DL05 Micro PLC User Manual, Volume 1 of 2: Chapter 2: Installation, Wiring and Specifications, pages 46 to 54

Pages 46 to 54 of 379, from DL05 Micro PLC User Manual, Volume 1 of 2

The original document is the PDF (5.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the AutomationDirect D0-05AA

Page 46

Chapter 2: Installation, Wiring, and Specifications In the next example we connect a PLC DC output point to the sinking input of a field device. This is a bit tricky, because both the PLC output and field device input are sinking type. Since the circuit must have one sourcing and one sinking device, we add sourcing capability to the PLC output by using a pull-up resistor. In the circuit below, we connect Rpull-up from the output to the DC output circuit power input.

A 2 3 R D R 5 6 NOTE 1: DO NOT attempt to drive a heavy load (>25 mA) with this pull-up method. 7 NOTE 2: Using the pull-up resistor to implement a sourcing output has the effect of inverting the output point logic. In other words, the field device input is energized when the PLC output is OFF, from a ladder logic point-of-view. Your ladder program must comprehend this and generate an inverted output. Or, you 8 may choose to cancel the effect of the inversion elsewhere, such as in the field device. It is important to choose the correct value of Rpull-up. In order to do so, we need to know 9 the nominal input current to the field device (I input) when the input is energized. If this value is not known, it can be calculated as shown (a typical value is 15 mA). Then use I input 10 and the voltage of the external supply to compute Rpull-up. Then calculate the power Ppull-up (in watts), in order to size Rpull-up properly. 11 V I = R 12 2 V V – 0.7 R P = = –R 13 R I The drawing below shows the actual wiring of the DL05 Micro PLC to the supply and 14 pull-up resistor. A B C D PLC DC Output +DC pwr

Power

Field Device pull-up (sourcing)

(sinking)

Output

+

Input (sinking)

–

Ground input

Supply

Common input input (turn–on)

input supply supply pull-up input pull-up pullup input

Common

–

Output

Supply +

DL05 Micro PLC User Manual, 6th Edition, Rev. A

2–19

Page 47

Chapter 2: Installation, Wiring, and Specifications

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D 2–20

Relay Output Wiring Methods The D0–05AR and the D0–05DR models feature relay outputs. Relays are best for the following applications: • Loads that require higher currents than the solid-state DL05 outputs can deliver • Cost-sensitive applications • Some output channels need isolation from other outputs (such as when some loads require AC while others require DC)

Some applications in which NOT to use relays: • Loads that require currents under 10 mA • Loads which must be switched at high speed and duty cycle

Assuming relays are right for your application, we’re now ready to explore various ways to wire relay outputs to the loads. Note that there are six normally-open SPST relays available. They are organized with three relays per common. The figure below shows the relays and the internal wiring of the PLC. Note that each group is isolated from the other group of outputs. Y0 Common Y1

Y2

Y3

Y4 Common Y5

In the circuit below, all loads use the same AC power supply which powers the DL05 PLC. In this example, all commons are connected together.

Fuse or Circuit Breaker

Line Ground Neutral

Output Point Wiring

In the circuit on the following page, loads for Y0 – Y2 use the same AC power supply which powers the DL05 PLC. Loads for Y3 – Y5 use a separate DC supply. In this example, the commons are separated according to which supply powers the associated load.

DL05 Micro PLC User Manual, 6th Edition, Rev. A

Page 48

Chapter 2: Installation, Wiring, and Specifications

A 2 3 D 5 Surge Suppression For Inductive Loads Inductive load devices (devices with a coil) generate transient voltages when de-energized with 6 a relay contact. When a relay contact is closed it “bounces”, which energizes and de-energizes the coil until the “bouncing” stops. The transient voltages generated are much larger in amplitude than the supply voltage, especially with a DC supply voltage. 7 When switching a DC-supplied inductive load the full supply voltage is always present when the relay contact opens (or “bounces”). When switching an AC-supplied inductive load there 8 will be times when the relay contact will open (or “bounce”) when the AC sine wave is at zero crossing. If the voltage is not zero when the relay contact opens, there is energy stored in the inductor that is released when the voltage to the inductor is suddenly removed. This release of 9 energy is the cause of the transient voltages. 10 When inductive load devices (motors, motor starters, interposing relays, solenoids, valves, etc.) are controlled with relay contacts, it is recommended that a surge suppression device be connected directly across the coil of the field device. If the inductive device has plug-type 11 connectors, the suppression device can be installed on the terminal block of the relay output. Transient Voltage Suppressors (TVS or transorb) provide the best surge and transient 12 suppression of AC and DC powered coils, providing the fastest response with the smallest overshoot. 13 Metal Oxide Varistors (MOV) provide the next best surge and transient suppression of AC and DC powered coils. 14 For example, the waveform in the figure below shows the energy released when opening a contact switching a 24 VDC solenoid. Notice the large voltage spike. A B C D Fuse or Circuit Breaker

