2 25mA 25mA F0-08ADH-1 25mA 25mA F0-08ADH-2 25mA 150mA F0-04DAH-1 25mA 220mA F0-08DAH-1 25mA 30mA F0-04DAH-2 25mA 30mA F0-08DAH-2 50mA 30mA F0-2AD2DA-2 100mA 40mA F0-4AD2DA-1 100mA none F0-4AD2DA-2 70mA none F0-04RTD 30mA none F0-04THM 45mA none D0-DEVNETS 530mA none H0-PSCM 250mA none H0-ECOM 250mA none H0-CTRIO 300mA none H0-ECOM100 1mA none F0-08SIM 250 mA none D0-DCM 150 mA none F0-CP128 1 mA none F0-08SIM
Programmable Controllers
Field I/O Software C-more & other HMI Drives Soft Starters Motors & Gearbox Steppers/ Servos Motor Controls Proximity Sensors Photo Sensors Limit Switches Encoders Current Sensors Pressure Sensors Temperature Sensors Pushbuttons/ Lights Process Relays/ Timers Comm. Terminal Blocks & Wiring power 24VDC power Current Required 5VDC (mA) (mA)
Power
D0-06DD1
600mA
280mA*
D0-16ND3
35mA
0
D0-10TD1
150mA
0
D0-08TR
280mA
0
Enclosures
F0-4AD2DA-1
100mA
0
Tools
D0-06LCD
50mA
0
Total Used
1215mA
280mA
A
285mA
20mA
Appendix
B
785mA note 1
Product Index
Remaining
Circuit Protection
Pneumatics
* Auxiliary 24 VDC used to power V+ terminal of D0-06DD1 sinking outputs. Part # Index
Note 1: If the PLC’s auxiliary 24 VDC power source is used to power the sinking outputs, use power choice A, above. Volume 13 w w w. a u to m at i o n d i re c t . c o m / d l 06
Programmable Controllers e2-29
Page 13
DL06 LCD Display The optional D0-06LCD (<--->) is a cost effective LCD display panel that is easy to install. This device is available exclusively for the DL06 PLCs.
One simple ladder instruction is used to set up the display. The LCD configuration instruction is available in DirectSOFT, version 4.0 or later.
16 X 2 backlit display
Note: The D2-HPP handheld programmer does not support DL06 LCD configuration.
The 16 character x 2 row display mounts directly on the face of the PLC. The LCD is backlit and is accessible using the seven function keys on the front of the display.
Monitor or change data values You can view V-memory registers, I/O status, PLC mode, or system errors without interrupting the PLC’s control function. Display messages required for alarm or monitoring purposes can be preprogrammed or imported as ASCII data.
Password protection Two layers of password protection prevent unauthorized changes to clock and calendar setup and V-memory data values. Individuals with password authorization can change clock, calender, Vmemory values, force bits on or off, etc.
The DL06 User Manual (D0-06USER-M) describes more fully the installation and operation of the D0-06LCD. Be sure to consult this manual before installing the DL06 LCD. The manual is available free on our Web site, or it can be purchased separately.
Snap-in installation The display installs easily into any model DL06 PLC.
Buzzer The piezo electric buzzer can be configured to provide pushbutton feedback.
Keypad navigation Seven function keys on the face of the LCD display provide navigation through messages or menu items. Messages fall into two categories: • Error messages • User-defined preprogrammed messages At power-up the default screen is displayed. The default screen can be userdefined. Seven menu choices allow you to view or change all accessible data values (see next page).
Note: Remove power to the PLC before installing or removing the LCD display. Remove the plastic cover (located between the input and output terminals) by sliding the cover to the left. In its place, slide in the LCD display until it snaps into place. Display or change individual bits (up to 16 bits per screen) or 32-bit double word values from V-memory.
Left
Up
Right
Down Escape
Enter Menu
Volume 13 e2-30
Programmable Controllers
1 - 80 0 - 633 - 0405
Page 14
DL06 LCD Display
Company Information Systems Overview
Menu choices
Ladder instruction
Pressing the Menu key takes you to the last accessed menu (or the first menu selection, if you haven’t previously accessed a menu). Each time you press the Menu key (or if you simply hold the menu key down) the display will step through all menu choices.
