Page 134

Chapter 5: Standard RLL - Boolean Instructions

Or (OR) DS5 Implied HPP

Used

The Or instruction logically ors a normally open contact in parallel with another contact in a rung. The status of the contact will be the same state as the associated image register point or memory location.

Aaaa

Or Not (ORN) DS5 Implied The Or Not instruction logically ors a normally closed HPP

Used contact in parallel with another contact in a rung. The status of the contact will be opposite the state of the associated image register point or memory location. Operand Data Type

Aaaa

DL05 Range aaa

....................................A Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Y Control Relays . . . . . . . . . . . . . . . . . . . . . . . . . . C Stage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CT Special Relay . . . . . . . . . . . . . . . . . . . . . . . . . . SP

0–377 0–377 0–777 0–377 0–177 0–177 0–777

In the following Or example, when input X1 or X2 is on, output Y5 will energize. DirectSOFT 5 Direct SOFT32 X1

Handheld Programmer Keystrokes Y5

B

$ STR

OUT

1 C

Q OR

X2

GX OUT

2 F 5

ENT ENT ENT

In the following Or Not example, when input X1 is on or X2 is off, output Y5 will energize. DirectSOFT 5 Direct SOFT32 X1

Handheld Programmer Keystrokes Y5 OUT

X2

$

B STR

1

R ORN

C

GX OUT

F

2 5

ENT ENT ENT

DL05 Micro PLC User Manual, 6th Edition, Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–11

Page 135

Chapter 5: Standard RLL - Boolean Instructions

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Or Bit-of-Word (ORB) DS5 Implied HPP

Used

The Or Bit-of-Word instruction logically ors a normally open contact in parallel with another contact in a rung. Status of the contact will be the same state as the bit referenced in the associated memory location.

Aaaa.bb

Or Not Bit-of-Word (ORNB) DS5 Implied HPP

Used

The Or Not Bit-of-Word instruction logically ors a normally closed contact in parallel with another contact in a rung. Status of the contact will be opposite the state of the bit referenced in the associated memory location. Operand Data Type

DL05 Range

..................................... V-memory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A B PB aaa bb

See memory map See memory map

BCD, 0 to 15 BCD, 0 to 15

In the following Or Bit-of-Word example, when input X1 or bit 7 of V1400 is on, output Y7 will energize. DirectSOFT 5 DirectSOFT32 X1

Y7 OUT

B1400.7 Handheld Programmer Keystrokes STR OR

1

ENT

SHFT

B

K

7

ENT

7

ENT

OUT

V

1

4

0

0

In the following Or Bit-of-Word example, when input X1 is on or bit 7 of V1400 is off, output Y7 will energize. DirectSOFT 5

DirectSOFT32 X1

Y7 OUT

B1400.7 Handheld Programmer Keystrokes STR ORN

OUT

5–12

Aaaa.bb

1

ENT

SHFT

B

K

7

ENT

7

ENT

V

DL05 Micro PLC User Manual, 6th Edition, Rev. A

1

4

0

0

Page 136

Chapter 5: Standard RLL - Boolean Instructions

And (AND) DS5 Implied The And instruction logically ands a normally open HPP

Used

Aaaa contact in series with another contact in a rung. The status of the contact will be the same state as the associated image register point or memory location.

And Not (ANDN) DS5 Implied HPP

Used

The And Not instruction logically ands a normally closed contact in series with another contact in a rung. The status of the contact will be opposite the state of the associated image register point or memory location.

Aaaa

Operand Data Type

DL05 Range

....................................A aaa

Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Y Control Relays . . . . . . . . . . . . . . . . . . . . . . . . . . C Stage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CT Special Relay . . . . . . . . . . . . . . . . . . . . . . . . . . SP

0–377 0–377 0–777 0–377 0–177 0–177 0–777

In the following And example, when input X1 and X2 are on output Y5 will energize.