+

Line

Ground

–

Neutral

Output Point Wiring

+24 VDC

–24 VDC

+24 VDC

Module Relay Contact

–324 VDC

DL05 Micro PLC User Manual, 6th Edition, Rev. A

2–21

Page 49

Chapter 2: Installation, Wiring, and Specifications

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D 2–22

This figure shows the same circuit with a transorb (TVS) across the coil. Notice that the voltage spike is significantly reduced. +24 VDC –24 VDC

+24 VDC –42 VDC

Module Relay Contact

Use the following table to help select a TVS or MOV suppressor for your application based on the inductive load voltage. Surge Suppressors Vendor / Catalog

Type

Inductive Load Voltage

Part Number

AutomationDirect Transient Voltage Suppressors, LiteOn Diodes; from Digi-Key Catalog: Phone: 1-800-344-4539

TVS TVS TVS TVS Diode

110/120 VAC 24 VDC 220/240 VAC 12/24 VDC 12/24 VDC

ZL-TD8-120 ZL-TD8-24 P6KE350CA P6K30CAGICT–ND 1N4004CT–ND

Digi-key www.digikey.com

MOV MOV

110/120 VAC 220/240 VAC

Contact Digi-Key, Corp.

Prolonging Relay Contact Life Relay contacts wear according to the amount of relay switching, amount of spark created at the time of open or closure, and presence of airborne contaminants. There are some steps you can take to help prolong the life of relay contacts, such as switching the relay on or off only when it is necessary, and if possible, switching the load on or off at a time when it will draw the least current. Also, take measures to suppress inductive voltage spikes from inductive DC loads such as contactors and solenoids. PLC Relay Output

Inductive Field Device Input

Output

R C Common

Supply

+

–

Common

Adding external contact protection may extend relay life beyond the number of contact cycles listed in the specification tables for relay modules. High current inductive loads such as clutches, brakes, motors, direct-acting solenoid valves and motor starters will benefit the most from external contact protection. When using an RC network, locate it close to the relay module output connector. To find the values for the RC snubber network, first determine the voltage across the contacts when open, and the current through them when closed. If the load supply is AC, then convert the current and voltage values to peak values.

DL05 Micro PLC User Manual, 6th Edition, Rev. A

Page 50

Chapter 2: Installation, Wiring, and Specifications Now you are ready to calculate values for R and C, according to the formulas:

A V 50 I , where x = 1 + C (μF) = R (Ω) = 2 10 x I V 10 C minimum = 0.001 μF, the voltage rating of C must be ≥ V, non-polarized 3 R minimum = 0.5 Ω, 1/2 W, tolerance is ± 5% D For example, suppose a relay contact drives a load at 120VAC, 1/2 A. Since this example has an AC power source, first calculate the peak values: 5 =I x 1.414, = 0.5 x 1.414 = 0.707 Amperes I V =V x 1.414 = 120 x 1.414 = 169.7 Volts 6 Now, finding the values of R and C,: 7 0.707 I = C (μF) = = 0.05 μF, voltage rating ≥ 170 Volts 8 10 10 V 50 9 , where x = 1 + R (Ω) = 10 x I V 10 50 169.7 = 1.29 x= 1+ R (Ω) = = 26 Ω, 1/2 W, ± 5% 169.7 10 x 0.707 11 For inductive loads in DC circuits we recommend using a suppression diode as shown in the diagram. When the load is energized the diode is reverse-biased (high impedance). When the 12 load is turned off, energy stored in its coil is released in the form of a negative-going voltage spike. At this moment the diode is forward-biased (low impedance) and shunts the energy to 13 ground. This protects the relay contacts from the high voltage arc that would occur just as the contacts are opening. 14 WARNING: DO NOT use this circuit with an AC power supply. Place the diode as close to the inductive field device as possible. Use a diode with a peak A inverse voltage rating (PIV) at least 100 PIV, 3A forward current or larger. Use a fast-recovery type (such as Schottky type). DO NOT use a small-signal diode such as 1N914, 1N941, etc. B Be sure the diode is in the circuit correctly before operation. If installed backwards, it will short-circuit the supply when the relay energizes. C DO NOT use this circuit with an AC power supply. D 2 x peak rms peak

