Manual · AutomationDirect
DL05 Micro PLC User Manual, Volume 1 of 2
Manual379 pagesPDF 5.8 MB
User manual, volume 1 of 2, for the AutomationDirect DL05 Micro PLC family, including the D0-05AA, covering installation, wiring and programming.
Covers · 1 model
The models it covers
Summary
What is in it
Volume 1 of the AutomationDirect DL05 Micro PLC User Manual. It covers getting started and PLC checkout, safety, mounting, wiring guidelines and I/O wiring diagrams for each DL05 model (D0-05AR, D0-05DR, D0-05AD, D0-05DD, D0-05AA, D0-05DA and the DC-powered versions), CPU specifications and operation, the memory map, configuring the comm ports for Modbus and DirectNET networking, and the standard RLL and Intelligent Box (IBox) instructions.
Its parts
- Getting Started
- Installation, Wiring, and Specifications
- CPU Specifications and Operation
- Configuration and Connections
- Standard RLL and Intelligent Box (IBox) Instructions
From the manual
Key facts from this manual
Each line names its page in the PDF.
AutomationDirect DL05 Micro PLC User Manual, Volume 1 of 2 (manual D0-USER-M, sixth edition, revision A, dated 4/10). It covers all eight DL05 versions: D0–05AR, D0–05DR, D0–05AD, D0–05DD, D0–05AA, D0–05DA, D0–05DR–D and D0–05DD–D. It walks through installation, wiring and specifications, CPU setup and operation, network connections, and the RLL and IBox instruction set.
- Device
- D0-05AA: DL05 Micro PLC with eight AC inputs and six AC outputs p. 63
- Inputs
- D0-05AA: AC inputs, 120 V AC only, in two banks of four, each bank with an isolated common p. 20, 63
- Outputs
- D0-05AA: two banks of three triac switches, each bank with a common terminal p. 63
- Power
- D0-05AA: AC external power, 95-240 VAC, 30 VA maximum p. 63, 64
- Memory
- 6K words: 2K words of ladder memory and 4K words of V-memory; program stored in FLASH p. 73
- Communication ports
- Two built-in RS232C ports on RJ-12 jacks; port 1 fixed at 9600 baud, port 2 from 300 to 38.4K baud p. 75
- Programming cable
- D2–DSCBL to COM port 1 (comes with the HPP); replacement cable DV–1000CBL p. 21
- Programming tools
- DirectSOFT version 2.4 or later, or D2–HPP handheld programmer with firmware 1.09 or later p. 18
- Memory backup
- No battery; a super capacitor keeps values briefly after power loss; battery backup only with the D0–01MC memory cartridge p. 80
- Expansion
- Stand-alone PLC with one option module slot; no expansion bases p. 25
- Instructions
- Over 120 instructions, close to the DL240 CPU set p. 17, 73
- Fixed I/O
- Fourteen fixed I/O points: eight discrete inputs and six outputs p. 73
What this manual walks you through
- Wiring switches, power and a programming device for a first checkout p. 20, 21
- Unit dimensions and mounting hole locations p. 34
- Field wiring of the D0-05AA inputs and outputs p. 63
- Reading the status LEDs and using the mode switch p. 77
- Setting retentive memory ranges p. 80
- Configuring the ports for Modbus RTU or DirectNET networks p. 109
- RS-422 multi-drop networking with converters p. 110
Good to know
- On the AC input versions the discrete inputs accept 120 VAC nominal only; do not wire the example switches to 240 VAC units. p. 20
- The 5V pins on the communication ports are rated at 200mA maximum. p. 75
- Switching to RUN with no program loaded produces a fatal error, cleared by cycling power. p. 77
- RS-232 links reach up to 15 meters; the RS-422 cable distance is up to 1000 meters. p. 109, 110
Questions this manual answers
What programming cable does the DL05 use?
Cable D2–DSCBL connects to COM port 1 and comes with the handheld programmer; the replacement cable is DV–1000CBL. p. 21
Does the DL05 have a battery?
No. A super capacitor keeps values for a short time after power loss; battery backup needs the D0–01MC memory cartridge. p. 80
Can a DL05 be expanded?