The LCD instruction in DirectSOFT gives the PLC programmer a convenient way to define screen messages. A literal string can be programmed using the LCD instruction. Embedding variables allows you to customize the messages for an application that involves changing values. The following example shows an embedded date and time on an alarm message:
There are seven built-in menus. Use the Menu key to locate the menu you need, and press the Enter key to view or change values.
Messages can also be retrieved from Vmemory and sent to the display. Select K1 or K2 to indicate which line you want to write to and select “From Vmemory” as the source of the string. Up to 16 characters of ASCII text can be displayed per line. In the example, K16 indicates that 16 bytes (8 words) of ASCII text is retrieved for display.
From the default screen or a message screen, press and hold the Menu key. The display will scroll through the following choices: M1 : PLC information M2 : System configuration M3 : Monitor M4 : Calendar R/W M5 : Password operation M6 : Error history read M7 : LCD test and set Make a menu selection by pressing the Enter key. Change data values using the direction arrow keys.
The top line (16 characters) is designated K1, and the second line is K2. The sample instructions on this page show how a message is developed. A permissive contact turns on the instruction block, which sends the message to the display.
Programmable Controllers
Field I/O Software C-more & other HMI Drives Soft Starters Motors & Gearbox Steppers/ Servos Motor Controls Proximity Sensors Photo Sensors Limit Switches Encoders
Message with embedded date and time
Current Sensors
Message from PLC memory
Pressure Sensors Temperature Sensors
Message programming examples
Pushbuttons/ Lights Process Relays/ Timers Comm. Terminal Blocks & Wiring Power
Simple text message
Circuit Protection
Message with embedded data
Enclosures Tools Pneumatics Appendix Product Index Part # Index
Volume 13 w w w. a u to m at i o n d i re c t . c o m / d l 06
Programmable Controllers e2-31
Page 15
Accessories DL05, DL06 and Option Module Accessories Part Number
Description
Price
D0-MC-BAT
Replacement battery for the D0-01MC memory option modules (DL05 only).
<--->
D2-BAT-1
Replacement RAM retentive memory backup battery for the DL06.
<--->
F0-IOCON
DL05 or DL06 replacement terminal blocks, 8-position, for the F0-04AD-1, F0-04AD-2, F0-2AD2DA-2, <---> F0-4AD2DA-1, F0-4AD2DA-2 and H0-CTRIO option modules (qty. 2).
or DL06 thermocouple option module F0-IOCON-THM DL05 replacement terminal block, quantity one. 12ft. (3.66m) RS-232C shielded networking cable without RTS connections for DL05 or DL06 RJ12 networking ports. Enables direct networking of two PLCs.
D0-CBL
DL05 accessory pack includes one each of the I/O terminal block, I/O terminal block cover, and option slot cover. DL06 replacement terminal blocks (qty. 2), terminal block covers (qty. 2), terminal block labels (qty. 2) and short bar (qty. 1). DL06 replacement option module slot covers (qty. 4), DL06 top covers (qty. 4), LCD slot cover, and lower access panel cover. DL05 or DL06 discrete I/O option module replacement terminal blocks, includes 13-position (qty. 2) and 10-position (qty. 2).
D0-ACC-1 D0-ACC-2 D0-ACC-3 D0-ACC-4
<--->
<--->
<---> <--->
DL05 option module slot cover, I/O terminal block, and I/O terminal block cover D0-ACC-1
<---> <--->
D0-06ADPTR
DL06 15-pin high density D-sub vertical adapter for <---> DL06 Port 2 serial communications port.
D2-FUSE-1 ZL-CMA15
DL05 or DL06 F0-04TRS replacement fuse
ZL-CMA15L
Discrete and analog option module terminal blocks D0-ACC-4
<--->
ZIPLink PLC communication adapter for 15-pin port <--->
DL06 replacement option module slot covers, DL06 top covers, LCD slot cover, and lower access panel cover D0-ACC-3
ZIPLink PLC communication adapter for 15-pin port with surge protection plus Power, Transmit, and <---> Receive LED indicators
ZL-CMA15 DL06 replacement terminal blocks, terminal block covers, terminal block labels and short bar D0-ACC-2
ZL-CMA15L See the Wiring Solutions section in this catalog for more inforamton.
DL06 15-pin high density D-sub port adapter D0-06ADPTR
Volume 13 e2-32
Programmable Controllers
1 - 80 0 - 633 - 0405