DirectSOFT 5 Direct SOFT32 X1

Handheld Programmer Keystrokes X2

Y5 OUT

$

B STR

1

V AND

C

GX OUT

F

2 5

ENT ENT ENT

In the following And Not example, when input X1 is on and X2 is off output Y5 will energize. DirectSOFT 5 Direct SOFT32 X1

Handheld Programmer Keystrokes X2

Y5 OUT

$

B STR

1

W ANDN

C

GX OUT

F

2 5

ENT ENT ENT

DL05 Micro PLC User Manual, 6th Edition, Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–13

Page 137

Chapter 5: Standard RLL - Boolean Instructions

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

And Bit-of-Word (ANDB) DS5 Implied The And Bit-of-Word instruction logically ands a HPP

Used

Aaaa.bb normally open contact in series with another contact in a rung. The status of the contact will be the same state as the bit referenced in the associated memory location.

And Not Bit-of-Word (ANDNB) DS5 Implied HPP

Used

The And Not Bit-of-Word instruction logically ands a normally closed contact in series with another contact in a rung. The status of the contact will be opposite the state of the bit referenced in the associated memory location. Operand Data Type

DL05 Range

..................................... V-memory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A B PB aaa bb

See memory map See memory map

BCD, 0 to 15 BCD, 0 to 15

In the following And Bit-of-Word example, when input X1 and bit 4 of V1400 is on output Y5 will energize. DirectSOFT 5 X1

B1400.4

Y5 OUT

Handheld Programmer Keystrokes STR AND

1

ENT

SHFT

B

K

4

ENT

5

ENT

OUT

V

1

4

0

0

In the following And Not Bit-of-Word example, when input X1 is on and bit 4 of V1400 is off output Y5 will energize. DirectSOFT 5 X1

Y5

B1400.4

OUT

Handheld Programmer Keystrokes STR ANDN

OUT

5–14

Aaaa.bb

1

ENT

SHFT

B

K

4

ENT

V

5

ENT

DL05 Micro PLC User Manual, 6th Edition, Rev. A

1

4

0

0

Page 138

Chapter 5: Standard RLL - Boolean Instructions

And Store (AND STR)

1 2 3 Or Store (OR STR) The Or Store instruction logically ors two branches of a rung in parallel. Both branches 4 must begin with the Store instruction. 5 In the following And Store example, the branch consisting of contacts X2, X3, and X4 have been anded with the branch consisting of contact 6 X1. 7 8 9 10 11 12 In the following Or Store example, the branch consisting of X1 and X2 have been ored with the branch consisting of X3 and X4. 13 14 A B C D

DS5 Implied HPP

Used

The And Store instruction logically ands two branches of a rung in series. Both branches must begin with the Store instruction.

OUT

2

1

1

DS5 Implied HPP

OUT

Used

2

DirectSOFT 5 Direct SOFT32 X1

Handheld Programmer Keystrokes

X3

X2

Y5

$

B

STR

OUT

1

$

C

STR

X4

2

V AND

D

Q

E

3

OR

L ANDST

4

X1

ENT ENT

F

5

ENT

Handheld Programmer Keystrokes

X2

Y5

$

X4

B

STR

OUT

X3

ENT

ENT

GX OUT

DirectSOFT 5 Direct SOFT32

ENT

1

V AND

C

$

D

2

STR

3

V AND

M ORST GX OUT

E

4

ENT ENT ENT ENT

ENT

F

5

ENT

DL05 Micro PLC User Manual, 6th Edition, Rev. A

5–15

Page 139

Chapter 5: Standard RLL - Boolean Instructions

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Out (OUT) DS5

Used

HPP

Used

Aaaa The Out instruction reflects the status of the rung (on/off ) and OUT outputs the discrete (on/off ) state to the specified image register point or memory location. Multiple Out instructions referencing the same discrete location should not be used since only the last Out instruction in the program will control the physical output point. Instead, use the next instruction, the Or Out.