2 rms

2 x

1.29

DL05 Micro PLC User Manual, 6th Edition, Rev. A

2–23

Page 51

Chapter 2: Installation, Wiring, and Specifications

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

DC Input Wiring Methods

Input

DL05 Micro PLCs with DC inputs are particularly flexible because they can be either sinking or sourcing. The dual diodes (shown to the right) allow 10.8 – 26.4 VDC. The target applications are +12 VDC and +24 VDC. You can actually wire half of Common the inputs as DC sinking and the other half as DC sourcing. Inputs grouped by a common must be all sinking or all sourcing. In the first and simplest example below, all commons are connected together and all inputs are sinking.

– +24 VDC

+

In the next example, the first four inputs are sinking, and the last four are sourcing.

–

+

+

–

+12 VDC

+24 VDC

2–24

PLC DC Input

DL05 Micro PLC User Manual, 6th Edition, Rev. A

Page 52

Chapter 2: Installation, Wiring, and Specifications

DC Output Wiring Methods

A 2 • There is only one electrical common for all six outputs. All six outputs belong to one bank. • The output switches are current-sinking only. However, you can still use different DC voltages from 3 one load to another. • The output circuit inside the PLC requires external power. The supply (–) must be connected to a D common terminal, and the supply (+) connects the right-most terminal on the upper connector. In the example below, all six outputs share a common supply. 5 6 7 8 9 – + 10 In the next example below, the outputs have “split” supplies. The first three outputs are using 11 a +12 VDC supply, and the last three are using a +24 VDC supply. However, you can split the outputs among any number of supplies, as long as: 12 • all supply voltages are within the specified range • all output points are wired as sinking 13 • all source (–) terminals are connected together 14 A B C D – – DL05 DC output circuits are high-performance transistor switches with low on-resistance and fast switching times. Please note the following characteristics which are unique to the DC output type:

+24 VDC

Output Point Wiring

+12 VDC

+24 VDC

+

+ Output Point Wiring

DL05 Micro PLC User Manual, 6th Edition, Rev. A

2–25

Page 53

Chapter 2: Installation, Wiring, and Specifications

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

High Speed I/O Wiring Methods DL05 versions with DC type input or output points contain a dedicated High-Speed I/O circuit (HSIO). The circuit configuration is programmable, and it processes select I/O points independently from the CPU scan. Chapter 3 discusses the programming options for HSIO. While the HSIO circuit has six modes, we show wiring diagrams for two of the most popular modes in this chapter. The high-speed input interfaces to points X0 – X2. Properly configured, the DL05 can count quadrature pulses at up to 5 kHz.

Signal Common Phase B +

Phase A

12 – 24 VDC –

Encoder Input Wiring

Encoder

DL05 versions with DC type output points can use the High Speed I/O Pulse Output feature. It can generate high-speed pulses up to 7 KHz for specialized control such as stepper motor / intelligent drive systems. Output Y0 and Y1 can generate pulse and direction signals, or it can generate CCW and CW pulse signals respectively. See Appendix E on high-speed input and pulse output options.

+ Signal Common Motor

Amplifier

Pulse Direction

Pulse Output Wiring Power Input

2–26

DL05 Micro PLC User Manual, 6th Edition, Rev. A

+24 VDC

–

Page 54

Chapter 2: Installation, Wiring, and Specifications

This page is intentionally left blank.

DL05 Micro PLC User Manual, 6th Edition, Rev. A

A 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D 2–27