Not with expansion bases. It is a stand-alone PLC with one slot for an option module. p. 25
What baud rates do the DL05 ports support?
Port 1 is fixed at 9600 baud; port 2 runs from 300 to 38,400 baud. p. 75
Can the DL05 accept 5VDC inputs?
No, 5 volts is below the DC input ON threshold, but many TTL circuits can drive the inputs wired as open collector (sinking) inputs. p. 26
Contents
Chapters and sections
Each line opens the PDF at its page.
- DL05 Micro PLC User Manual Volume 1 of 21
- Warning3
- Publication History5
- Volume One: Table of Contents7
- Chapter 1: Getting Started14
- Chapter 2: Installation, Wiring and Specifications28
- Safety Guidelines29
- Orientation to DL05 Front Panel32
- Mounting Guidelines34
- Wiring Guidelines38
- System Wiring Strategies41
- Wiring Diagrams and Specifications55
- D0–05AR I/O Wiring Diagram55
- D0–05DR I/O Wiring Diagram57
- D0–05AD I/O Wiring Diagram59
- D0–05DD I/O Wiring Diagram61
- D0–05AA I/O Wiring Diagram63
- D0–05DA I/O Wiring Diagram65
- D0–05DR-D I/O Wiring Diagram67
- D0–05DD–D I/O Wiring Diagram69
- Glossary of Specification Terms71
- Chapter 3: CPU Specifications and Operation72
34 more lines, from page 93 on
- Memory Map93
- Chapter 4: Configuration and Connections106
- Chapter 5: Standard RLL and Intelligent Box Instructions124
- Introduction125
- Using Boolean Instructions127
- Boolean Instructions132
- Comparative Boolean148
- Immediate Instructions154
- Timer, Counter and Shift Register Instructions158
- Accumulator/Stack Load and Output Data Instructions171
- Logical Instructions (Accumulator)183
- Math Instructions191
- Bit Operation Instructions205
- Number Conversion Instructions (Accumulator)210
- Table Instructions219
- CPU Control Instructions222
- Program Control Instructions224
- Interrupt Instructions231
- Message Instructions234
- Intelligent I/O Instructions241
- Network Instructions243
- Intelligent Box (IBox) Instructions247
The whole text · 40 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 41-4
- Pages 5 to 135-13
- Chapter 1: Getting Started14-27
- Chapter 2: Installation, Wiring and Specifications, pages 28 to 3628-36
- Chapter 2: Installation, Wiring and Specifications, pages 37 to 4537-45
- Chapter 2: Installation, Wiring and Specifications, pages 46 to 5446-54
- Chapter 2: Installation, Wiring and Specifications, pages 55 to 6355-63
- Chapter 2: Installation, Wiring and Specifications, pages 64 to 7164-71
- Chapter 3: CPU Specifications and Operation, pages 72 to 8072-80
- Chapter 3: CPU Specifications and Operation, pages 81 to 8981-89
- Chapter 3: CPU Specifications and Operation, pages 90 to 9890-98
- Chapter 3: CPU Specifications and Operation, pages 99 to 10599-105
- Chapter 4: Configuration and Connections, pages 106 to 114106-114
- Chapter 4: Configuration and Connections, pages 115 to 123115-123
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 124 to 133124-133
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 134 to 143134-143
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 144 to 153144-153
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 154 to 163154-163
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 164 to 173164-173
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 174 to 183174-183
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 184 to 193184-193
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 194 to 203194-203
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 204 to 213204-213
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 214 to 223214-223
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 224 to 233224-233
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 234 to 243234-243
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 244 to 253244-253
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 254 to 263254-263
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 264 to 273264-273
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 274 to 283274-283
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 284 to 293284-293
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 294 to 303294-303
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 304 to 313304-313
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 314 to 323314-323
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 324 to 333324-333
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 334 to 343334-343
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 344 to 353344-353
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 354 to 363354-363
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 364 to 373364-373
- Chapter 5: Standard RLL and Intelligent Box Instructions, pages 374 to 379374-379
The file