Operand Data Type

DL05 Range aaa

....................................A Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Y Control Relays . . . . . . . . . . . . . . . . . . . . . . . . . . C

0–377 0–377 0–777

In the following Out example, when input X1 is on, output Y2 and Y5 will energize. DirectSOFT 5 Direct SOFT32

Handheld Programmer Keystrokes

X1

Y2

$

B STR

OUT Y5 OUT

1

GX OUT

C

GX OUT

F

2 5

ENT ENT ENT

Or Out (OROUT) DS5

Used

HPP

Used

5–16

The Or Out instruction allows more than one rung of discrete logic to control a single output. Multiple Or Out instructions referencing the same output coil may be used, since all contacts controlling the output are logically ORed together. If the status of any rung is on, the output will also be on. Operand Data Type

A aaa OR OUT

DL05 Range

....................................A aaa

Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Y Control Relays . . . . . . . . . . . . . . . . . . . . . . . . . . C

0–177 0–177 0–777

In the following example, when X1 or X4 is on, Y2 will energize. DirectSOFT 5 Direct SOFT32 X1

Handheld Programmer Keystrokes Y2

$

B STR

OR OUT

O INST#

1 D

F 3

5 E

$ STR X4

Y2 OR OUT

O INST#

4 D

F 3

DL05 Micro PLC User Manual, 6th Edition, Rev. A

5

ENT ENT

ENT

C

ENT

C

2

ENT

ENT ENT

2

ENT

Page 140

Chapter 5: Standard RLL - Boolean Instructions

Out Bit-of-Word (OUTB) DS5

Used

HPP

Used

1 2 3 Operand Data Type DL05 Range 4 aaa bb 5 In the following Out Bit-of-Word example, when input X1 is on, bit 3 of V1400 and bit 6 of 6 V1401 will turn on. 7 8 9 10 11 12 The following Out Bit-of-Word example contains two Out Bit-of-Word instructions using the same bit in the same memory word. The final state bit 3 of V1400 is ultimately controlled 13 by the last rung of logic referencing it. X1 will override the logic state controlled by X0. To avoid this situation, multiple outputs using the same location must not be used in 14 programming. A B C D The Out Bit-of-Word instruction reflects the status of the rung (on/off ) and outputs the discrete (on/off ) state to the specified bit in the referenced memory location. Multiple Out Bit-of-Word instructions referencing the same bit of the same word generally should not be used since only the last Out instruction in the program will control the status of the bit.

....................................A V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B Pointer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PB

Aaaa.bb OUT

See memory map See memory map

BCD, 0 to 15 BCD, 0 to 15

DirectSOFT 5

X1

B1400.3 OUT

B1401.6 OUT

Handheld Programmer Keystrokes STR

OUT

OUT

1

SHFT

B

K

3

SHFT

B

K

6

ENT

V

1

4

0

0

V

1

4

0

1

ENT

ENT location must not be used in programming. X0

B1400.3 OUT

X1

B1400.3 OUT

DL05 Micro PLC User Manual, 6th Edition, Rev. A

5–17

Page 141

Chapter 5: Standard RLL - Boolean Instructions

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Not (NOT) DS5

Used

HPP

Used

The Not instruction inverts the status of the rung at the point of the instruction. In the following example when X1 is off, Y2 will energize. This is because the Not instruction inverts the status of the rung at the Not instruction. DirectSOFT 5 DirectSOFT32

Handheld Programmer Keystrokes

X1

$

Y2

B STR

ENT

1

OUT

N TMR

SHFT GX OUT

O INST#

T MLR

C

ENT

2

ENT

NOTE: DirectSOFT Release 1.1i and later supports the use of the NOT instruction. The above example rung is merely intended to show the visual representation of the NOT instruction. The rung cannot be created or displayed in DirectSOFT versions earlier than 1.1i.

Positive Differential (PD) DS5

Used

HPP

Used

5–18

The Positive Differential instruction is typically known as a one shot. When the input logic produces an off to on transition, the output will energize for one CPU scan.

A aaa PD

Operand Data Type

DL05 Range aaa

....................................A Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Y Control Relays . . . . . . . . . . . . . . . . . . . . . . . . . . C

0–377 0–377 0–777

In the following example, every time X1 makes an off to on transition, C0 will energize for one scan. DirectSOFT 5 DirectSOFT32 X1

Handheld Programmer Keystrokes C0

$

B STR

PD SHFT

DL05 Micro PLC User Manual, 6th Edition, Rev. A

1 P CV

SHFT

ENT D

A 3

0

Page 142

Chapter 5: Standard RLL - Boolean Instructions

Store Positive Differential (STRPD) DS5

Used

HPP

Used

DS5

Used

HPP

Used

1 2 3 4 5 Store Negative Differential (STRND) 6 The Store Negative Differential instruction begins a new rung or an additional branch in a rung with a 7 normally closed contact. The contact closes for one CPU scan when the state of the associated image register point makes an On-to-Off transition. 8 Thereafter, the contact remains open until the next On-to-Off transition (the symbol inside the contact 9 represents the transition). Operand Data Type DL05 Range 10 aaa 11 12 13 In the following example, each time X1 is makes an Off-to-On transition, Y4 will energize for one scan. 14 A B In the following example, each time X1 is makes an On-to-Off transition, Y4 will energize for one scan. C D The Store Positive Differential instruction begins a new rung or an additional branch in a rung with a normally open contact. The contact closes for one CPU scan when the state of the associated image register point makes an Off-to-On transition. Thereafter, the contact remains open until the next Off-to-On transition (the symbol inside the contact represents the transition). This function is sometimes called a “one-shot”. This contact will also close on a program-to-run transition if it is within a retentative range and on before the PLC mode transition.

Aaaa

Aaaa

....................................A Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Y Control Relays . . . . . . . . . . . . . . . . . . . . . . . . . . C Stage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CT

0–377 0–377 0–777 0–377 0–177 0–177

DirectSOFT 5

Handheld Programmer Keystrokes

DirectSOFT32 X1

Y4

OUT

DirectSOFT 5

STR

SHFT

GX OUT

D

P

CV

E

4

B

3

1

ENT

ENT

Handheld Programmer Keystrokes

DirectSOFT32 X1

$

Y4

OUT

$

STR

GX OUT

SHFT

N TMR E 4

B

D

3

1

ENT

ENT

DL05 Micro PLC User Manual, 6th Edition, Rev. A

5–19

Page 143

Chapter 5: Standard RLL - Boolean Instructions

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Or Positive Differential (ORPD) DS5 Implied The Or Positive Differential instruction logically ors a contact HPP

Used in parallel with another contact in a rung. The status of the contact will be open until the associated image register point makes an Off-to-On transition, closing it for one CPU scan. Thereafter, it remains open until another Off-to-On transition.

Aaaa

Or Negative Differential (ORND) DS5 Implied The Or Negative Differential instruction logically ors a HPP

5–20

Used contact in parallel with another contact in a rung. The status of the contact will be open until the associated image register point makes an On-to-Off transition, closing it for one CPU scan. Thereafter, it remains open until another On-to-Off transition.

Aaaa

DL05 Range

Operand Data Type aaa

....................................A Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . X Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Y Control Relays . . . . . . . . . . . . . . . . . . . . . . . . . . C Stage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CT

0–377 0–377 0–777 0–377 0–177 0–177

In the following example, Y 5 will energize whenever X1 is on, or for one CPU scan when X2 transitions from Off to On. DirectSOFT 5 DirectSOFT32 X1

Handheld Programmer Keystrokes $

B

Y5

STR

OUT

Q OR

X2

ENT

1 SHFT

P CV

3

F

GX OUT

C

D

2

ENT

ENT

5

In the following example, Y 5 will energize whenever X1 is on, or for one CPU scan when X2 transitions from On to Off. DirectSOFT 5

Handheld Programmer Keystrokes

DirectSOFT32 X1

Y5 OUT

B

$ STR Q OR

X2

GX OUT

DL05 Micro PLC User Manual, 6th Edition, Rev. A

1 SHFT

N TMR F 5

ENT D

C 3

ENT

2